ches and relief valves don’t exceed the maximum 
service pressure of any system component.
 •  Verify that all electrical  connections inside the 

condensing unit are properly fastened as they 
could have worked loose during transporta-
tion.

 •  When a crankcase heater is required, the unit 

must be energized at least 12 hours before ini-
tial start-up and start-up after prolonged shu-
tdown for belt type crankcase heaters.

 •  The unit is equipped with a main switch with 

overload protection. Overload protection is 
preset from factory, but it is recommended to 
check the value before taking the unit in ope-
ration. The overload protection value can be 
found in the wiring diagram in the unit front 
door.

 •  Check if discharge temperature sensor is firm 

and has proper contact with discharge pipe.

12 – Start-up

  •  Never start the unit when no refrigerant is char-

ged.

  •  All service valves must be in the open position.
 •  Rotalock valve on the receiver must be tur-

ned 1 round to close direction to get the right 
condensing pressure for the pressure transmit-
ter

 •  Check compliance between unit and power 

supply.

  •  Check that the crankcase heater is working.
  •  Check that the fan can rotate freely.
  •  Check that the protection sheet has been remo-

ved from the backside of condenser.

  •  Balance the HP/LP pressure.
 •  Energize the unit. It must start promptly. If the 

compressor does not start, check wiring confor-
mity and voltage on terminals.

  •  Eventual reverse rotation of a 3-phase compres-

sor can be detected by following phenomena; 
the compressor doesn’t build up pressure, it has 
abnormally high sound level and abnormally 
low power consumption. P05 models are equip-
ped with a phase-reversal relay and compressor 
doesn’t start, the compressor doesn’t build up 
pressure, in case of wrong phase sequences.

 

In 

such case, shut down the unit immediately and 
connect the phases to their proper terminals.

 •  If the rotation direction is correct the low pres-

sure indication on the controller (or low pres-
sure gauge) shall show a declining pressure and 
the high pressure indication (or high pressure 
gauge) shall show an increasing pressure.

13 – Check with running unit

 •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

  •  Check current draw and voltage.
  •  Check suction superheat to reduce risk of slug-

ging.

 •  When a sight glass is provided observe the oil 

level at start and during operation to confirm 

that the oil level remains visible.

  •  Respect the operating limits.
 •  Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 
measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as 
far as possible from the compressor. The com-
pressor must be operating during this process.

  •  For P02 version models (OP-xxxxxxxxxP02E) :
 -  Check sight glass and make sure no bubbles in 

liquid line for proper liquid injection.   

 -  When o30 is set 19= R404A or 40=R448A or 

41=R449A and readout U26  > 125 in controller, 
check and make sure liquid injection is ON. Eco-
nomizer inlet pipe should be cold.

  •  Do not overcharge the system.
 •  Follow the local regulations for restoring the 

refrigerant from unit.

  •  Never release refrigerant to atmosphere.
 •  Before leaving the installation site, carry out a 

general installation inspection regarding clean-
liness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 
for future inspections.

14 – Emergency running without controller

In case of controller failure, the condensing unit 
can still be operated when the controller standard 
wiring (picture 4) is modified into a temporary 
wiring (picture 5) as described below. 

 This modification may be done by authorized 

electricians only. Country legislations have to be 
followed.

 Disconnect the condensing unit from power 

supply (turn hardware main switch off)
 •  Contact of Room Thermostat must be possible 

to switch 250VAC. 

 •  Remove wire 22 (safety input DI3) and wire 24 

(room thermostat DI1) and put them together 
with an insulated 250 Vac 10mm² terminal 
bridge.

 •  Remove wire 25 (room thermostat DI1) and 

wire 11 (compressor supply) and put them 
together with an insulated 250VAC 10mm² ter-
minal bridge.

 •  Remove wire 6 and connect it with terminal 

bridge for wire 11 and 25. A fan pressure switch 
or fan speed controller can be connected in 
series to wire 6.

  •  Remove wire 14 (crankcase heater) and connect 

it to the compressor contactor terminal 22.

 •  Remove wire 12 (supply crankcase heater), ex-

tend this wire by using an 250 Vac 10mm² termi-
nal bridge and 1,0mm² brown cable and connect 
it to compressor contactor terminal 21

 •  

Remove the large terminal block from the 
controller terminals 10 to 19.

 •  Connect the condensing unit to power supply 

(turn hardware main switch on).

15 – Maintenance

 Always switch off the unit at main switch be-

fore opening the fan door (s).

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.
Maintenance operators and installers require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 
regulations are performed.

To prevent system related problems, following 
periodic maintenance is recommended:
 •  Verify that safety devices are operational and 

properly set.

  •  Ensure that the system is leak tight.
  •  Check the compressor current draw.
 •  Confirm that the system is operating in a way 

consistent with previous maintenance records 
and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 •  Keep the unit clean and verify the absence of 

rust and oxidation on the unit components, 
tubes and electrical connections.

The condenser must be checked at least once a 
year for clogging and be cleaned if deemed ne-
cessary. Access to the internal side of the conden-
ser takes place through the fan door. Microchan-
nel coils tend to accumulate dirt on the surface 
rather than inside, which makes them easier to 
clean than fin-&-tube coils.
 •  Switch off the unit at main switch before ope-

ning the fan door.

 •  Remove surface dirt, leaves, fibres, etc. with 

a vacuum cleaner, equipped with a brush or 
other soft attachment. Alternatively, blow com-
pressed air through the coil from the inside out, 
and brush with a soft bristle. Do not use a wire 
brush. Do not impact or scrape the coil with the 
vacuum tube or air nozzle.

 •  Before closing the fan door, turn the fan blade 

in a safe position, to avoid that the door hits the 
fan.

If the refrigerant system has been opened, the 
system has to be flushed with dry air or nitrogen 
to remove moisture and a new filter drier has to 
be installed. If evacuation of refrigerant has to be 
done, it shall be done in such a way that no refrige-
rant can escape to the environment.

16 – Declaration of incorporation 
 •  

Pressure Equipment Directive 2014/68/EU

EN 378-2:2016

 - Refrigerating systems and Heat 

Pumps - Safety and environmental requirements-
Parts 2: Design, construction, testing, marking 
and documentation.

Low Voltage Directive 2014/35/EU

 EN 60335-

1:2012 + A11:2014- Household and similar elec-
trical appliances-Safety-Part 1: General requi-

Summary of Contents for Optyma Plus

Page 1: ...h p 56 E Greek p 62 Norsk Norwegian p 68 B lgarski Bulgarian p 74 Rom n Romanian p 80 e tina Czech p 86 Polski Polish p 92 Russian p 98 GA Drawings GA tegninger GA Zeichnungen Sch mas GA Diagramas GA...

Page 2: ...4X41 250 550 456 456 Housing 2 Code n 114X32 or 114X42 250 650 530 530 Housing 3 Code n 114X33 or 114X43 250 760 581 581 Housing 4 Code n 114X34 or 114X44 250 900 700 700 Picture 1 Minimum mounting di...

Page 3: ...switches Replaceable filter drier Electronic controller Main circuit breaker Main switch with overload protection Fan and compressor capacitors Compressor contactor Supply monitoring relay Robust wea...

Page 4: ...are also equipped with phase sequence relay to protect the unit against phase loss sequence asymmetry and under over voltage For units with a 3 phase scroll compressor OP MPXMxxxxxxxxE correct phase s...

Page 5: ...nspections 14 Emergency running without controller In case of controller failure the condensing unit can still be operated when the controller standard wiring picture 4 is modified into a temporary wi...

Page 6: ...testing and test methods part 2 Condensing units 17 Warranty Always transmit the model number and serial number with any claim filed regarding this pro duct The product warranty may be void in followi...

Page 7: ...interface Module B Plus powers on power LED 1 will be solid red all the time When the Module is powered off power LED 1 will be off If Module B Plus powers on and has no error status LED 2 will be so...

Page 8: ...k Tryk p den nederste knap for at skifte til tempe raturv rdien for kondenseringstrykket Billede 3 Elektronisk regulatordisplay W Q R X Z Y Q Luft ind R Luft ud Enhed W mm X mm Y mm Z mm Hus 1 Kodenr...

Page 9: ...ter Elektronisk regulator Hovedafbryder hovedafbryder med overbe lastningssikring Ventilator og kompressorkondensatorer Kompressorkontaktor Forsyningsoverv gningsrel Robust vejrbestandigt hus V skeind...

Page 10: ...mpres sorens omdrejningsretning p aggregater med en 3 faset scroll kompressor OP MPXMxxxxxxxxE Find faser kkef lgen ved hj lp af en fasem ler for at etablere faser kkef lgen for fase L1 L2 og L3 Tilsl...

Page 11: ...og t thed kontrolleres Not r b de k lemiddeltypen og fyldningen foruden driftsbetingelserne Dette anvendes som referencepunkt ved fremtidige eftersyn 14 N ddrift uden regulator Kondenseringsaggregatet...

Page 12: ...g v skek lere til pro cesk ling Kondenseringsaggregatm linger er udf rt i henhold til standarden EN 13771 2 2017 Kom pressorer og kondenserende enheder til k ling Ydeevnepr vning og pr vningsmetoder D...

Page 13: ...r slukket vil LED 1 v re slukket Hvis Modul B Plus t nder og ikke har nogen fejl vil LED 2 v re konstant gr n Se billede 6 vedr rende placering af LED 1 og LED 2 p Modul B Plus Hvis Modul B Plus t nde...

Page 14: ...017 OP MPYM008 009 012 014 OP MPHM007 010 012 015 018 H1 OP LPQM026 048 068 074 OP MPBM018 024 026 034 OP MPXM034 046 057 OP MPGM033 34 OP MPHM026 034 OP LPHM026 H2 Instructions 104 AN18658643414604 0...

Page 15: ...on are in mm Dansk Legend A 12 hul til montering B Skueglas C Regulatordisplay D Luft ind E Luft ud F Suger r G V sker r H Typeskilt Elektriske ledninger Bem rk Alle m l angives i mm Deutsch Legende A...

Page 16: ...ning voor de bevestiging B Kijkglas C Regelaar display D Luchtinlaat E Luchtuitlaat F Zuigpoort G Vloeistofpoort H Typeplaatje Elektrische kabels Opmerking alle afmetingen zijn in mm Suomi Legenda A 1...

Page 17: ...dge Switch auto reset PSL R1 Ambient Temperature sensor T4 R2 Discharge Temperature Sensor T2 R3 Suction Temperature Sensor T3 R8 Discharge Temperature Sensor T1 Insulation P00 Models OP LPQM017 026 0...

Page 18: ...s 7 Fl ssigkeits Kugelabsperrventil 8 Saugseitiges Kugelabsperrventil B1 Druckmessaufnehmer Hochdruck P1 B2 Druckmessaufnehmer Niederdruck P2 B3 Hochdruck Patronendruckschalter automa tisches Zur ckse...

Page 19: ...presostat automatick reset PSL R1 Sn ma teploty okol T4 R2 Sn ma v tla n teploty T2 R3 Sn ma sac teploty T3 R8 Sn ma v tla n teploty T1 Izolace Polski Legenda 1 Spr arka 2 Elektryczny zaw r rozpr ny 3...

Page 20: ...Code G OP LPQM048 068 WD 1 Instructions 110 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02...

Page 21: ...Code G OP LPQM026 074 OP MPGM033 OP LPHM018 OP MPBM018 024 026 034 WD 2 Instructions 118U3276G AN18658643414604 001701 111 Danfoss Climate Solutions 2022 02...

Page 22: ...Code G OP MPXM068 080 Instructions 112 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 WD 3...

Page 23: ...Code E OP MPBM026 034 Instructions 118U3276G AN18658643414604 001701 113 Danfoss Climate Solutions 2022 02 WD 4...

Page 24: ...Code E OP LPQM048 068 074 OP MPXM034 046 057 Instructions 114 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 WD 5...

Page 25: ...Code E OP LPOM067 084 098 Instructions 118U3276G AN18658643414604 001701 115 Danfoss Climate Solutions 2022 02 WD 6...

Page 26: ...Instructions 116 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 Code E OP LPOM120 168 WD 7...

Page 27: ...Code G OP LPQM017 OP MPYM008 009 012 014 Instructions 118U3276G AN18658643414604 001701 117 Danfoss Climate Solutions 2022 02 WD 8...

Page 28: ...Instructions 118 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 Code G OP MPXM034 046 057 WD 9...

Page 29: ...Instructions 118U3276G AN18658643414604 001701 119 Danfoss Climate Solutions 2022 02 Code E OP LPQM215 271 OP MPXM125 162 WD 10...

Page 30: ...Instructions 120 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 Code E OP LPQM096 136 OP MPXM068 080 108 WD 11...

Page 31: ...Instructions 118U3276G AN18658643414604 001701 121 Danfoss Climate Solutions 2022 02 Code E P05 OP MPXM034 046 057 WD 12...

Page 32: ...Instructions 122 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 Code E P05 OP MPXM068 080 108 WD 13...

Page 33: ...Instructions 118U3276G AN18658643414604 001701 123 Danfoss Climate Solutions 2022 02 Code E P05 OP MPXM125 162 WD 14...

Page 34: ...ar g B4 Pressostato bassa pressione OFF 0 3bar g ON 0 5bar g C1 Condensatore di avviamento compressore C2 Condensatore di marcia compressore C3 Condensatore di marcia ventola 1 C4 Condensatore di marc...

Page 35: ...otorbeveiliging K1 Schakelaar K2 Startrelais M1 Compressor M2 Ventilatormotor 1 M3 Ventilatormotor 2 M4 Elektronisch expansieventiel Q1 Hoofdschakelaar R1 Sensor omgevingstemperatuur R2 R8 Voeler pers...

Page 36: ...e a motorului K1 Contactor K2 Releu de pornire M1 Compresor M2 Motor ventilator 1 M3 Motor ventilator 2 M4 Valv electronic de expansiune Q1 Comutator principal R1 Senzor temp ambiant R2 R8 Senzor temp...

Reviews: