94 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
4. Remove the 250V PWM ground wire from the service side.
5. Remove the cable from the service side.
6. Open the panel containing the DC-DC.
7. Disconnect the 250 V (J2) clip from DC-DC.
Figure 110 - DC-DC J2 and
J6 Connector (Revisions A
and B)
8. Disconnect the 250V DC-DC ground wire from the DC-DC.
9. Remove the cable from the DC-DC panel.
Removal (Revisions C and Later Cables):
1. Isolate the Compressor and VFD power as described in the
section of this manual.
2. Remove the Service Side Cover.
3. Disconnect the J11 connector from the PWM.
J2 Connector
J6 Connector
Figure 109 - PWM J11
Connector (Revisions A
and B)
J11 Connector