Bit 05, ON 3/OFF 3
When bit 02 of the control word is 0, bit 05 = 0.
When bit 02 of the control word is 1, bit 05 = 1.
Bit 06, start possible/start not possible
If
[1] PROFIdrive
has been selected in
parameter 8-10 Control Word Profile
, bit 06 is 1 after a
switch-off acknowledgement, after activation of OFF2 or
OFF3, and after switching on the mains voltage. To reset
Start not possible
, set bit 00 of the control word to 0, and
bits 01, 02, and 10 to 1.
Bit 07, no warning/warning
Bit 07 = 0 means that there are no warnings.
Bit 07 = 1 means that a warning has occurred.
Bit 08, speed ≠ reference/speed = reference
When bit 08 = 0, the current speed of the motor deviates
from the set speed reference value. The deviation may
occur, for example, when the speed is being changed
during start/stop through ramp up/down.
When bit 08 = 1, the current speed of the motor
corresponds to the set speed reference value.
Bit 09, local operation/bus control
Bit 09 = 0 indicates that the frequency converter has been
stopped with
[Stop]
on the LCP, or that
[0] Linked to hand
or
[2] Local
has been selected in
parameter 3-13 Reference
Site
.
When bit 09 = 1, the frequency converter can be
controlled through the serial interface.
Bit 10, out of frequency limit/frequency limit OK
When bit 10 = 0, the output frequency is outside the limits
set in
parameter 4-52 Warning Speed Low
and
parameter 4-53 Warning Speed High
.
When bit 10 = 1, the output frequency is within the
indicated limits.
Bit 11, no operation/operation
When bit 11 = 0, the motor does not turn.
When bit 11 = 1, the frequency converter has a start
signal, or the output frequency is higher than 0 Hz.
Bit 12, drive OK/stopped, auto-start
When bit 12 = 0, there is no temporary overload of the
inverter.
When bit 12 = 1, the frequency converter has stopped due
to overload. However, the frequency converter has not
switched off (tripped) and starts again after the overload
has ended.
Bit 13, voltage OK/voltage exceeded
When bit 13 = 0, the voltage limits of the frequency
converter are not exceeded.
When bit 13 = 1, the direct voltage in the DC link of the
frequency converter is too low or too high.
Bit 14, torque OK/torque exceeded
When bit 14 = 0, the motor torque is below the limit
selected in
parameter 4-16 Torque Limit Motor Mode
and
parameter 4-17 Torque Limit Generator Mode
.
When bit 14 = 1, the limit selected in
parameter 4-16 Torque Limit Motor Mode
or
parameter 4-17 Torque Limit Generator Mode
is exceeded.
Bit 15, thermal OK/limit exceeded
When bit 15 = 0, the timers for the motor thermal
protection and thermal frequency converter protection
have not exceeded 100%.
When bit 15 = 1, one of the limits has exceeded 100%.
Control
PROFINET
16
Danfoss A/S © 04/2017 All rights reserved.
MG06G102
4
4