Configuración básica

Entradas y salidas

Alarma HACCP

Nivel 1

Nivel 2

Descripción

Valores

Min.

Def.

Max.

bcn

b00

Retraso de todas las funciones al recibir el voltaje de alimentación

Min.

0

0

255

b01

Temporizador de la luz del cuarto frio

Min.

0

0

999

b10

Función del código de acceso (Password)

0

=Inactivo, 

1

=Bloqueo de acceso a parámetros, 

2

=Bloqueo del teclado

0

0

2

PAS

Código de acceso (Password)

0

0

99

b20

Dirección MODBUS

1

1

247

b21

Velocidad de comunicación: 

0

=9600 bps, 

1

=19200 bps, 

2

=38400 bps, 

3

=57600 bps

bps

0

0

3

b22

Alarma acústica habilitada: 

0

= No, 

1

=Si

0

1

1

Unt

Work units: 

0

=ºC, 

1

=ºF

0

1

1

EP

Salida a nivel 1

Nivel 1

Nivel 2

Descripción

Valores

Min.

Def.

Max.

In0

I00

Sensores conectados

1

=Sensor 1 (Cámara),

 2

=Sensor 1 (Cámara) + Sensor 2 (Evaporador)

1

2

2

I10**

Configuración de la entrada digital 1

0

=Desactivada, 

1

=Contacto de puerta, 

2

=Alarma externa,

3

=Alarma externa severa, 

4

=Cambio de SP, 

5

=Deshielo remoto,

6

=Bloqueo de deshielo, 

7

=Switch de baja presión, 

8

=Stand-by remoto

0

*

8

I11

Polaridad de la entrada digital 1

0

=Activa en contacto cerrado; 

1

=Activa en contacto abierto

0

*

1

I20

Configuración de la entrada digital 2

0

=Desactivada, 

1

=Contacto puerta, 

2

=Alarma externa,

3

=Alarma externa severa, 

4

=Cambio de SP, 

5

=Desescarche remoto,

6

=Bloqueo de deshielo, 

7

=Registrar sensor, 

8

=2º Sensor de evaporador,

9

=Switch de alta presion para gas caliente, 

10

=Stand-by remoto

0

0

10

I21

Polaridad de la entrada digital 2

0

=Activa en contacto cerrado; 

1

=Activa en contacto abierto

0

0

1

O00**

Configuración del relevador AUX1

0

=Desactivado, 

1

=Compresor/Resistencia al cárter, 

2

=Luz, 

3

=Control 

virtual

0

*

3

O10

Configuración del relevador AUX2

0

=Desactivado, 

1

=Alarma, 

2

=Luz, 

3

=Control virtual, 

4

=Resistencia 

del marco de puerta, 

5

=Deshielo de 2º evaporador, 

6

=Acción Igual al 

solenoide, 

7

=Acción igual al estado del equipo

0

2

7

EP

Salida a nivel 1

Nivel 1

Nivel 2

Descripción

Valores

Min.

Def.

Max.

HCP

h1

Temperatura máxima para alarma HACCP

ºF

-58

210

210

h2

Tiempo máximo permitido para activación de alarma HACCP 

(

0

=Deshabilitada)

H.

0

0

255

EP

Salida a nivel 1

* Según asistente de configuración.

** Solo se puede modificar mediante el asistente de configuración (InI).

Summary of Contents for Optyma AK-RC 251

Page 1: ...are programmable and their operation depends on the configuration The function of the digital inputs depends on the configuration The recommended currents and powers are the maximum working currents a...

Page 2: ...pressing once mutes the acoustic alarm Pressing for 3 seconds accesses the Set Point setting Indicators Fixed Stand By Mode activated Regulation is paused Flashing Controlled shutdown process for the...

Page 3: ...ters Diagram to be used Cold regulation Defrost Evaporator fans o00 I00 I10 I11 I20 I21 d1 d7 F3 0 Demo Mode it displays the temp but does not regulate or activate relays 1 Solenoid Electric Yes 0 2 0...

Page 4: ...0 Minimum time of compressor in OFF 1 Minimum time of compressor in OFF and in ON in each cycle 0 0 1 C5 Protection delay time Value of the option selected in parameter C4 Min 0 0 120 C6 COOL relay s...

Page 5: ...en the compressor shuts down 0 No 1 Yes 0 0 1 F3 Status of the fans during the defrost 0 Shut down 1 Running 0 0 1 F4 Delay of start up after defrost If F3 0 It will only actuate if it is higher than...

Page 6: ...ure switch 8 Remote Stand by 0 8 I11 Polarity of the digital input 1 0 Activates on closing contact 1 Activates on opening contact 0 1 I20 Configuration of digital input 2 0 Deactivated 1 Door contact...

Page 7: ...in A1 has been reached AL Minimum temperature alarm in control probe The temperature value programmed in A2 has been reached AE External alarm activated by digital input AES Severe external alarm act...

Page 8: ...15 A 250 V UL 60730 9 FLA 54 LRA 240 V AC UL 60730 RES 12 A 240 V AC NC EN60730 1 15 13 A 250 V UL 60730 6 FLA 36 LRA 240 V AC UL 60730 RES 6A 240 V AC Relay AUX 2 SPDT 16 A NO EN60730 1 12 9 A 250 V...

Page 9: ...i n debe tener en cuenta las normas locales vigentes Los rel s AUXILIARES son programables y su funcionamiento depende de la configuraci n La funci n de las entradas digitales depende de la configurac...

Page 10: ...ica Presionar este bot n durante 3 segundos accede al ajuste del Set Point de temperatura Indicadores Fijo Modo Stand By activo el control del cuarto fr o esta detenido Intermitente Proceso de paro co...

Page 11: ...laci n Par metros Diagramma a utilizar Regulaci n del fr o Deshielo Ventiladores evaporador o00 I00 I10 I11 I20 I21 d1 d7 F3 0 Modo demo muestra temperatura en pantalla pero no regula temperatura ni a...

Page 12: ...el compresor 0 Tiempo m nimo del compresor en OFF 1 Tiempo m nimo del compresor en OFF y en ON en cada ciclo 0 0 1 C5 Tiempo de retraso de la protecci n Valor de la opci n elegida en par metro C4 Min...

Page 13: ...rar compresor 0 No 1 Si 0 0 1 F3 Estado de los ventiladores durante el deshielo 0 Parados 1 Encendidos 0 0 1 F4 Retraso de arranque despu s del deshielo Si F3 0 Solo se activa si es superior a d9 Min...

Page 14: ...baja presi n 8 Stand by remoto 0 8 I11 Polaridad de la entrada digital 1 0 Activa en contacto cerrado 1 Activa en contacto abierto 0 1 I20 Configuraci n de la entrada digital 2 0 Desactivada 1 Contact...

Page 15: ...ado el valor de temperatura programado en A1 AL Alarma de temperatura m nima en sensor de control Se ha alcanzado el valor de temperatura programado en A2 AE Alarma externa activada por entrada digita...

Page 16: ...0 V AC UL 60730 RES 12 A 240 V AC NC EN60730 1 15 13 A 250 V UL 60730 6 FLA 36 LRA 240 V AC UL 60730 RES 6A 240 V AC Relevador AUX 2 SPDT 16 A NO EN60730 1 12 9 A 250 V UL 60730 5 FLA 30 LRA 240 V AC...

Reviews: