3. Application Range
3.1 Operation range
Note:
1. Install sufficient insulation on liquid feed piping and suction gas piping. (Refer to the insulation (*) thickness in the following table.)
Note:
Where the thermal conductivity of insulator is 0.035W/m-K, if the liquid feed pipe and the suction gas pipe touch each other, it could
cause a superheat as a result of heat transfer between these pipes. Separate these pipes effectively.
2. Do not use the unit in a corrosive atmosphere.
3. Arrange at site such that the degree of superheat of suction gas will fall within a range of 5 deg to 40 deg.
Use this condensing unit within the following operation ranges.
Item
Unit
Specifications
Refrigerant
-
R744
Evaporation temperature
°C
-45 ~ 5
Low pressure (LP)
bar abs
8.3 ~ 30.5
Suction gas temperature(Ts)
°C
Evaporating tempe40°C
Discharge temperature(Td)
°C
125 or under
Ambient temperature
°C
-20 ~ 43
Power supply voltage
-
Within ±10% of rated voltage
(380/400/415 V)
Voltage unbalance rate
-
Within ±2% of rated voltage
Type
OP-UPAC015COP04E
Pipe section
Liquid feed
Suction
For cooling
20mm
30mm
For freezing
30mm
40mm
-50
-45
-40
-35
-30
-25
-20
-15
-10
5
10
-5
0
-20
-30
-10
0
10
20
30
40
43
43
50
Outdoor air temperature °C
Evaporation temperature °C