DKRCC.PI.CD0.A3.22 / 520H8467  

© Danfoss A/S (AC-MC / jmn), 2014-02

Installation

Select an accessible location, where the thermostat will not 

be subject to damage. Mount the KPU on a bracket or on a 

completely flat surface. Mounting on an uneven surface may 

cause incorrect thermostat operation. For bracket mounting, 

use only the 10-32 x 

3

/

16

 in. screws furnished with the 

thermostat. Other screws may interfere with the functioning of 

the thermostat. In no case can screws protrude more than 

1

/

8

 

in. into the thermostat. Use only the mounting holes provided. 

Do not make additional holes.

IMPORTANT: 

For vapor charged thermostats, ensure that the bulb 

is installed in a colder location than the thermostat 

housing and capillary tube. This prevents charge 

migration from the bulb and ambient temperature 

will have no effect on regulation accuracy.

For adsorption charged thermostats, the bulb can be placed 

in a warmer or colder location than the thermostat housing 

and capillary tube.

General recommendations for capillary tube 

and bulb installation:

1.

 Protect the capillary tube from damage due to vibration.

a)

 When the thermostat unit is mounted directly on the 

compressor, the capillary tube must be secured to the 

compressor so that both vibrate together.

b)

 For mounting otherwise, form surplus capillary tube 

into a loose loop, and secure the length of capillary tube 

between the compressor and the loop to the compressor. 

Secure the length from the loop to the thermostat to the 

base on which the thermostat is mounted.

2.

 Leave a little slack in the capillary tube to help dampen 

vibration.

3.

 Avoid sharp bends and bending the capillary tube at the 

same point several times, as these actions can weaken the 

material and increase the likelihood of the tube cracking.

4.

 Form and locate the capillary tube away from sharp or 

abrasive objects that might damage it.

5.

 Never allow the capillary tube of a vapor charged  

thermostat to run alongside of a suction line in a wall entry.

6.

 Ensure minimal length of capillary tube exposed to 

temperature for KPU with straight capillary bulb type:

− 16 in. for KPU tharmostats with 80 in.  

capillary tube,

− 22 in. for KPU thermostats with 200 in.  

capillary tube.

7.

 For thermostats with room sensor coils, make sure that 

placement allows free airflow around the coil and bulb. 

At the same time, ensure that the bulb is not exposed to 

drafts from doors, or to heat radiated from the evaporator 

surface. Make sure that the bulb does not come into 

contact with a wall surface. Never mount the thermostat 

directly on a cold wall. Instead, mount the unit on an 

insulating plate. 

IMPORTANT: 

Do not dent or deform the bulb of the thermostat, as 

doing so could damage the bulb and cause charge 

leakage.

Wiring

Electrical ratings according to UL regulations

120 V a.c.

24 FLA, 144 LRA - make only

240 V a.c.

24 FLA, 144 LRA - make only

240 V d.c.

12 W pilot duty

European electrical ratings according to EN 60947

AC1

AC3

AC15

LR

DC13

16 A

16 A

10 A

112 A

12 W

400 V

220 V

CAUTION: 

To avoid the possibility of electric shock and damage 

to equipment, diconnect the power supply before any 

wiring connections are made.  Never touch current 

conducting (LIVE) parts with your fingers or with tools.

NOTE:

All wiring should conform to the National Electrical 

Code and to applicable local regulations.  Use only 

copper wire. Use only the terminal screws furnished in 

the terminal block. Do not exceed tightening torque  

of 20 inch pounds (2.3 Nm). Do not exceed the 

thermostat’s specified electrical ratings.

The terminal block as well as grounding screw are accessible 

after dismounting the front cover.

Summary of Contents for KPU 61

Page 1: ...61B 060L5204 B 80 man min 1 20 60 5 fixed 2 250 KPU 61B 060L5205 B 200 man min 1 20 60 5 fixed 2 250 KPU 61 060L5210 B 80 auto 20 60 4 18 2 250 KPU 62 060L5206 C1 0 auto 20 60 4 18 2 250 KPU 63 060L5213 A 80 auto 60 15 10 25 2 250 KPU 63 060L5214 B 80 auto 60 15 10 25 2 250 KPU 68 060L5215 C1 0 auto 25 95 5 22 2 250 KPU 69 060L5217 B 80 auto 25 95 5 22 2 250 Adsorption KPU 62 060L5207 C2 0 auto 20...

Page 2: ... times as these actions can weaken the material and increase the likelihood of the tube cracking 4 Form and locate the capillary tube away from sharp or abrasive objects that might damage it 5 Never allow the capillary tube of a vapor charged thermostat to run alongside of a suction line in a wall entry 6 Ensure minimal length of capillary tube exposed to temperature for KPU with straight capillar...

Page 3: ...he lever Use fingers only B Manual reset button only on versions sold with manual reset function C Terminal block D Grounding screw Wiring Option A Cut Out on temperature fall Wiring Option B Cut Out on temperature rise C F KPU 61 KPU 62 C F LSP B C F D C KPU 63 LSP C F LSP KPU 68 KPU 69 C F C F 15 10 0 10 20 30 70 15 F Differential lines Differential lines 130 0 20 40 60 80 100 120 90 80 70 60 50...

Page 4: ...used for service on non electrical parts Interrupt mains power before servicing electrical parts Adjustment thermostat with automatic reset Scale plate directly indicates High Switching Point and Differential Adjustment thermostat with manual reset Scale plate directly indicates Low Switching Point which is Cut Out There is no pointer for Differential Differential value is fixed and printed on the...