32a
Service parameter(s) 10-11
In addition to the settings in line 1 to 7 on the grey side of the
ECL Card, there is an extended service menu from line 10 and
onwards.
Push repeatedly to reach the lines numbered 10
and onwards.
Line
0
0
1
Value
Range indicator
Now you can move to any line of your choice.
Set the parameter value.
You can select any of the two circuits no matter
what line you are in. You will not necessarily enter
the same line number. See the service parameters
in section 31.
Check that you have entered all the required settings in
circuit I - and circuit II, if available.
If you want to copy the new settings to the ECL Card
(recommended by Danfoss), see section 34.
Make a note of your new settings in the parameter list in section
31.
When you have entered all your personal settings, turn the ECL
Card over so that the yellow side faces you.
Adjusting the service
parameters
32
10 Choice of room panel / remote control
Circuit
Setting range
Factory setting
I
1 ... 2
1
Decides the communication with the room panel or remote
control.
Please note that the room panel / remote control is only active
if the system device bus is active. The bus is active when the
outdoor temperature sensor is connected.
Choose between
1:
Room panel ECA 60 / 62 or remote control
ECA 61 / 63 with address A
2:
Room panel ECA 60 / 62 or remote control
ECA 61 / 63 with address B
The room panel / remote control has no influence on the DHW
control.
11 Setback temperature dependent on outdoor
temperature
Circuit
Setting range
Factory setting
I
OFF / -29 ... 10 °C
-15 °C
Below this outdoor temperature, the setback temperature setting
has no influence.
-29 ... 10:
The setback temperature depends on the
outdoor temperature, when the outdoor
temperature is above the set limit. The
lower the outdoor temperature, the less the
temperature reduction. When the outdoor
temperature is below the set limit, there is
no temperature reduction.
OFF:
The setback temperature does not depend
on the outdoor temperature.
100%
0%
-20
-10
-29
0
20
10
Reduction
Outdoor
temperature °C
Setting line 11