A
E
B
D
F
G
H
C
e3
0b
j3
51
.1
0
Illustration 9: Dimensions of the Liquid-cooled Inductors
7.6 Terminal and Torque Specifications
Table 14: DC Filter Terminal Sizes and Tightening Torques
Filter type code
Connection size
Connection Torque [Nm]
Mounting location
Terminal
Grounding
Terminal
Grounding
LDC-0010-6-0-Axx
≤ 6 mm
2
M6
1.8
9
Base
LDC-0020-5-0-Axx
≤ 6 mm
2
M6
1.8
9
Base
LDC-0030-6-0-Axx
≤ 6 mm
2
M6
1.8
9
Base
LDC-0050-6-0-Axx
Busbar 1 x D9, M8
M8
20
20
Base
LDC-0092-5-0-Axx
Busbar 1 x D9, M8
M8
20
20
Base
LDC-0092-6-0-Axx
Busbar 1 x D9, M8
M8
20
20
Base
LDC-0092-5-0-Bxx
Busbar 1 x D9, M8
M8
20
20
Base
LDC-0170-6-0-Axx
Busbar 1 x D11, M10
M10
40
40
Base
LDC-0270-5-0-Axx
Busbar 1 x D11, M10
M10
40
40
Base
LDC-0400-6-0-Axx
Busbar 1 x D11, M10
M10
40
40
Base
LDC-0400-6-0-Bxx
Busbar 1 x D11, M10
M10
40
40
Base
LDC-0420-5-0-Axx
Busbar 1 x D13, M12
M10
70
40
Base
LDC-0540-6-0-Bxx
Busbar 1 x D13, M12
M10
70
40
Base
LDC-0900-5-0-Bxx
Busbar 2 x D13, 2 x M12
M10
70
40
Base
LDC-0160-6-0-Cxx
Busbar 1 x D9, M8
M10
20
40
Base
AJ377845348678en-000101 / 172F4785 | 23
Danfoss A/S © 2023.01
Specifications
DC Filters
Design Guide