background image

8510197P01-D         © Danfoss Maneurop 

 

06-2002

3

Instructions

responsible for ensur ing compliance could
invalidate the user’s authorization to operate the
equipment.

2 - Transportation, storage

·

 The compressor must be handled in the verti-

cal position (maximum offset from the vertical: 15

°

).

Should the compressor be handled in an upside-
down position, its performance may no longer be
insured.

·

 Beware that all compressor handling must be

carried out with extreme caution to avoid any
shocks. Dedicated packing handles are to be used
for all required manipulation of the compressor;
otherwise appropriate and safe lifting equipment
is to be used during handling and unpacking.
(Refer to Fig. 3).

·

 Any damage noticed on either the packaging

or the product itself upon reception should be
indicated on a Customer Claim addressed to the
shipping company. The same recommendation ap-
plies to all instances when transpor t
instructions have not been fully respected.

·

 Please review the safety instructions printed

on the cardboard packaging before storage.

·

 Verify that the compressor is never stored in

an ambient temperature of below -35

°

C (-31

°

F)

or above the limit specified on the compressor
name plate (Ps or Ts, whichever limit is reached
first, depending on the refrigerant used).

·

 Ensure that the compressor and its packaging

are not exposed to rain and/or a corrosive,
flammable atmosphere.

3 - Safety measures prior to assembly

·

 All installation and servicing is to be performed

by qualified personnel in compliance with all
 pertinent practices and safety procedures.

·

The compressor must be located in a

ventilated area to ensure that the ambient
temperature never exceeds 50

°

C (122

°

F) during

the off-cycle.

·

 Make certain that the compressor can be

mounted on to a horizontal plane with a maximum
slope of  3

°

.

·

 Check that the compressor model corresponds

to system specifications (capacity, use of
refrigerant, etc.).

·

 Verify that the power supply corresponds to

compressor motor characteristics (refer to the
compressor nameplate for precision).

·

  Ensure that the refrigerant-charging equip-

ment, vacuum pumps, etc. for HFC refrigerant
systems have been specifically reserved for these
refrigerants and never used with other CFC, HCFC
refrigerants.

·

 Use only clean and dehydrated refrigeration-

grade copper tubes as well as silver alloy
brazing material.

·

 Verify that all system components are appropri-

ate (use of refrigerant, etc.), clean and
dehydrated before being connected to the completed
assembly.

·

 Perform a check on the suction lines: Horizon-

tal sections are to be sloped downwards towards
the compressor. Suction gas velocity must be high
enough to provide for an adequate oil return.
This velocity must be within 8 to 12 m/s in vertical
risers. In horizontal pipes, this velocity can
decrease to 4 m/s. The use of U-trap and double-
suction risers may be required on vertical
sections, but not in excess of 4 m unless a second
U-trap system has been fitted (refer to Fig. 4).
Suction line piping must be insulated in order to
minimize the effects of superheating.

·

 Perform a check on the discharge lines: Pip-

ing to the condenser must be designed so as to
prevent liquid return to the compressor. The use
of non-return valves may prove necessary,
depending on the position of the compressor with
respect to the condenser. A suitably-sized U-trap
may also be necessary if the condenser has been
placed above the compressor (refer to Fig. 5).

·

 The piping connected to the compressor must

be configured on the basis of a flexible 3-axis de-
sign to dampen vibrations and designed in such a
way as to prevent free liquid refr igerant
migration and drainage back to the compressor
sump (refer to Fig. 5).

·

 Note that all local and regional regulations and

safety standards, such as EN378, must be taken
into account when designing, connecting and
 running  the system.

4 - Assembly

The compressor’s time of exposure to the at-

mosphere during installation shall be held to a
minimum. The compressor connection must be fast
in order to avoid moisture contamination of the
lubricant.

·

 The grommets must be installed under the

compressor feet, as shown in Figs. 1 and 2.
Rubber grommets are to undergo compression
until contact is made between the flat washer and
the steel mounting sleeve.

Before opening the compressor connection

fittings, it is mandatory to connect a 1/4" service
hose to the Schrader fitting on the compressor
shell in order to gradually release the nitrogen
holding charge.

·

 Ensure that no material enters into the system

while cutting the tubing. Moreover, never drill holes
in the pipe work after installation.

·

 Should additional components need to be

connected on to the compressor sight glass or oil
equalization ports, it is recommended that such an
operation be carried out prior to final assembly, to
allow for compressor inclination and movement.

·

 Avoid flare-type connections and exercise great

care while brazing (use only state-of-the-art
practices); apply a nitrogen gas flow to prevent oxi-
dation inside the tubing, especially when HFC
refrigerants are being used. All brazing material is
to contain a minimum of 5% silver.

·

 When  brazing, protect  the terminal box and painted

surfaces  of the compressor  from torch heat damage.

·

 For compressors equipped with Rotolock, re-

move the Teflon gaskets when brazing Rotolock
connectors with the solder sleeve and be aware
that original suction and discharge gaskets must
be replaced.

·

 When installing Rotolock fittings, always use

two wrenches when tightening any fittings to en-
sure that the torque is effectively cancelled on the
adjacent tubing and fittings. Do not exceed the
maximum tightening torque for Rotolock
connections to the compressor.
(1’’ Rotolock 80Nm - 1’’1/4 Rotolock 90Nm
1’’3/4 Rotolock 110Nm - 2’’1/4 Rotolock 130Nm).

·

 Be sure to connect the required safety and con-

trol devices onto compressor shutoff valves or fittings.

·

  In case of oil return through the Schrader fit-

ting on the compressor shell, make sure the inter-
nal valve is removed.

5 – Leak detection

 Never use oxygen or dry air in order to avoid

the risk of fire or explosion.

·

 Perform a leak detection test on the complete

system by means of: a dry nitrogen pressure test,

Contents

1

- Introduction

2

- Transportation,  storage

3

- Safety measures prior to assembly

4

- Assembly

5

- Leak detection

6

- Vacuum procedure

7

- Electrical connections

8

- Filling the system

9

- Verification before commissioning

10 - Start up
11 - Troubleshooting
12 - Maintenance
13 - Replacement
14 - User advisory

1- Introduction

These instructions pertain to Performer

®

 hermetic

scroll compressors used for A/C purposes. They
are intended to provide necessary information
regarding safety features and proper handling of
this product.
Note that this is a general document for the
entire range of scroll compressors;
cer tain details therefore may not be
applicable to the par ticular model you
purchased. Please keep your manual and all
relevant infor mation handy for future
reference.

·

Equipment descr iption: This compressor

is delivered with all assembly equipment (rubber
mounting grommets and screws, washers,
connecting sleeves depending on models)
 the electrical box and cover and Instructions.

·

 Approved list of refrigerants:

o The SM/SY series can be used with R22,
o The SZ 084 to 185 series can be used   with
R134a,R407C, R404A and R507A.
o The SZ 240 and 300 can be used with
R407C.

·

 Compressors are filled with lubricant before

leaving the factory:

o The SM series with mineral oil (ref. 160P),
o The SZ series with poloyester oil (ref. 160SZ),
o The SY series with poloyester oil (ref. 320SZ).

These lubricants must not be mixed with one another.

·

 Performer

®

 Scroll compressors must only be

used for their designed purpose(s) and within their
scope of application (refer to Fig. 6).

Compressors are delivered under nitrogen

gas pressure (between 0.3 and 1 bar) and hence
cannot be connected as is; please refer to the
 “Assembly” section for further details.

Compressors are not certified for mobile and

explosion-proof applications. Any use of
flammable refrigerant (e.g. hydrocarbons) or air is
also strictly forbidden.

·

 Under all circumstances, the EN378 (or other

applicable local regulation) requirement must be
fulfilled.
In agreement with the European directive
97/23/EC (PED), the compressor name plate gives
the low side maximum allowable pressure Ps and
the highest corresponding temperature Ts calcu-
lated for applicable refrigerants.

When pressure tests are required on the sys-

tem, they are to be perfor med by qualified
personnel, in paying close attention to potential
pressure-related hazards and heeding the
pressure limits displayed on the compressor
nameplate or in the application guidelines.

Modifications or alterations (such as brazing

on the shell) not expressly approved by the party

Summary of Contents for Performer SM R22

Page 1: ...P01 D Danfoss Maneurop 06 2002 Fig 1 INSTRUCTIONS INSTRUKTION Fig 3 Fig 2 1 3 4 5 6 Fig 5 Fig 4 1 2 3 4 5 6 HP LP OIL OIL OIL OIL LP HP U trap Evaporator 8 to 12 m s max 4m max 4m 0 5 0 5 4m s LP HP LP Condenser ...

Page 2: ... 0 5 10 15 20 25 20 15 10 5 0 5 10 15 20 20 15 10 5 0 5 10 15 20 25 20 15 10 5 0 5 10 15 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 Evaporating temperature C Evaporating temperature C Evaporating temperature C Evaporating temperature C Evaporating temperature C Evaporating t...

Page 3: ...ressor connection fittings it is mandatory to connect a 1 4 service hose to the Schrader fitting on the compressor shell in order to gradually release the nitrogen holding charge Ensure that no material enters into the system while cutting the tubing Moreover never drill holes in the pipe work after installation Should additional components need to be connected on to the compressor sight glass or ...

Page 4: ...r current protection an external manual reset overload protector must be used Note that Performer compressors SM SZ 084 090 100 110 120 161 are protected against overheating and overloading by an internal safety motor protector However an external manual re set overload protector is recommended for protecting the circuit against over current Fig 7 S240 300 motors are protected by an external modul...

Page 5: ...ng surface tempera tures may exceed 100 C 212 F and cause se vere bodily burns Special precaution must be taken when working around the compressor and refrigerant tubing Moreover a compressor in operation can generate very cold surface tempera tures as low as 25 C 13 F thereby exposing personnel to the risk of freezing burns Pressure inside the compressor can reach dangerously high levels e g abno...

Page 6: ... 0 5 10 15 20 25 20 15 10 5 0 5 10 15 20 20 15 10 5 0 5 10 15 20 25 20 15 10 5 0 5 10 15 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 Evaporating temperature C Evaporating temperature C Evaporating temperature C Evaporating temperature C Evaporating temperature C Evaporating t...

Page 7: ...ne réclamation adressée au transporteur Les mêmes recommandations s appliquent aux cas de non respect des instructions de transport Veuillez lire soigneusement les consignes de sécurité imprimées sur l emballage carton avant l entreposage Vérifiez que le compresseur entreposé ne sera pas soumis à une température ambiante inférieure à 35 C 31 F ou dès qu une des valeurs limites données sur la plaqu...

Page 8: ... le circuit est sous vide risque de court circuit du moteur claquage moteur 7 Connexions électriques Vérifiez que l alimentation électrique principale du système a été coupée et isolée conformément aux règles en vigueur avant d effectuer toute opé ration de raccordement Se reporter aux schémas 7 8 et 9 pour les détailsderaccordementetdecâblagecorrespondants aux différents modèles de compresseurs N...

Page 9: ...ressions maximum de sécurité du compresseur L utilisation d un pressostat de sécurité basse pression est recommandée pour empêcher un fonctionnement sous vide Réglage minimum recommandé 1 1 bar absolu Vérifiez que toutes les connexions électriques sont bien serrées et conformes aux réglementations de sécurité en vigueur au niveau local Lorsqu une résistance de carter est nécessaire voir guide d ap...

Page 10: ...urs de chaleur surchauffe sous refroidissement Ces paramètres de fonctionnement doivent toujours se situer dans la plage d utilisation du compresseur o Vérifiez que les dispositifs de sécurité sont tous opérationnels et correctement réglés o Contrôlez le niveau d huile et son aspect En cas de changement de couleur vérifiez sa qualité Ceci peut inclure un test d acidité un contrôle d humidité une a...

Page 11: ...5 10 15 20 25 20 15 10 5 0 5 10 15 20 20 15 10 5 0 5 10 15 20 25 20 15 10 5 0 5 10 15 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 Verdampfungstemperatur C Verdampfungstemperatur C Verdampfungstemperatur C Verdampfungstemperatur C Verdampfungstemperatur C Verdampfungstemperatu...

Page 12: ...r in Positi on mit dem Kopf nach unten kann seine Funkti onstüchtigkeit nicht gewährleistet werden Bitte beachten dass alle Handhabungen des Verdichters mit äußerster Sorgfalt erfolgen sollen um Stöße zu vermeiden Für alle erforderlichen Beförderungen des Verdichters sind die dafür vorgesehenen Transportgriffe zu benutzen darüber hinaus sind für die Handhabung und beim Auspacken geeignete und sich...

Page 13: ...des Rotolock Anschlusses mit der Lötbuchse ist die Teflondichtung zu entfernen und darauf zu achten dass die ursprünglichen Saug und Ausgangsdichtungen ersetzt werden müssen Bei der Installation von Rotolock Anschlüssen sind beim Festspannen eines Fittings immer zwei Schraubschlüssel zu benutzen um ein Überfüh ren des Moments auf die anschließenden Rohre und Fittings wirksam zu vermeiden Die maxim...

Page 14: ... Inbetriebnahme und oder nach längeren Stillstandsperioden eingeschaltet wird 10 Inbetriebnahme Keinesfalls den Verdichter ohne Kältemittel befüllung starten Weder der Niederdruck noch irgend ein an derer Sicherheitsschalter dürfen während des Starts überbrückt werden Stromaufnahme und Spannungsgrößen sind zu überprüfen Das Ölschauglas falls montiert ist 60 Minuten lang zu beobachten um einen sich...

Page 15: ...nungsverfahren und ausrüstungen entfernt und anschließend sicher gelagert werden Kältemitteldämpfe können die Luft verdrän gen und zu Erstickungsgefahr führen Deshalb ist bei Servicearbeiten an der Anlage immer zwin gend für eine ausreichende Entlüftung zu sorgen Der Austausch von Kälteanlagen komponenten hat immer in Übereinstimmung mit den lokalen Vorschriften zu erfolgen Es ist sicherzustellen ...

Page 16: ... other material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss the Danfoss logotype and Performer are trademarks of Danfoss AS All ri...

Reviews: