© Danfoss | DCS (vt) | 2021.02
AN36292867744601-000101 | 7
Information (reading only)
Messages
Level 1
Level 2
Description
Values
Min.
Def.
Max.
tid
InI
Option chosen in the configuration wizard
Pd**
Pump down active?
0
=No,
1
=Yes
PU
Program version
Pr
Program revision
bU
Bootloader version
br
Bootloader revision
PAr
Parameter map revision
EP
Exit to level 1
Messages
A
R
Pd
Pump down malfunction error (Shutdown)
LP
Pump down malfunction error (Start-up)
E1/E2/E3
Probe 1/2/3 failure (Open circuit, crossed circuit or temperature outside the limits of the probe)
Ad0
Open door alarm. Only if the door stays open for a greater time than is indicated in parameter
A12
AH
Maximum temperature alarm in control probe. The temperature value programmed in
A1
has been reached
AL
Minimum temperature alarm in control probe. The temperature value programmed in
A2
has been reached
AE
External alarm activated (by digital input)
AES
Severe external alarm activated (by digital input)
Adt
Defrost alarm concluded due to time-out. The time established in
d1
has been exceeded
HCP
HACCP alarm. The temperature has reached the value of parameter
h1
during a longer period than has been
established in
h2
hCP + PF
HACCP alarm due to a fault in the power supply. The temperature established in
h1
has been reached following a
fault in the power supply
dEF
Indicates that a defrost is being performed
PAS
Access code (Password) request. See parameters
b10
and
PAS
S1 - S2
Shown sequentially with the temperature:
The controller is in demo mode, the configuration has not been
made.
** It can only be modified using the configuration wizard (InI).
A:
Activates the acoustic alarm
R:
Activates the alarm relay