Operating Guide

Termix VVX-B – 7 Series BS

7.3 Troubleshooting HE

Problem

Possible cause

Solution

Insufficient credit on the pre-payment unit,
if installed.

Top up your credit.

Strainer clogged in DH or HE circuit
(radiator circuit).

Clean gate/strainer(s).

The filter in the energy meter on DH circuit
clogged.

Clean the filter (after consulting the DH
plant operator).

Defective or wrongly adjusted differential
pressure controller.

Check the operation of the differential
pressure controller – clean the valve seat if
required.

Sensor defective – or possibly dirt in the
valve housing.

Check the operation of the thermostat –
clean the valve seat if required.

Automatic controls, if any, wrongly set or
defective - possibly power failure.

Check if the setting of the controller
is correct – see separate instructions.
Check the power supply. Temporary
setting of motor to “manual” control – see
instructions on automatic controls.

Pump out of operation.

Check if the pump is receiving power and
that it turns. Check if there is air trapped in
the pump housing – see pump manual.

The pump is set at too low speed of
rotation.

Set the pump at higher speed of rotation.

Pressure drop – the pressure drop on
the radiator circuit shows lower than
recommended operating pressure.

Fill water on the system and check the
functioning of the pressure expansion
vessel if required.

Air pockets in the system.

Vent the installation thoroughly.

Limiting of the return temperature
adjusted too low.

Adjust according to instructions.

Defective radiator valves.

Check – replace.

Uneven heat distribution in building
because of incorrectly set balancing valves,
or because there are no balancing valves.

Adjust/install balancing valves.

Too little or no heat.

Diameter of pipe to substation too small or
branch pipe too long.

Check pipe dimensions.

Uneven heat distribution.

Air pockets in the system.

Vent the installation thoroughly.

DH supply temperature too high.

Wrong setting of thermostat or of
automatic controls, if any.

Adjust automatic controls, – see
instructions for automatic controls.

Defective controller. The controller does
not react as it should according to the
instructions.

Call automatic controls manufacturer or
replace the regulator.

Defective sensor on self-acting thermostat.

Replace thermostat – or sensor only.

LGB40404

DEN-GT

21

Summary of Contents for Termix VVX-B-7 BS Series

Page 1: ...t up 6 4 3 Electrical connections 7 5 0 Design 10 5 1 Design 10 5 2 Schematic diagram 11 6 0 Controls 12 6 1 Heating circuit 12 6 2 DHW temperature control 16 6 3 Other 17 6 4 Extras 18 6 5 Maintenanc...

Page 2: ...ump The temperature of the heating can be controlled thermostatically or by an electronic controller with an outdoor temperature sensor Depending on the application different heat exchangers dimension...

Page 3: ...eaks or other dangerous circumstances interrupt all energy sources to the station if possible and seek expert help In case of discoloured or bad smelling domestic hot water close all shut off valves o...

Page 4: ...be taken to mean the primary supply Connections 1 Domestic cold water DCW 2 Domestic hot water DHW 3 District heating DH return 4 District heating DH supply 5 Heating HE return 6 Heating HE supply Co...

Page 5: ...allation Clean and rinse Prior to installation all substation pipes and connections should be cleaned and rinsed Tightening Due to vibration during transport all substation connections must be checked...

Page 6: ...e ball valve is then closed the hose removed and the plug put back in Start up 1 Pump speed Set the pump to highest speed before start up 2 Start pump Start the pump and heat through the system 3 Open...

Page 7: ...bol Disconnection The substation must be electrically connected so that it can be disconnected for repairs Outdoor temperature sensor Outdoor sensors should be mounted so as to avoid exposure to direc...

Page 8: ...emperature The IMIT Thermostat is preset to 60 C shutting off the pump and the primary on off valve when the flow to the underfloor heating exceeds 60 C The IMIT Thermostat is if not already factory f...

Page 9: ...Operating Guide Termix VVX B 7 Series BS 4 3 3 Wiring diagram Radiator heating Underfloor heating LGB40404 DEN GT 9...

Page 10: ...gn description A Heat exchanger HE 9 Strainer 38 Expansion tank B Heat exchanger DHW 10 Circulator pump 41 Fitting piece energy meter 4 Safety valve 20 Filling drain valve 48 Air vent manual 7A Thermo...

Page 11: ...Shut off valve 1 Ball valve 20 Filling drain valve 48 Air vent manual 2B Double check valve WRAS 24 Delivered loose with unit 62B Pressure Absorber with non return valve 4 Safety valve 26 Pressure gau...

Page 12: ...low temperature in the heating circuit is controlled by the HE temperature controller 6 1 3 RAVK controller RAVK controller 35 75 C The temperature setting is as follows 1 30 C 2 40 C 3 52 C 4 64 C 5...

Page 13: ...as follows 1 35 C 2 55 C 3 75 C 4 95 C 5 100 C The values are intended as a guide Thermostatic control The temperature of the HE flow line is adjusted as follows To increase temperature turn the hand...

Page 14: ...ats it is recommended that thermostats be set for minimum temperature in each room 6 1 8 Outdoor temperature sensor ESMT Outdoor sensors should be mounted so as to avoid exposure to direct sunlight Th...

Page 15: ...ser interface switches to setting selection if the user interface is unlocked You can change the settings as they appear The selection of the control mode depends on the system type and the allocation...

Page 16: ...ler 20 60 The temperature setting is as follows 1 20 C 2 35 C 3 50 C 4 60 C 5 70 C The values are intended as a guide The AVTB operates at its best at DH supply temperatures of up to 90 C Thermostatic...

Page 17: ...uld be cleaned regularly by authorized personnel The frequency of cleaning would depend on operating conditions and the manufacturer s instructions 6 3 3 Pressure Absorber The Pressure Absorber reduce...

Page 18: ...er Do not forget the gaskets 4 Tighten connections After mounting of the energy meter remember to check and tighten all threaded connections Sensor pocket energy meter The sensors of the energy meter...

Page 19: ...Temperatures Checking of all temperatures such as DH supply temperature and DHW temperature Connections Checking all connections for leakages Safety valves The operation of the safety valves should b...

Page 20: ...f order or with too low setting Check circulation pump Defective or clogged non return valve Replace clean No electricity Check Wrong setting of automatic controls if any To adjust an electronic contr...

Page 21: ...manual The pump is set at too low speed of rotation Set the pump at higher speed of rotation Pressure drop the pressure drop on the radiator circuit shows lower than recommended operating pressure Fil...

Page 22: ...radiators in the system from heating up at the bottom It is extremely important to keep the supply temperature to the radiators as low as possible while maintaining a reasonable level of comfort The s...

Page 23: ...Operating Guide Termix VVX B 7 Series BS 8 0 Declaration 8 1 Declaration of conformity Category 0 with electrical equipment LGB40404 DEN GT 23...

Page 24: ...Operating Guide Termix VVX B 7 Series BS Produced by Gemina Termix A S 03 2018...

Reviews: