Service parameters (10-199)
31a
Circuit I (heating and cooling)
Lines Setting ranges
Factory settings
Your settings
10
Choice of room panel / remote control
1, 2
1
11
Setback temperature dependent
on outdoor temperature
OFF / -29 ... 10 °C
-15 °C
°C
12
Boost
0 ... 99%
0 %
%
13
Reference ramping
0 ... 99 min.
0 min.
min.
14
Optimizing time constant
OFF / 10 ... 59
OFF
15
Adaptive function of room
temperature
OFF / 1 ... 30
OFF
17
Influence on desired flow temperature
OFF / 1 ... 20 K
OFF
K
20
Optimization based on room /
outdoor temperature
ON / OFF
OFF
21
Total stop
ON / OFF
OFF
22
Pump exercise
ON / OFF
OFF
23
Valve exercise
ON / OFF
OFF
24
Gear motor / thermo actuator
ON / OFF
ON
31
Return temperature limitation
- upper limit (X-axis)
-60 ... 20 °C
15 °C
°C
32
Return temperature limitation
- upper limit (Y-axis)
10 ... 110 °C
40 °C
°C
33
Return temperature limitation
- lower limit (X-axis)
-60 ... 20 °C
-15 °C
°C
34
Return temperature limitation
- lower limit (Y-axis)
10 ... 110 °C
60 °C
°C
35
Return temperature influence
- max. limitation
-9.9 ... 0 ... 9.9
-2.0
36
Return temperature influence
- min. limitation
-9.9 ... 0 ... 9.9
0.0
37
Time constant for return temperature
limitation
OFF / 1 ... 50
25
43
Parallel operation of DHW and heating
circuits
OFF / 1 ... 99 K
OFF
K
52
Closed valve / normal operation
ON / OFF
OFF
81
Time constant of input for
sensor S1
1 ... 250
50
31b
Service parameters (10-199)
Circuit I (heating and cooling)
Lines Setting ranges
Factory settings
Your settings
141
Override input selection
OFF / 1 ... 6
OFF
142
Restart period, TR
OFF / 1 ... 99 min.
20 min.
min.
145
Changeover time, TP
0.0 ... 23.9
16.1
146
Pressure stabilization time, TST
1 ... 99 sec.
15
sec.
153
Changeover delay, TCH
OFF / 1 ... 99 sec.
5
sec.
196
Service pin LON
ON / OFF
OFF
197
LON reset
ON / OFF
ON
198
Daylight saving time changeover
ON / OFF
ON
199
Master / slave address
0 ... 9, 15
15
Circuit II (DHW)
Lines Setting ranges
Factory settings
Your settings
22
Pump exercise
ON / OFF
OFF
30
Return temperature limitation
10 ... 110 °C
50 °C
°C
35
Return temperature influence
- max. limitation
-9.9 ... 0 ... 9.9
-2.0
36
Return temperature influence
- min. limitation
-9.9 ... 0 ... 9.9
0.0
37
Time constant for return temperature
limitation
OFF / 1 ... 50
25
141
Override input selection
OFF / 1 ... 6
OFF
142
Restart period, TR
OFF / 1 ... 99 min.
20 min.
min.
145
Changeover time, TP
0.0 ... 23.9
16.1
146
Pressure stabilization time, TST
1 ... 99 sec.
15
sec.
153
Changeover delay, TCH
OFF / 1 ... 99 sec.
5
sec.