![Danfoss Vacon NXP Design Manual Download Page 10](http://html1.mh-extra.com/html/danfoss/vacon-nxp/vacon-nxp_design-manual_3535777010.webp)
Drive enclo-
sure size
Drive type
High Voltage @ 750 V DC, f
s
= 5 kHz
Low Voltage @ max current, f
s
= 5 kHz
I
out
nominal [A] Filter selection
I
out
max [A] Filter selection
NXI_0920 5 < 1096
2 x LDC-0270-5-0-Axx 1750
2 x LDC-0400-6-0-Bxx
NXI_1030 5 < 1227
1750
FI13
NXI_1150 5 < 1370
LDC-0540-6-0-Bxx
2300
LDC-0900-5-0-Bxx
NXI_1300 5 < 1549
2550
NXI_1450 5 < 1727
LDC-0900-5-0-Bxx
2550
FI14
NXI_1770 5 < 2109
2 x LDC-0400-6-0-Bxx 3540
2 x LDC-0900-5-0-Bxx
NXI_2150 5 < 2561
2 x LDC-0540-6-0-Bxx 4300
NXI_2700 5 < 3217
5000
Table 4: DC Filter Selection for Air-cooled 690 V Drives According to Energy Storage Requirements
Drive enclosure size
Drive type
High Voltage @ 1025 V DC, f
s
= 5 kHz
Low Voltage @ max current, f
s
= 5 kHz
I
out
nominal [A]
Filter selection
I
out
max [A]
Filter selection
FR6
NXI_0010 6
< 11.1
LDC-0010-6-0-Axx
14.6
LDC-0010-6-0-Axx
NXI_0013 6
< 14.6
19
NXI_0018 6
< 20.3
26.3
NXI_0022 6
< 25
32
NXI_0027 6
< 31
39
LDC-0020-5-0-Axx
NXI_0034 6
< 39
LDC-0020-5-0-Axx
49
FR7
NXI_0041 6
< 47
60
NXI_0052 6
< 60
62
FR8
NXI_0062 6
< 71
LDC-0030-6-0-Axx
90
LDC-0030-6-0-Axx
NXI_0080 6
< 92
117
LDC-0050-6-0-Axx
NXI_0100 6
< 117
LDC-0050-6-0-Axx
135
FI9
NXI_0125 6
< 146
183
LDC-0092-6-0-Axx
NXI_0144 6
< 168
LDC-0092-6-0-Axx
210
NXI_0170 6
< 198
248
NXI_0208 6
< 245
250
FI10
NXI_0261 6
< 308
LDC-0170-6-0-Axx
382
LDC-0170-6-0-Axx
NXI_0325 6
< 383
475
NXI_0385 6
< 454
490
NXI_0416 6
< 490
490
FI12
NXI_0460 6
< 548
2 x LDC-0092-6-0-Axx
673
2 x LDC-0170-6-0-Axx
AJ377845348678en-000101 / 172F4785
10 | Danfoss A/S © 2023.01
Selection
DC Filters