Two Sensors
Measuring for
Balancing by
the
Proportional
Method
1. Tap on Proportional
measure button
2. Balancing by proportional
method window will open.
Measuring is on line from the
both measuring units. The
datas from the measuring unit
1 are displayed in the left side
of the screen, measuring unit 2
is displayed in the right side of
the screen. Units for the flow
and pressure you have to
choose in the Main menu/
Settings.
3. If you choose for the flow unit the Lambda value, you have
to set also the requested flow from the displayed menu after
tap on the Menu button.
3. Select reference measuring unit, for instance the number 1
in the upper of the window.
4. In the lower part of the window the measuirng unit 2 will
display the datas from the balanced valve from the branch.
5. For both measuring units, set the correct valve and
presetting.
6. By the measuring we are moving with the smart phone and
convertor away from the reference measuring unit. So we have
to use the the routers by the reference measuring unit (in our
case number 1) not to loose the signal. When
the routers are placed you have to tap on the left
button Use routers.
7. The flow on the both valves will be displayed like a
bar graph.
8. You can choose like a reference measuring unit the
both units, so it´s important to tap on the correct
button Use routers!
HEC
25