VLT
®
6000 HVAC Series
■
Unpacking and ordering a VLT frequency converter
If you are in doubt as to which frequency converter
you have received and which options it contains,
use the following to find out.
■
Type code ordering number string
On the basis of your order, the frequency converter is
given an ordering number that can be seen from the
nameplate on the unit. The number may look as follows:
VLT-6008-H-T4-B20-R3-DL-F10-A00-C0
This means that the frequency converter ordered is a
VLT 6008 for three-phase mains voltage of 380-460 V
(
T4
) in Bookstyle enclosure IP 20 (
B20
). The hardware
variant is with integral RFI filter, classes A & B (
R3
). The
frequency converter features a control unit (
DL
) with a
PROFIBUS option card (
F10
). No option card (A00)
and no conformal coating (C0) Character no. 8 (
H
)
indicates the application range of the unit:
H
= HVAC.
IP 00: This enclosure is only available for the larger
power sizes of the VLT 6000 HVAC series. It is
recommended for installation in standard cabinets.
IP 20 Bookstyle: This enclosure is designed for
cabinet installation. It takes up a minimum of
space and can be fitted side-by-side without
installation of extra cooling equipment.
IP 20/NEMA 1: This enclosure is used as standard
enclosure for VLT 6000 HVAC. It is ideal for
cabinet installation in areas where a high degree
of protection is required. This enclose also
permits side-by-side installation.
IP 54: This enclosure can be fitted direct to the
wall. Cabinets are not required. IP 54 units can
also be installed side-by-side.
Hardware variant
The units in the programme are available in the
following hardware variants:
ST:
Standard unit with or without control unit.
Without DC terminals, except for
VLT 6042-6062, 200-240 V
VLT 6016-6072, 525-600 V
SL:
Standard unit with DC terminals.
EX:
Extended unit with control unit, DC terminals,
connection of external 24 V DC supply for
back-up of control PCB.
DX:
Extended unit with control unit, DC terminals,
built-in mains fuses and disconnector,
connection of external 24 V DC supply for
back-up of control PCB.
PF:
Standard unit with 24 V DC supply for back-up
of control PCB and built-in main fuses. No DC
terminals.
PS:
Standard unit with 24 V DC supply for back-up
of control PCB. No DC terminals.
PD: Standard unit with 24 V DC supply for back-up
of control PCB, built-in main fuses and
disconnect. No DC terminals.
RFI filter
Bookstyle units always come
with
an integral RFI
filter that complies with EN 55011-B with 20 m
screened/armoured motor cable and EN 55011-A1
with 150 m screened/armoured motor cable. Units
for mains voltage of 240 V and a motor power of up
to and including 3.0 kW (VLT 6005) and units for a
mains voltage of 380-460 V and a motor power of
up to 7.5 kW (VLT 6011) are always supplied with an
integral class A1 & B filter. Units for higher motor
power than these (3.0 and 7.5 kW, respectively) can
be ordered either with or without an RFI filter.
Control unit (keypad and display)
All types of units in the programme, except for
IP21 VLT 6402-6602, 380-460 V, VLT 6502-6652,
525-600 V and IP 54 units, can be ordered either
with or without the control unit. IP 54 units always
come
with
a control unit. All types of units in the
programme are available with built-in application
options including a relay card with four relays or a
cascade controller card.
Conformal Coating
All types of units in the programme are available with
or without conformal coating of the PCB.
VLT 6402-6602, 380-460 V and VLT 6102-6652,
525-600 V are only available coated.