66 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
Temperature
º C
Resistance
Ω
Temperature
º C
Resistance
Ω
Temperature
º C
Resistance
Ω
-50
803.1
40
1155.4
130
1498.3
-40
842.7
50
1194.0
140
1535.8
-30
882.2
60
1232.4
150
1573.3
-20
921.6
70
1270.8
160
1610.5
-10
960.9
80
1309.0
170
1647.7
0
1000.0
90
1347.1
180
1684.8
10
1039.0
100
1385.1
190
1721.7
20
1077.9
110
1422.9
200
1758.6
30
1116.7
120
1460.7
Table 20 - Stator
Thermistor R/T Curve
9. Verify resistance of each circuit at the external connector to housing (ground).
• Should be “open.”
10. If the Stator Temperature Sensor Feed Through is suspected to have a problem, remove it and
test as above directly at the internal connector. Refer to the
“Stator Temperature Sensor Feed
section of this manual.
11. Restore power to the Compressor.
NOTE
Measured values must be within
±
10% of the values in Table 20 (Stator Thermistor R/T Curve).
Summary of Contents for Turbocor VTT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...18 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...24 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 132: ...132 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 152: ...152 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 158: ...158 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 160: ...160 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...