VLT
®
6000 HVAC Series
PNU
Parameter
Factory setting
Range
Changes 4-Setup
Conversion
Data
#
description
during operation
index
type
300
Terminal 16, Digital input
Reset
Yes
Yes
0
5
301
Terminal 17, Digital input
Freeze output
Yes
Yes
0
5
302
Terminal 18, Digital input
Start
Yes
Yes
0
5
303
Terminal 19, Digital input
Reversing
Yes
Yes
0
5
304
Terminal 27, Digital input
Coasting stop, inverse
Yes
Yes
0
5
305
Terminal 29, Digital input
Jog
Yes
Yes
0
5
306
Terminal 32, Digital input
No operation
Yes
Yes
0
5
307
Terminal 33, Digital input
No operation
Yes
Yes
0
5
308
Terminal 53, analogue input voltage Reference
Yes
Yes
0
5
309
Terminal 53, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
310
Terminal 53, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
311
Terminal 54, analogue input voltage No operation
Yes
Yes
0
5
312
Terminal 54, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
313
Terminal 54, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
314
Terminal 60, analogue input current Reference
Yes
Yes
0
5
315
Terminal 60, min. scaling
4.0 mA
0.0 - 20.0 mA
Yes
Yes
-4
5
316
Terminal 60, max. scaling
20.0 mA
0.0 - 20.0 mA
Yes
Yes
-4
5
317
Time out
10 sec.
1 - 99 sec.
Yes
Yes
0
5
318
Function after time out
Off
Yes
Yes
0
5
319
Terminal 42, output
0 - I
MAX
0-20 mA
Yes
Yes
0
5
320
Terminal 42, output, pulse scaling
5000 Hz
1 - 32000 Hz
Yes
Yes
0
6
321
Terminal 45, output
0 - f
MAX
0-20 mA
Yes
Yes
0
5
322
Terminal 45, output, pulse scaling
5000 Hz
1 - 32000 Hz
Yes
Yes
0
6
323
Relay 1, output function
Alarm
Yes
Yes
0
5
324
Relay 01, ON delay
0.00 sec.
0 - 600 sec.
Yes
Yes
0
6
325
Relay 01, OFF delay
0.00 sec.
0 - 600 sec.
Yes
Yes
0
6
326
Relay 2, output function
Running
Yes
Yes
0
5
327
Pulse reference, max. frequency
5000 Hz
Depends on
input terminal
Yes
Yes
0
6
328
Pulse feedback, max. frequency
25000 Hz
0 - 65000 Hz
Yes
Yes
0
6
364
Terminal 42, bus control
0
0.0 - 100 %
Yes
Yes
-1
6
365
Terminal 45, bus control
0
0.0 - 100 %
Yes
Yes
-1
6
Changes during operation:
"Yes" means that the parameter can be changed,
while the frequency converter is in operation. "No"
means that the frequency converter must be stopped
before a change can be made.
4-Setup:
"Yes" means that the parameter can be programmed
individually in each of the four setups, i.e. the
same parameter can have four different data
values. "No" means that the data value will be
the same in all four setups.
Conversion index:
This number refers to a conversion figure to
be used when writing or reading by means
of a frequency converter.
Conversion index
Conversion factor
74
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
Data type:
Data type shows the type and length of the telegram.
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
MG.61.A5.02 - VLT is a registered Danfoss trademark
164