VLT
®
6000 HVAC Series
Installation
■
Technical data, mains supply 3x380-460V
According to international requirements
VLT type
6152
6172
6222
6272
6352
I
VLT,N
[A] (380-440 V)
212
260
315
395
480
Output current
I
VLT, MAX
(60 s) [A]
(380-440 V)
233
286
347
435
528
I
VLT,N
[A] (441-460 V)
190
240
302
361
443
I
VLT, MAX
(60 s) [A]
(441-460 V)
209
264
332
397
487
S
VLT,N
[kVA] (400 V)
147
180
218
274
333
Output power
S
VLT,N
[kVA] (460 V)
151
191
241
288
353
Typical shaft output (380-440 V) P
VLT,N
[kW]
110
132
160
200
250
Typical shaft output (441-460 V) P
VLT,N
[HP]
150
200
250
300
350
Max. cable cross-section to motor and DC-bus
[mm
2
]
2) 4) 5)
2x70
2x70
2x185
2x185
2x185
Max. cable cross-section to motor and DC-bus
[AWG]
2) 4) 5)
2x2/0
mcm
2x2/0
mcm
2x350
mcm
2x350
mcm
2x350
mcm
Min. cable cross-section to motor and DC-bus
[mm
2
/AWG]
2) 4) 5)
35/2
35/2
35/2
35/2
35/2
I
L,N
[A] (380 V)
208
256
317
385
467
Max. input current
(RMS)
I
L,N
[A] (460 V)
185
236
304
356
431
Max. cable cross-section to power [mm
2
]
2) 4) 5)
2x70
2x70
2x185
2x185
2x185
Max. cable cross-section to power [AWG]
2) 4) 5)
2x2/0
mcm
2x2/0
mcm
2x350
mcm
2x350
mcm
2x350
mcm
Max. pre-fuses
[-]/UL
1)
[A]
300/300 350/350
450/400 500/500 630/600
Weight IP 00
[kg]
82
91
112
123
138
Weight IP 20
[kg]
96
104
125
136
151
Weight IP 54
[kg]
96
104
125
136
151
Efficiency at rated frequency
0.98
Power loss at max.
load.
[W]
2619
3309
4163
4977
6107
Enclosure
IP 00/IP 21/NEMA 1/IP 54
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Max. cable
cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus).
MG.61.A5.02 - VLT is a registered Danfoss trademark