VLT
®
6000 HVAC Series
Installation
■
Mains supply (L1, L2, L3)
Mains supply (L1, L2, L3):
Supply voltage 200-240 V units ........................................................................ 3 x 200/208/220/230/240 V ±10%
Supply voltage 380-460 V units ........................................................................ 3 x 380/400/415/440/460 V ±10%
Supply voltage 525-600 V units ............................................................................... 3 x 525/550/575/600 V ±10%
Supply frequency ............................................................................................................................ 48-62 Hz ± 1%
Max. imbalance of supply voltage:
VLT 6002-6011, 380-460 V and 525-600 V and VLT 6002-6005, 200-240 V .......... ±2.0% of rated supply voltage
VLT 6016-6072, 380-460 V and 525-600 V and VLT 6006-6032, 200-240 V .......... ±1.5% of rated supply voltage
VLT 6102-6602, 380-460 V and VLT 6042-6062, 200-240 V ..................................
±3.0% of rated supply voltage
VLT 6102-6652, 525-600 V .......................................................................................
±3% of rated supply voltage
True Power factor (
λ
) ...................................................................................................... 0.90 nominal at rated load
Displacement Power Factor (cos.
ϕ
) ............................................................................................ near unity (>0.98)
No. of switches on supply input L1, L2, L3 ..........................................................................
approx. 1 time/2 min.
Max. short-circuit current ....................................................................................................................... 100.000 A
VLT output data (U, V, W):
Output voltage ................................................................................................................ 0-100% of supply voltage
Output frequency:
Output frequency 6002-6032, 200-240V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6042-6062, 200-240V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6002-6062, 380-460V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6072-6602, 380-460V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6002-6016, 525-600V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6022-6062, 525-600V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6072, 525-600V ......................................................................................... 0-120 Hz, 0-450 Hz
Output frequency 6102-6352, 525-600V ................................................................................ 0-132 Hz, 0-200 Hz
Output frequency 6402-6652, 525-600V ................................................................................ 0-132 Hz, 0-150 Hz
Rated motor voltage, 200-240 V units .............................................................................. 200/208/220/230/240 V
Rated motor voltage, 380-460 V units .............................................................................. 380/400/415/440/460 V
Rated motor voltage, 525-600 V units ............................................................................................ 525/550/575 V
Rated motor frequency ............................................................................................................................ 50/60 Hz
Switching on output ................................................................................................................................. Unlimited
Ramp times ....................................................................................................................................... 1 - 3600 sec.
Torque characteristics:
Starting torque ............................................................................................................................... 110% for 1 min.
Starting torque (parameter 110
High break-away torque)
....................................... Max. torque: 160% for 0.5 sec.
Acceleration torque ....................................................................................................................................... 100%
Overload torque ............................................................................................................................................ 110%
MG.61.A5.02 - VLT is a registered Danfoss trademark
21