Do not use any Hand tools to modify 
the Potentiometer setting. This 
operation must be done by Hands 
with proper PPE.
Do not rotate this Potentiometer 
setting screw in Counter-clockwise 
direction. This can potentially 
reduce the fan speed, risking the 
performance and compressor safety

8 – Safety

Electrical box door should be in 
closed condition before connecting to 
power supply.
Discharge tube temperature will 
go upto 120°C during unit running 
condition.
Recommended to install PRV inside 
unit and release of refrigerant should 
routed to atmosphere directly.

Units will be with 3/8" NPT adapter plug. User can 
select various options as mentioned in EN378-
2:2016 Article § 6.2.2.3 
 •  The unit/installation into which the condensing 

unit is mounted/integrated, must be in 
accordance with the PED.

 •  As per EU F-gas regulation, R1234yf, R454C & 

R455A are considered as A2L refrigerant. Optyma™ 
Slim Pack units are qualified with R1234yf, R454C 
& R455A. All precaution and safety measure to be 
taken care before and after installation.

 •  All Optyma™ Slim pack condensing units are 

supplied with adjustable dual pressure switch 
(KP-17WB) with maximum 0.5A current rating.

 •  In order to avoid electric arc between hermetic 

connector pins, compressor must not start or 
electrical tests such dielectric strength must not 
be performed while the refrigerating system 
under vacuum.

 •  All components should be compatible to use with  

specified refrigerants according to Optyma™ Slim 
Pack condensing units codes .Refer Annex A.

 •  Optyma™ Slim Pack condensing units have pre 

ventilation via condenser fan prior to  compressor 
starting (30 seconds). Never disconnect or modify 
timer settings.

 •  Beware of hot and extremely cold components.
 •  Beware of moving components. Power supply 

should be disconnected while servicing.

 •  

Danfoss always recommend to main IP54 
electrical box. In case of any damage to rubber 
gasket, customer should replace immediately.

  •   Compressor has Internal overload protector (OLP).  

Its will protect compressor pressure going 

 

beyond 32 bar pressure.

  •  No valves and detachable joints shall be located 

in areas accessible to the general public except 
when they comply with EN 16084

  •  Refrigerant piping shall be protected or enclosed 

to avoid damage.

 •  Field piping should be installed such that it will 

be free from corrosive or salty environment to 
avoid corrosion in copper /Aluminum piping.

 •  In case of fire incidence, pressure increases due 

to increasing in temperature at receiver. Hence it 
is very important to install the PRV.

9 – Filling the system
 •  Before filling the refrigerant into the Optyma™ 

Slim Pack condensing unit wear appropriate 
Personal Protective Equipment (PPE).

 •  Never start the compressor under vacuum. Keep 

the compressor switched off.

 •  If additional oil is required please refer to the 

compressors label for type of oil. Check the 
Compressor application guideline for minimum 
oil level limit before refilling.

 •  Use only the refrigerant for which the unit is 

designed for. Check unit name plate for more 
details.

 •  

For glide refrigerants such as R454C, R455A, 
R448A, R449A, R452A use liquid valve in the 
refrigerant cylinder to charge.

 • 

 

Fill the refrigerant in liquid phase into the 
condenser or liquid receiver. Ensure a slow 
charging of the system to 4 – 5 bar for R448A, 
R449A, R452A, R407A, R407F, R507, R404A, , 
R454C or R455A and approx. 2 bar for R134a, 
R513A. R1234yf.

 •  Do not put liquid refrigerant through suction line.
 •  It is not allowed to mix additives with the oil 

and/or refrigerant. The remaining charge is done 
until the installation has reached a level of stable 
nominal condition during operation.

 •  Never leave the filling cylinder connected to the 

circuit.

 •  When charging A2L refrigerant make sure that 

the charging area is well ventilated

 •  The Liquid receiver is fitted with Rotolock Valve 

for service purpose. As a factory setting, the 
valve will be in completely OPEN position. During 
maintenance and Pump down, the Valve must 
be Rotated in Clockwise direction until it is in 
completely CLOSED position.

 •  

Suction, Liquid valves and Receiver Rotolock 
valves as Schrader port for service operation like 
Gas Charging, pressure measurement.

10 – Verification before commissioning

Use safety devices such as safety 
pressure switch and mechanical 
relief valve (not supplied) in 
compliance with both International 
and local applicable regulations and 
safety standards. Ensure that they 
are operational and properly set.
Check that the settings of high-
pressure switches and relief valves 
don’t exceed the maximum service 
pressure of any system component.

 •  Verify that all electrical connections are properly 

fastened and in compliance with international 
and local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-up 
and start-up after prolonged shut-down period.

 • 

 

Crankcase heater must be firmly fixed with 
compressor shell. Ensure that it does not fall 
down.

 •  Electrical panel door must be firmly closed using 

the knob in door panel. For W09 version only, the 
front door of the Electrical box is fastened by 4 
screws on each corners. 

•  

All interconnecting tubes with  (liquid and 
suction) Optyma™ Slim pack condensing unit 
must be sized properly depending upon the 
evaporator location.

  •  Pressure drop in the suction and liquid line pipes 

must be evaluated as per evaporator location 
and distance (refer coolselector2).

 •  Optyma™ Slim Pack condensing units suction/

discharge pressure and temperatures must be 
within the operating envelope, never operate 
condensing unit suction pressure below absolute 
pressure (vacuum).

11 – Start-up
 • 

 

Never start the unit when no refrigerant is 
charged.

 •  All service valves must be in the open position.

See picture 3.

 • 

 

Check compliance between unit and power 
supply.

 •  Check that the crankcase heater is working.
 •  Check that the fan can rotate freely.
 

• 

 

Check that the protection sheet has been 
removed from the backside of condenser.

 •  Balance the HP/LP pressure.
 •  

Energize the unit. Condenser fan must start 
promptly and after 30 seconds of time delay the 
compressor starts (pre ventilation).

 •  If the fan motor rotation direction is correct the 

low pressure indication on the low pressure 
gauge shall show a declining pressure and the 
high pressure indication on the high pressure 
gauge shall show an increasing pressure.

 •  Ensure you have read the installation guideline 

that is delivered with the condensing unit

 •  Only use the correct refrigerant(s) as detailed on 

the data plate

 •  Check compressor oil level
 •  Check all mechanical connections are tight
 •  Check all electrical overload settings are correct 

(See Annex D - Wiring Drawing).

12 – Check with running unit
 •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

 •  Check current drawn and voltage.
 •  Check suction superheat to reduce risk of liquid 

slugging.

 •  For glide refrigerants use temperature difference 

between saturated dew point at suction pressure 
and Suction line temperature on the tube.

 • 

 

When a compressor sight glass is provided 
observe the oil level at start and during operation 
to confirm that the oil level remains visible.

 •  Respect the operating limits.
 

• 

 

Optyma™ Slim Pack condensing units are 
designed to operate up to 43°C. During normal 
operation or peak operation, saturated dew 
point condensing temperature not to exceed 
corresponding to 63 °C for R448A, R449A, R452A, 
R454C, R455A. Saturated dew point condensing 
temperature not to exceed corresponding to 

 

65 °C for R134a, R513A & R1234yf.

 •  Check all interconnecting tubes are free from 

abnormal vibrations. If in case of excess vibrations, 
require corrective measures such as supporting 
brackets, clamps.

 •  

When needed, additional refrigerant in liquid 
phase may be added in the low-pressure side 
as slow and far away as possible from the 
compressor. The compressor must be operating 
during this process.

 •  Do not overcharge the system.
 •  Follow the local regulations for restoring the 

refrigerant from unit.

 •  Never release refrigerant to free atmosphere.
 •  

Before leaving the installation site, carry out 
a general installation inspection regarding 
cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference for 
future inspections.

 •  Check refrigerant charge and running currents of 

motors to ensure correct operation 

 •  Check compressor suction superheat to reduce 

risk of liquid slugging

 •  Allow the system to run for 3 – 4 hours. Check 

compressor oil level and top up with the correct 

Summary of Contents for MSIM

Page 1: ...a Technische Daten Donn es techniques Datos t cnicos Dati tecnici Dados t cnicos Dane techniczne p 50 Annex B KP switch settings KP Schaltereinstellungen R glages des contacteurs KP Ajustes de los int...

Page 2: ...ver used for other CFC HFO or HCFC refrigerants Use clean and dehydrated refrigeration grade Copper Aluminium tubes with appropriate thickness and silver alloy brazing material Use clean and dehydrate...

Page 3: ...iping material should comply with EN12735 1 And all pipe joints should comply with EN14276 2 At filed installation support to added according to size and weight Recommended maximum spacing for pipe su...

Page 4: ...ation like Gas Charging pressure measurement 10 Verification before commissioning Use safety devices such as safety pressure switch and mechanical relief valve not supplied in compliance with both Int...

Page 5: ...e that proper model designation and direction of flow Ensure to conduct the leakage check after replacement The condenser must be checked at least once a year for clogging and be cleaned if deemed nec...

Page 6: ...ign requirements for energy related products REGULATION EU 2015 1095 implementing Eco design Directive 2009 125 EC with regard to Eco design requirements for professional refrigerated storage cabinets...

Page 7: ...4yf 8 bar 360 1 turn Approx 0 8 bar Clockwise rotation Increase pressure setting Counter clockwise rotation Decrease pressure setting 061H3248 V R404A R452A R507 15 bar X R404A R507 R407A R407F R448A...

Page 8: ...en Anforderungen des Verfl ssigungssatzes entspricht siehe Typenschild am Ger t Verwenden Sie bei der Installation der Verfl ssigungss tze f r die K ltemittel R454C R455A und R1234yf nur Teile die spe...

Page 9: ...zt und laut ihrem jeweiligen Hersteller keine Z ndquelle f r zugelassene K ltemittel sind Die Feldverdrahtung Anschluss und Kommunikationsleitung darf nur durch IP65 Kabelverschraubungen und Kabeleinf...

Page 10: ...t m ssen so verlegt werden dass sie nicht in einer korrosiven oder salzhaltigen Umgebung liegen um Korrosion in Kupfer Aluminiumrohrleitungen zu vermeiden Bei einem Brand erh ht sich der Druck aufgrun...

Page 11: ...r dass die Wartung entsprechend den Installationsanweisungen durchgef hrt wird 13 Wartung Schalten Sie den Verfl ssigungssatz immer mit dem Hauptschalter aus bevor Sie die L ftert r ffnen Der in der A...

Page 12: ...n und W rmepumpen Sicherheitstechnische und umweltrelevante Anforderungen Teil 2 Konstruktion Herstellung Pr fung Kennzeichnung und Dokumentation Niederspannungsrichtlinie 2014 35 EU EN60335 1 2012 A1...

Page 13: ...n Doppeldruckschalter 18 K ltemitteleinstellung Doppeldruckschalter K ltemittel Hochdruckeinstellungen bar g Niederdruckeinstellungen bar g ON EIN OFF AUS ON EIN OFF AUS R404A R507 R407A R407F R448A R...

Page 14: ...e ambiante d utilisation du groupe ne doit pas d passer 50 C lors du cycle d arr t Assurez vous que l alimentation lectrique correspond aux caract ristiques du groupe voir la plaque signal tique dans...

Page 15: ...our le c blage in situ ne percer que les trous strictement n cessaires Aucun trou perc ne doit tre laiss sans c ble En cas de per age ind sirable toute la plaque presse toupe doit tre remplac e 118U52...

Page 16: ...lle EPI appropri s pour le remplissage en r frig rant du groupe de condensation Optyma Slim Pack Ne d marrez jamais le compresseur lorsqu il se trouve sous vide Maintenez le compresseur hors tension S...

Page 17: ...conformit aux normes locales Veillez ce que la maintenance soit effectu e conform ment aux instructions d installation 13 Maintenance Arr tez toujours l unit l aide de l interrupteur g n ral avant de...

Page 18: ...et documentation Directive basse tension 2014 35 UE EN 60335 1 2012 A11 2014 Appareils lectrodomestiques et analogues S curit Partie 1 Exigences g n rales pour tous les groupes de condensation mentio...

Page 19: ...de pressostat double 18 Pressostat double R glage du r frig rant R frig rants Param tres de haute pression bar g Param tres de basse pression bar g MARCHE ARR T MARCHE ARR T R404A R507 R407A R407F R44...

Page 20: ...nte de la unidad no debe superar los 50 C durante los ciclos de inactividad Aseg rese de que la fuente de alimentaci n sea compatible con los requisitos de la unidad consulte la placa de caracter stic...

Page 21: ...r sustituirse toda la placa del prensaestopas 118U5258 Repuesto prensaestopas El panel divisorio tiene aberturas espec ficas para ventilaci n previa no selle obstruya cierre las aberturas de ninguna m...

Page 22: ...racter sticas de la unidad para obtener m s informaci n Para los refrigerantes con deslizamiento como R454C R455A R448A R449A y R452A utilice la v lvula de l quido para cargar Llene el condensador o e...

Page 23: ...ese de que se realicen las inspecciones de servicio peri dicas necesarias para garantizar la fiabilidad del sistema de acuerdo con lo dispuesto en la legislaci n local vigente Para evitar que se produ...

Page 24: ...encionadas anteriormente DIRECTIVA sobre Eco dise o 2009 125 CE que establece un marco para determinar los requisitos de Eco dise o para productos relacionados con la energ a REGULACI N UE 2015 1095 q...

Page 25: ...antihora rio disminucion del ajuste de presi n 061H3248 V R404A R452A R507 15 bar X R404A R507 R407A R407F R448A R449A R452A excepto R134a y R513A 15 bar T R404A R507 R455A R454C R448A R449A R452A 15...

Page 26: ...e si installa l unit per l uso con refrigeranti R454C R455A e R1234yf utilizzare attrezzature specifiche per refrigeranti leggermente infiammabili che non siano mai state utilizzate per refrigeranti C...

Page 27: ...pannello divisorio dotato di aperture dedicate per la pre ventilazione non sigillare ostruire chiudere mai le aperture In caso di perdite incerte per evitare una concentrazione di refrigerante nel van...

Page 28: ...ettagli controllare la targhetta dell unit Per i refrigeranti con glide di temperatura come R454C R455A R448A R449A e R452A utilizzare una valvola liquido nel cilindro del refrigerante da caricare Rie...

Page 29: ...addetti alla manutenzione e gli installatori necessitano di DPI competenze e strumenti appropriati per svolgere l attivit di manutenzione La temperatura della tubazione pu superare i 100 C e pu causa...

Page 30: ...similare Parte 1 Requisiti generali per tutte le unit condensatrici sopra menzionate DIRETTIVA Ecodesign 2009 125 CE relativa all istituzione di un quadro per l elaborazione di requisiti per la proget...

Page 31: ...all applicazione 20 Impostazione del regolatore velocit del ventilatore EC B3 W09 Modello del controllore di velo cit delle ventole Controllore delle velocit delle ventole N parte di ricambio Lettera...

Page 32: ...talar unidades para refrigerantes R454C R455A e R1234yf utilize equipamento reservado especificamente para refrigerantes ligeiramente inflam veis que nunca tenha sido utilizado para outros refrigerant...

Page 33: ...rma Em caso de fugas incertas para evitar a concentra o de refrigerante no compartimento do compressor este possui um atraso de 30 segundos defini o de f brica n o reduza para uma defini o inferior a...

Page 34: ...sor para obter informa es sobre o limite m nimo de n vel de leo antes de reabastecer Utilize apenas o refrigerante para o qual a unidade foi concedida Verifique a placa de identifica o da unidade para...

Page 35: ...atura da superf cie s o perigosas e podem provocar les es permanentes Os operadores de manuten o e instaladores necessitam de EPI compet ncias e ferramentas adequadas para realizar a atividade de manu...

Page 36: ...Requisitos gerais para todas as unidades de condensa o acima mencionadas Diretiva sobre Eco design 2009 125 CE que estabelece um enquadramento para a defini o dos requisitos de Eco design para produt...

Page 37: ...Defini o do controlador de velocidade da ventoinha Motor da ventoinha EC B3 W09 Tipo de FSC Controlador de velocidade do ventilador N mero da pe a de reposi o Identifica o do Refrigerante Para o refr...

Page 38: ...stalowania agregat w na czynniki ch odnicze R454C R455A i R1234yf stosowa sprz t przeznaczony specjalnie do umiarkowanie atwopalnych czynnik w ch odniczych kt ry nigdy wcze niej nie by u ywany do inny...

Page 39: ...tych otwor w w aden spos b W celu unikni cia gromadzenia si czynnika ch odniczegowkomorzespr arkiwwynikuwycieku spr arka jest uruchamiana z 30 sekundowym op nieniem ustawienie fabryczne Nie zmniejsza...

Page 40: ...rmacji podanych jest na tabliczce znamionowej urz dzenia W przypadku czynnik w ch odniczych z po lizgiem temperaturowym takich jak R454C R455A R448A R449A i R452A do nape niania nale y stosowa zaw r c...

Page 41: ...siada odpowiednie rodki ochronyindywidualnej umiej tno ci i narz dzia do wykonywania czynno ci konserwacyjnych Tempe ratura rur mo e przekroczy 100 C i spowodowa powa ne oparzenia Nale y przeprowadza...

Page 42: ...u ytkowania Cz 1 Og lne wymagania dla wszystkich wy ej wymienionych agregat w skraplaj cych DYREKTYWA dotycz ca ekoprojektu 2009 125 WE ustanawiaj ca og lne zasady ustalania wymog w dotycz cych ekopr...

Page 43: ...bryczne presostatu podw jnego 18 Ustawienia czynnika ch odniczego dla presostatu podw jnego Czynniki ch odnicze Nastawy wysokiego ci nienia bar g Nastawy niskiego ci nienia bar g W WY W WY R404A R507...

Page 44: ...SVM MSTM MSSM MSIM R448A R449A R452A R407A R407F R507 R404A R134a R513A R1234yf R454C R455A B1 B2 EC B3 IP54 W09 W05 W09 2 35 C 50 C 3 A2L PED I II A 1 3 50 C R454C R455A R1234yf Optyma Optyma Slim Pa...

Page 45: ...SlimPack PED I II PED A NPT 3 8 Coolselector2 Loctite 554 30 Danfoss EN 14276 2 EN 16084 4 Optyma Slim Pack 2014 68 EC PED A 2 A 3 19 IP65 118U5258 30 30 EN12735 1 EN14276 2 EN12735 1 EN12735 2 5 25 6...

Page 46: ...R1234yf R454C R455A A2L Optyma Slim Pack R1234yf R454C R455A Optyma Slim Pack KP 17WB 0 5 Optyma Slim Pack A Optyma Slim Pack 30 Danfoss IP54 32 EN 16084 9 Optyma Slim Pack R454C R455A R448A R449A R45...

Page 47: ...olutions 2022 02 118A2176C AN37261865152501 010301 47 D 12 Optyma Slim Pack 43 C 63 C R448A R449A R452A R454C R455A 65 C R134a R513A R1234yf 3 4 24 13 100 C 30 Optyma Slim Pack A2L R454C R455A R1234yf...

Page 48: ...1 2 3 4 5 W09 1 2 3 4 1 2 3 4 1 2 3 4 1 3 4 2 1 2 3 4 1 2 3 4 14 2014 68 EU EN 378 2 2016 2 2014 35 EU EN 60335 1 2012 A11 2014 1 2009 125 EC EU 2015 1095 2009 125 EC EN 13771 2 2017 2 Danfoss Coolsel...

Page 49: ...23 2 1 R455A 21 25 2 1 R448A R449A 22 26 2 1 19 AC B1 B2 XGE 2C 061H3144 S R134a R513A R1234yf 8 360 1 0 8 061H3248 V R404A R452A R507 15 X R404A R507 R407A R407F R448A R449A R452A R134a R513A 15 T R4...

Page 50: ...ht glass yes yes Crankcase heater yes yes HP LP adjustable pressostat Auto Manual reset mode Auto Manual reset mode Access door s yes for E Box yes for E Box Acoustic insulation Provided as accessory...

Page 51: ...41 114X7294 OP MSSM021SC SC21G G G 1 3 I 32 3 8 3 8 B1 530 910 364 114X7233 114X7299 OP MSTM022DS DS22TB G T 3 4 II 32 1 2 1 2 B2 690 1079 464 114X7248 114X7304 OP MSSM026CS CS26TB G G 3 4 II 32 1 2 1...

Page 52: ...k W05 W09 Verfl ssigungssatz IP Schutzart IP54 IP54 K ltemittel Gruppe 1 Gruppe 2 Gruppe 1 Gruppe 2 Verdichtertechnologie Hubkolbenverdichter Scrollverdichter Hubkolbenverdichter Scrollverdichter Inte...

Page 53: ...4 II 32 1 2 1 2 B2 690 1079 464 114X7248 114X7304 OP MSSM026CS CS26TB G G 3 4 II 32 1 2 1 2 B2 690 1079 464 114X7234 114X7300 OP MSTM026DS DS26TB G T 3 4 II 32 1 2 1 2 B2 690 1079 464 114X7235 114X73...

Page 54: ...s 230 V Optyma Slim Pack W05 W09 Groupe de condensation niveau IP IP54 IP54 R frig rant Groupe 1 Groupe 2 Groupe 1 Groupe 2 Technologie du compresseur piston scroll piston scroll Bo tier de commande p...

Page 55: ...9 464 114X7248 114X7304 OP MSSM026CS CS26TB G G 3 4 II 32 1 2 1 2 B2 690 1079 464 114X7234 114X7300 OP MSTM026DS DS26TB G T 3 4 II 32 1 2 1 2 B2 690 1079 464 114X7235 114X7301 OP MSTM026DS DS26T3 E T...

Page 56: ...Controlador de velocidad para ventilador s Interruptor principal disyuntor s Secador del filtro conexiones roscadas s s Visor de l quido s s Resistencia de c rter s s Presostato ajustable de AP BP Mod...

Page 57: ...114X7293 OP MSSM018SC SC18G G G 1 3 I 32 3 8 3 8 B1 530 910 364 114X7241 114X7294 OP MSSM021SC SC21G G G 1 3 I 32 3 8 3 8 B1 530 910 364 114X7233 114X7299 OP MSTM022DS DS22TB G T 3 4 II 32 1 2 1 2 B2...

Page 58: ...400 V trifase e ventilatore 230 V monofase Optyma Slim Pack W05 W09 Unit condensatrice grado IP IP54 IP54 Refrigerante Gruppo 1 Gruppo 2 Gruppo 1 Gruppo 2 Tecnologia compressore Alternativo Scroll Al...

Page 59: ...3 I 32 3 8 3 8 B1 530 910 364 114X7241 114X7294 OP MSSM021SC SC21G G G 1 3 I 32 3 8 3 8 B1 530 910 364 114X7233 114X7299 OP MSTM022DS DS22TB G T 3 4 II 32 1 2 1 2 B2 690 1079 464 114X7248 114X7304 OP...

Page 60: ...0 V ventilador monof sico Optyma Slim Pack W05 W09 Unidade de condensa o n vel IP IP54 IP54 Refrigerante Grupo 1 Grupo 2 Grupo 1 Grupo 2 Tecnologia do compressor Alternativo Percorrer Alternativo Perc...

Page 61: ...8 3 8 B1 530 910 364 114X7241 114X7294 OP MSSM021SC SC21G G G 1 3 I 32 3 8 3 8 B1 530 910 364 114X7233 114X7299 OP MSTM022DS DS22TB G T 3 4 II 32 1 2 1 2 B2 690 1079 464 114X7248 114X7304 OP MSSM026C...

Page 62: ...ltr odwadniacz przy cza rubunkowe tak tak Wziernik tak tak Grza ka karteru tak tak Presostat regulowany HP LP Tryb automatycznego r cznego odblokowania Tryb automatycznego r cznego odblokowania Drzwic...

Page 63: ...8SC SC18G G G 1 3 I 32 3 8 3 8 B1 530 910 364 114X7241 114X7294 OP MSSM021SC SC21G G G 1 3 I 32 3 8 3 8 B1 530 910 364 114X7233 114X7299 OP MSTM022DS DS22TB G T 3 4 II 32 1 2 1 2 B2 690 1079 464 114X7...

Page 64: ...09 Optyma Slim Pack 8 G 230 1 E 400 3 230 1 Optyma Slim Pack W05 W09 IP IP54 IP54 1 2 1 2 IP54 IP54 Pressure Relief Valve Optyma Slim Pack A A2L N O L M L L M N O 250 80 550 550 1 Address Danfoss Ltd...

Page 65: ...690 1079 464 114X7248 114X7304 OP MSSM026CS CS26TB G G 3 4 II 32 1 2 1 2 B2 690 1079 464 114X7234 114X7300 OP MSTM026DS DS26TB G T 3 4 II 32 1 2 1 2 B2 690 1079 464 114X7235 114X7301 OP MSTM026DS DS26...

Page 66: ...12W 50VA 16A 96 240 240 120 FL A A C A D SPDT LP signal Listed refrigeration controller LP HP signal Contacts Cut In Cut In Cut In Cut out Cut out Cut out Differential Differential fixed Differential...

Page 67: ...e K hlstellenregler ND HD Signal Kontakte Einschaltwert Einschaltwert Einschaltwert Abschaltwert Abschaltwert Abschaltwert Differenz Differenz fest Differenz Spannung Nur Kupferdraht verwenden Anzugsd...

Page 68: ...P R gulateur d vaporateur r pertori Signal BP HP Contacts Enclenchement Enclenchement Enclenchement Coupure Coupure Coupure Diff rentiel Diff rentiel fixe Diff rentiel Tension Utiliser uniquement le f...

Page 69: ...aci n listado Se al LP HP Contactos Enganche Enganche Enganche Corte Corte Corte Diferencial Diferencial fijo Diferencial Tensi n Utilice nicamente cable de cobre Par de apriete de 20 lb in Para el us...

Page 70: ...ato segnale LP HP Contatti Cut In Cut In Cut In Cut out Cut out Cut out Differenziale Differenziale fisso Differenziale Voltaggio Usare esclusivamente filo di rame Coppia di serraggio 2 5 Nm 20lb in I...

Page 71: ...ar Desligar Diferencial Diferencial fixo Diferencial Tens o Use apenas fio de cobre Torque de aperto 20 lb pol Quando usado de acordo com os regulamentos UL HP BP man Reposi o BP aut Reposi o Teste ma...

Page 72: ...egulator urz dze ch odniczych Sygna NC WC Styki W czenie W czenie W czenie Wy czenie Wy czenie Wy czenie R nica za cze R nica za cze sta a R nica za cze Napi cie Stosowa tylko drut miedziany Moment ob...

Page 73: ...52501 010301 73 1 bar Pe 30in Hg KP17WB KP 17B 060 539366 060 539466 LR 112A 400 V AC1 10A AC3 10A AC11 10A DC 11 12 W 220 V A B LR A 240 8 16 48 8A 3A 61B5 12W 50VA 16A 96 240 240 120 FL A A C A D SP...

Page 74: ...emat rozmieszczenia oraz orurowania i oprzyrz dowania Instructions Danfoss Climate Solutions 2022 02 74 AN37261865152501 010301 118A2176C 630 344 10 4 NOS 327 867 530 364 45 I B C G A F H D E OP LSVM...

Page 75: ...na linii cieczowej D Dop yw powietrza E Wyp yw powietrza F Etykieta bezpiecze stwa drzwi G Tabliczka znamionowa H Olej wewn trz I Wej cie przewodu Kable elektryczne Uwaga wszystkie wymiary podano w m...

Page 76: ...PSH F1 V1 PSL PSH PDI SP SP FSC B1 D1 B2 B3 SP W1 SP D1 E1 E2 F1 English Legend B1 Liquid receiver B2 Filter drier Flare B3 Sight glass Flare D1 FSA connection Flare E1 Liquid service valve E2 Suction...

Page 77: ...L fterdrehzahlregler SP 1 4 Zoll Schraderanschluss PDI Doppeldruckschalter V1 Hubkolbenverdichter W1 MCHE mit L fter PSL Niederdruckseite PSHHochdruckseite Isolierung L gende en fran ais B1 Bouteille...

Page 78: ...P LSVM016 014 OP MSSM012 015 018 WD1 Annex D Wiring Diagram Schaltplan Sch ma de c blage Diagrama de cableado Schema elettrico Diagrama de fia o schemat okablow ania Instructions Danfoss Climate Solut...

Page 79: ...WD2 Code G W05 OP MSIM034 044 046 057 Instructions 118A2176C AN37261865152501 010301 79 Danfoss Climate Solutions 2022 02...

Page 80: ...Code E W05 OP MSIM034 044 046 057 WD3 Instructions Danfoss Climate Solutions 2022 02 80 AN37261865152501 010301 118A2176C...

Page 81: ...WD4 Code G W05 OP LSVM048 068 OP MSTM022 026 034 OP LSVM026 034 OP MSSM030 026 Instructions 118A2176C AN37261865152501 010301 81 Danfoss Climate Solutions 2022 02...

Page 82: ...Code E W05 OP MSTM026 034 OP LSVM048 068 WD5 Instructions Danfoss Climate Solutions 2022 02 82 AN37261865152501 010301 118A2176C...

Page 83: ...WD6 Code G W09 OP MSTM008 009 012 014 018 OP MSSM012 015 018 021 OP LSVM014 016 Instructions 118A2176C AN37261865152501 010301 83 Danfoss Climate Solutions 2022 02...

Page 84: ...Code G W09 OP LSVM048 068 OP MSTM022 026 034 OP LSVM026 034 OP MSSM030 026 WD7 Instructions Danfoss Climate Solutions 2022 02 84 AN37261865152501 010301 118A2176C...

Page 85: ...WD8 Code G W09 OP MSIM034 044 046 057 Instructions 118A2176C AN37261865152501 010301 85 Danfoss Climate Solutions 2022 02...

Page 86: ...Code E W09 OP MSTM026 034 OP LSVM048 068 WD9 Instructions Danfoss Climate Solutions 2022 02 86 AN37261865152501 010301 118A2176C...

Page 87: ...Code E W09 OP MSIM034 044 046 057 WD10 Instructions 118A2176C AN37261865152501 010301 87 Danfoss Climate Solutions 2022 02...

Page 88: ...19 Code G W05 OP MSIM068 080 WD11 Instructions Danfoss Climate Solutions 2022 02 88 AN37261865152501 010301 118A2176C...

Page 89: ...19 Code G W09 OP MSIM068 080 WD12 Instructions 118A2176C AN37261865152501 010301 89 Danfoss Climate Solutions 2022 02...

Page 90: ...19 Code E W05 OP MSIM068 080 099 108 WD13 Instructions Danfoss Climate Solutions 2022 02 90 AN37261865152501 010301 118A2176C...

Page 91: ...19 Code E W09 OP MSIM068 080 099 108 WD14 Instructions 118A2176C AN37261865152501 010301 91 Danfoss Climate Solutions 2022 02...

Page 92: ...2 Condensateur de marche du compresseur C3 Condensateur de marche du ventilateur E1 R sistance de carter F1 Sectionneur principal F2 Relais de surcharge F3 Fusible circuit de commande F4 Protecteur th...

Reviews: