2. Product description
2.11 Noise level
Cooling mode
Freezing mode
Condensing unit Model
:
OP-UPAC015COP04E
Condensing Unit Code
:
114X6003
Housing
:
-
Compressor
:
CO2
Electrical code
:
Compressor 400V/3~/50Hz, Fan 230V/1~/50Hz
Number of Fans
:
2
Document No
:
118A5274
Revision
:
A
63
125
250
500
1000
2000
4000
8000
16k
L
WA
OP-UPAC015COP04E
1/1 Octave dB(A)
63
63
63
68
71
69
65
58
-
72
Evaporation
temperature (°C)
Ambient
temperature (°C)
Superheat (K) Compressor
speed (rps)
Fan Speed
(rps)
1m
3m
10m
-10
32
10
104
2 fans x 16.67
62
52.5
42
Acoustic spectrum data are calculated and validated at addition of sound power levels of compressor and fan motor at full speed according to EN13215 conditions.
As compressor and fan motor are placed in a packaged unit, effect of noise reduction due to enclosure and insulation was considered for evaluation of sound power
The values are declared according to EN13215 at MBP conditions at full speed of compressor (104 rps) and full speed of fan motors (2 fans X 16.67 rps)
Subject to change without prior information, Please check Coolselector 2 / Product store for updated information.
Distance (in Meters)
Sound Pressure (dB(A))
Acoustic/Sound Spectrum Data (50Hz)
Model
Sound Power Spectrum, 1/1 Octave
Calculated Sound Pressure (Free Field) (dB(A))
Sound Power Spectrum
EN13215 Conditions - MBP
63
63
63
68
71
69
65
58
72
0
10
20
30
40
50
60
70
80
90
100
63
125
250
500
1000
2000
4000
8000
LWA
SO
UN
D
PO
W
ER (d
B(A
))
1/1 OCTAVE FREQUENCY (HZ)
Acoustic/Sound Spectrum (50Hz)
Weighted dB(A)
Condensing unit Model
:
OP-UPAC015COP04E
Condensing Unit Code
:
114X6003
Housing
:
-
Compressor
:
CO2
Electrical code
:
Compressor 400V/3~/50Hz, Fan 230V/1~/50Hz
Number of Fans
:
2
Document No
:
118A5274
Revision
:
A
63
125
250
500
1000
2000
4000
8000
16k
L
WA
OP-UPAC015COP04E
1/1 Octave dB(A)
63
62
65
68
72
70
67
64
-
72
Evaporation
temperature (°C)
Ambient
temperature (°C)
Superheat (K) Compressor
speed (rps)
Fan Speed
(rps)
1m
3m
10m
-35
32
10
104
2 fans x 16.67
62
52.1
42
Acoustic spectrum data are calculated and validated at addition of sound power levels of compressor and fan motor at full speed according to EN13215 conditions.
As compressor and fan motor are placed in a packaged unit, effect of noise reduction due to enclosure and insulation was considered for evaluation of sound power
The values are declared according to EN13215 at LBP conditions at full speed of compressor (104 rps) and full speed of fan motors (2 fans X 16.67 rps)
Subject to change without prior information, Please check Coolselector 2 / Product store for updated information.
Distance (in Meters)
Sound Pressure (dB(A))
Acoustic/Sound Spectrum Data (50Hz)
Model
Sound Power Spectrum
Sound Power Spectrum, 1/1 Octave
Calculated Sound Pressure (Free Field) (dB(A))
EN13215 Conditions - LBP
63
62
65
68
72
70
67
64
72
0
10
20
30
40
50
60
70
80
90
100
63
125
250
500
1000
2000
4000
8000
LWA
SO
UN
D
PO
W
ER (d
B(A
))
1/1 OCTAVE FREQUENCY (HZ)
Acoustic/Sound Spectrum (50Hz)
Weighted dB(A)
Fig. 3
Fig. 4
18
AB408540130380en-000102
© Danfoss | Climate Solutions | 2023.02
Application Guidelines