background image

© Danfoss | DCS (vt) | 2021.02

AN36292867744601-000101 | 5

Defrost

Evaporator fans

Alarms

Level 1

Level 2

Description

Values

Min.

Def.

Max.

dEF

d0

Defrost frequency (Time between 2 starts)

H.

0

6

96

d1

Maximum defrost duration (

0

=defrost deactivated)

Min.

0

*

255

d2

Type of message during the defrost:

0

=Displays the real temperature; 

1

=Displays the temperature at the start of 

the defrost; 

2

=Displays the dEF message

0

2

2

d3

Maximum duration of the message

(Time added at the end of the defrost process)

Min.

0

5

255

d4

Final defrost temperature (by probe) (If I00 ≠ 1)

ºF

-58

46.4

122

d5

Defrost on connecting the unit:

0

=NO First defrost according to d0; 

1

=YES, First defrost according to d6

0

0

1

d6

Delay of the defrost start on connecting the unit

Min.

0

0

255

d7**

Type of defrost:

0

=Resistors; 

1

=Air/fans, 

2

=Hot gas; 

3

=Reversal of cycle

0

*

3

d8

Count of time between defrost periods:

0

=Total real time, 

1

 =Sum of compressor connected time

0

0

1

d9

Drip time when completing defrost (Shutdown of compressor and fans)

Min.

0

1

255

EP

Exit to level 1

Level 1

Level 2

Description

Values

Min.

Def.

Max.

FAn

F0

Shutdown temperature of fans

ºF

-58

113

122

F1

Probe 2 differential if fans are shut down

ºF

0.1

3.6

36

F2

Shut down fans when the compressor shuts down 

0

=No, 

1

=Yes

0

0

1

F3

Status of the fans during the defrost 

0

=Shut down; 

1

=Running

0

0

1

F4

Delay of start-up after defrost (If F3=0)

It will only actuate if it is higher than 

d9

Min.

0

2

99

EP

Exit to level 1

Level 1

Level 2

Description

Values

Min.

Def.

Max.

AL

A0

Configuration of the temperature alarms 

0

=Relative to SP 

1

=Absolute

0

1

1

A1

Alarm for maximum in probe 1 (It should be higher than the SP)

ºF

A2

210

210

A2

Alarm for minimum in probe 1 (It should be lower than the SP)

ºF

-58

-58

A1

A3

Delay of temperature alarms in the start-up

Min.

0

0

120

A4

Delay of temperature alarms from the end of a defrost

Min.

0

0

99

A5

Delay of temperature alarms from when the 

A1

 or 

A2

 value is reached

0

30

99

A6

Delay of the external alarm/Severe external alarm on receiving a signal in 

digital input (

I10

 or 

I20

 =2 or 3)

Min.

0

0

120

A7

Delay of external alarm deactivation/Severe external alarm deactivation 

when the signal in digital input disappears (

I10

 or 

I20

=2 or 3)

Min.

0

0

120

A8

Show warning if the defrost ends for maximum time, 

0

=No, 

1

=Yes

0

0

1

A9

Relay alarm polarity

0

= Relay ON in alarm (OFF without alarm); 

1

= Relay OFF in alarm (ON 

without alarm)

0

0

1

A10

Differential of temperature alarms (

A1

 and 

A2

)

ºF

0.1

1.8

36

A12

Delay of open door alarm (If 

I10

 or 

I20

=1)

Min.

0

10

120

EP

Exit to level 1

* According to wizard.

** It can only be modified using the configuration wizard (InI).

Summary of Contents for Optyma AK-RC 251

Page 1: ...are programmable and their operation depends on the configuration The function of the digital inputs depends on the configuration The recommended currents and powers are the maximum working currents a...

Page 2: ...pressing once mutes the acoustic alarm Pressing for 3 seconds accesses the Set Point setting Indicators Fixed Stand By Mode activated Regulation is paused Flashing Controlled shutdown process for the...

Page 3: ...ters Diagram to be used Cold regulation Defrost Evaporator fans o00 I00 I10 I11 I20 I21 d1 d7 F3 0 Demo Mode it displays the temp but does not regulate or activate relays 1 Solenoid Electric Yes 0 2 0...

Page 4: ...0 Minimum time of compressor in OFF 1 Minimum time of compressor in OFF and in ON in each cycle 0 0 1 C5 Protection delay time Value of the option selected in parameter C4 Min 0 0 120 C6 COOL relay s...

Page 5: ...en the compressor shuts down 0 No 1 Yes 0 0 1 F3 Status of the fans during the defrost 0 Shut down 1 Running 0 0 1 F4 Delay of start up after defrost If F3 0 It will only actuate if it is higher than...

Page 6: ...ure switch 8 Remote Stand by 0 8 I11 Polarity of the digital input 1 0 Activates on closing contact 1 Activates on opening contact 0 1 I20 Configuration of digital input 2 0 Deactivated 1 Door contact...

Page 7: ...in A1 has been reached AL Minimum temperature alarm in control probe The temperature value programmed in A2 has been reached AE External alarm activated by digital input AES Severe external alarm act...

Page 8: ...15 A 250 V UL 60730 9 FLA 54 LRA 240 V AC UL 60730 RES 12 A 240 V AC NC EN60730 1 15 13 A 250 V UL 60730 6 FLA 36 LRA 240 V AC UL 60730 RES 6A 240 V AC Relay AUX 2 SPDT 16 A NO EN60730 1 12 9 A 250 V...

Page 9: ...i n debe tener en cuenta las normas locales vigentes Los rel s AUXILIARES son programables y su funcionamiento depende de la configuraci n La funci n de las entradas digitales depende de la configurac...

Page 10: ...ica Presionar este bot n durante 3 segundos accede al ajuste del Set Point de temperatura Indicadores Fijo Modo Stand By activo el control del cuarto fr o esta detenido Intermitente Proceso de paro co...

Page 11: ...laci n Par metros Diagramma a utilizar Regulaci n del fr o Deshielo Ventiladores evaporador o00 I00 I10 I11 I20 I21 d1 d7 F3 0 Modo demo muestra temperatura en pantalla pero no regula temperatura ni a...

Page 12: ...el compresor 0 Tiempo m nimo del compresor en OFF 1 Tiempo m nimo del compresor en OFF y en ON en cada ciclo 0 0 1 C5 Tiempo de retraso de la protecci n Valor de la opci n elegida en par metro C4 Min...

Page 13: ...rar compresor 0 No 1 Si 0 0 1 F3 Estado de los ventiladores durante el deshielo 0 Parados 1 Encendidos 0 0 1 F4 Retraso de arranque despu s del deshielo Si F3 0 Solo se activa si es superior a d9 Min...

Page 14: ...baja presi n 8 Stand by remoto 0 8 I11 Polaridad de la entrada digital 1 0 Activa en contacto cerrado 1 Activa en contacto abierto 0 1 I20 Configuraci n de la entrada digital 2 0 Desactivada 1 Contact...

Page 15: ...ado el valor de temperatura programado en A1 AL Alarma de temperatura m nima en sensor de control Se ha alcanzado el valor de temperatura programado en A2 AE Alarma externa activada por entrada digita...

Page 16: ...0 V AC UL 60730 RES 12 A 240 V AC NC EN60730 1 15 13 A 250 V UL 60730 6 FLA 36 LRA 240 V AC UL 60730 RES 6A 240 V AC Relevador AUX 2 SPDT 16 A NO EN60730 1 12 9 A 250 V UL 60730 5 FLA 30 LRA 240 V AC...

Reviews: