3
Specifi
ca
tion
Features REP24
Power supply
24 Vac, ± 15%
Control Output
0-10 Vdc
Control Method
P + I
Proportional Band
2° K
Temperature range
10-30°C
Maximum ambient temperature
45°C
Control pollution
Degree 2
Design standard
EN 60730-2-9
Rated impulse voltage
2.5kV
Ball hardness test
75°C
Dimensions (mm)
85 wide x 86 high x 42 deep