Installation guide
Thermostat
Type KPU
© Danfoss A/S (AC-MC / jmn), 2014-02
DKRCC.PI.CD0.A3.22 / 520H8467
1
06
0R
976
9
06
0R
976
9
Application
KPU thermostats are used for regulation and to ensure safety
in refrigeration, freezing, air conditioning, ventilating and
heating systems.
KPU thermostats are available with vapor charge or with
adsorption charge.
All KPU thermostats are fitted with Single-Pole Double-Throw
(SPDT) switches.
For large a.c. motors and for all d.c. motors, KPU is installed
in the control circuit. For single phase ac motors, KPU
is installed in the line voltage supply to the motor.
The standard KPU enclosure is rated NEMA 1.
NEMA 1 is obtained when the thermostat is mounted on a flat
surface. When mounting KPU on a bracket, cover all unused
holes.
Product Specification
Thermostat bulb types
Charge
Type
Code no.
Bulb type
Capillary tube
length
Reset
function
Regulating
range
Differential Δt
Max. bulb
temperature
Ambient
temperature
[in.]
[°F]
[°F]
[°F]
[°F]
Vapor
KPU 61
060L5201
A
80
auto.
-20 – 60
4 – 18
2)
250
-40 – 122
(170 for max.
2 hours)
KPU 61
060L5203
B
80
auto.
-20 – 60
4 – 18
2)
250
KPU 61B
060L5204
B
80
man. (min.)
1)
-20 – 60
5 (fixed)
2)
250
KPU 61B
060L5205
B
200
man. (min.)
1)
-20 – 60
5 (fixed)
2)
250
KPU 61
060L5210
B
80
auto.
-20 – 60
4 – 18
2)
250
KPU 62
060L5206
C1
0
auto.
-20 – 60
4 – 18
2)
250
KPU 63
060L5213
A
80
auto.
-60 – 15
10 – 25
2)
250
KPU 63
060L5214
B
80
auto.
-60 – 15
10 – 25
2)
250
KPU 68
060L5215
C1
0
auto.
25 – 95
5 – 22
2)
250
KPU 69
060L5217
B
80
auto.
25 – 95
5 – 22
2)
250
Adsorption
KPU 62
060L5207
C2
0
auto.
-20 – 60
4 – 15
175
KPU 73
060L5208
E3
80
auto.
-15 – 60
5 – 35
175
KPU 73
060L5209
E1
80
auto.
-15 – 60
15 – 45
175
KPU 73B
060L5211
E3
80
man. (min.)
1)
-15 – 60
6 (fixed)
175
KPU 73
060L5212
D
80
auto.
-15 – 60
5 – 35
175
KPU 71
060L5218
E2
80
auto.
25 – 70
5 – 18
175
KPU 71B
060L5216
E2
80
man. (min.)
1)
25 – 70
5 (fixed)
175
KPU 74
060L5219
E1
80
auto.
0 – 80
9 – 35
175
KPU 74B
060L5220
E1
80
man. (min.)
1)
0 – 80
10 (fixed)
175
KPU 75
060L5221
F
80
auto.
30 – 95
5 – 18
230
KPU 77
060L5223
E3
80
auto.
60 – 140
6 – 18
265
1)
man. (min.): Manual reset after cut-out on falling temperature.
2)
The switch differential is dependent on range settings. Low range settings increases the differential.
High range settings decreases the differential. Use the graphs on page 3 to determine the correct differential setting.
A
B
C
D
E
F
straight capillary tube
remote air coil
air coil/room sensor
double contact remote coil
remote bulb
remote duct coil