97 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
Figure 115 - PWM Connector
- 6 Pin
9. The measured voltage drop should be 0.33-0.46 VDC.
Figure 116 - PWM Test Points
Pin 1
TP 2: HV-
TP 3: 17VDC
TP 1: HV+
Diode Test
1. Isolate the Compressor power as described in the
“Electrical Isolation of the Compressor/VFD”
section of this manual.
2. Disconnect the PWM Bearing Power Cables from the Compressor bearing feed throughs.
3. Unplug the 250V DC input to the PWM.
4. Using a Multimeter, set to measure Diode, place the po) test lead on the HV- test point of
the PWM and negative(-) lead in the first pin hole of the rear PWM Bearing Power Cable.
5. The measured voltage drop should be 0.33-0.46 VDC.
6. Repeat in a clockwise rotation for all the outer pin holes of the rear Bearing Power Cable and the
4 pins of the front Bearing Power Cable (The center pin of the rear Bearing Power Cable does not
have a test value.).
7. Place the negative (-) test lead on the HV+ test point of the PWM and the po) lead in the
first pin hole of the PWM Bearing Power Cable.
8. Repeat in a clockwise rotation for all the outer pin holes of the rear Bearing Power Cable and the
4 pins of the front Bearing Power Cable. (The center pin of the rear Bearing Power Cable does
not have a test value.)
Summary of Contents for Turbocor VTT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...18 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...24 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 132: ...132 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 152: ...152 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 158: ...158 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 160: ...160 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...