Dirty heatsink
•
Blocked air flow around the unit
•
Damaged heatsink fan
WARNING/ALARM 309, Mains earth fault
An earth (ground) fault was detected, measured by the CT
mains currents.
The sum current from three mains CTs is too high. The
earth fault must be detected at every sample during a
period of 400ms, for Alarm 309 to be reported.
Troubleshooting:
Check the installation mains CTs and wiring
Replace the AFC card
ALARM 310, RTDC buffer full
Contact supplier.
ALARM 311, Switch freq. limit
The average switching frequency of the unit exceeded the
limit.
If the actual switching frequency exceeds 6 kHz for 10
electrical cycles, Alarm 311 is reported.
Service parameter P98-21 displays the actual switching
frequency. NOTE: Do not change any service parameters
unless directed to do so in this service manual.
Troubleshooting
Perform the Mains Resonance Test ()
ALARM 312, CT range
Current transformer measurement limitation was detected.
Verify that the CTs used are of an appropriate ratio.
ALARM 314, Auto CT interrupt
Auto CT detection was interrupted by the user.
ALARM 315, Auto CT error
An error was detected while performing auto CT detection.
Auto CT detection does not work under the following
conditions: if any sum current transformers are installed,
when the active filter is supplied through a step up or step
down transformers, or when the filter is <10% of the CT
primary. Program the CT parameters manually if auto CT
detection fails.
WARNING 316, CT location error
The auto CT function could not determine the correct
locations of the CTs.
Program the CT parameters manually if auto CT detection
fails.
WARNING 317, CT polarity error
The auto CT function could not determine the correct
polarity of the CTs.
Program the CT parameters manually if auto CT detection
fails.
WARNING 318, CT ratio error
The auto CT function could not determine the correct
primary rating of the CTs.
Program the CT parameters manually if auto CT detection
fails.