Table A. Hidden Access Configuration Variables.

HIDDEN ACCESS 

(continued)

DIAGNOSTIC MESSAGES

The  control  console  can  recognize  many  of  the  faults  or

errors which may potentially occur in the sensors, valves,

operator console or wiring. It will report the condition on one

or both displays, sound the alarm and may shut the control

down if faulty machine operation is possible.

Faults may inhibit or stop valve drive when in auto mode but

will not in manual mode. Faults will clear when the cause is

repaired or eliminated.

The  KGS  console  is  pre-programmed  with  21  diagnostic

English messages which aid the operator in taking corrective

action. For faults which do not turn valve drive off, the display

fault  message  alternates  with  the  normal  operating

information.

Configuration 

Descripton Of 

Range Of Values

S u g g e s t e d

S u g g e s t e d

V a r i a b l e

Configuration Variable

D e f a u l t

Access Level

Battery

Control voltage supply

12V, 24V

24V

Dealer

Alarm

Audible alarm switch

off/on

on

Foreman

Displayed units 

Distance measure units

in,ft,mm

in

Foreman

Slope sensor configuration Quantity of slope sensors used

single, dual

single

Factory

Left side wand hub 

Hub location for grade sensor 

left, right

left

Foreman

Right side wand hub

on left side or right side

left, right

right

Foreman

Valve type

Tow point valve type

servo, on/off, proportional

proportional Dealer

Coil/drive type

Tow point valve coil wiring 

dual lo, dual hi, single 

dual hi

Dealer

Application

Machine type software

planer, paver

paver

Factory

Interlock

Motion sensor type 

none, external, speed, switch

external

Factory

(motor PPU or handle switch)

Display configuration 

No. of alpha/numeric displays

single, dual

single

Factory

PPU pulses

Motor speed pickup pulses 

200-30,000

10,000

Dealer

per 1000 ft or per 300 m

Interlock travel speed 

Machine speed to turn control 

0.0 to 20.0 ft/min or 0 to 7.0m/min 10.0 ft/min

Dealer

on or off

Switch interlock delay

Time delay after forward motion  

0.0 to 10.0 sec 

10.0 sec

Dealer

switch to turn control on

Front slope sensor weight

Effective position of slope sensor  0 to 100%

50%

Foreman

(from front sensor)

Slope error deadband

Slope error at start of valve drive  0.0% to 100% 

0.00%

Foreman

Wand error deadband

Grade error at start of valve drive  0.0 in to 1.0 in or 0.0 to 25.0 mm 

.02 in 

Foreman

Ultrasonic error deadband   Grade error at start of valve drive  0.0 in to 1.0 or 0.0 to 25.0 mm 

.04 in 

Foreman

Wand error limit

Grade error at valve drive hold

.10 to 4.0 in or 2.0 to 100 mm

1.0 in

Foreman

Ultrasonic error limit 

Grade error at valve drive hold

.10 in to 4.0 in or 2.0 to 100 mm 

1.0 in

Foreman

Servo frequency 

PWM frequency for servo valve

100 to 200 Hz

200 Hz

Dealer

On/off frequency 

Pulse frequency for time 

1 to 10 Hz

5 Hz

Dealer

proportional valve 

Proportional frequency

PWM frequency for proportional 

40 to 160 Hz

150 Hz

Dealer

solenoid valves

Left side raise valve step

Valve voltage % at start of raise

0 to 60%

35%

Foreman

 (servo or proportional ) leftside 

Right side raise valve step   Valve voltage % at start of raise 

0 to 60%

35%

Foreman

(servo or proportional ) right side

Left side lower valve step 

Valve voltage % at start of lower  0 to 60%

35%

Foreman

(servo or proportional ) left side 

Right side lower valve step   Valve voltage % at start of lower  0 to 60%

35%

Foreman

(servo or proportional ) right side 

Left side raise on/off 

Valve on time at start of raise

1 to 50 msec

20 msec

Dealer

valve step 

left side

Right side raise on/off 

Valve on time at start of raise

1 to 50 msec

20 msec

Dealer

valve step 

 right side

Left side lower on/off 

Valve on time at start of  lower 

1 to 50 msec

20 msec

Dealer

valve step 

left side

Right side lower on/off  

Valve on time at start of lower  

1 to 50 msec

20 msec

Dealer

valve step

right side

Summary of Contents for KGS

Page 1: ...es or proportional solenoid valves Fault recognition with diagnostics Full electrical and environmental protection Fewerelectricalaccessoriesandreducedmachine wiring possible SYSTEM CONFIGURATION The...

Page 2: ...uto mode from manual mode the prior setpoint is not saved but must be reset by the operator The motion interlocks are disabled with this option Controller Outputs 5 Solenoid valve or servovalve high s...

Page 3: ...l current CAN CONNECTION Two wire shielded cable Consult Danfoss ENVIRONMENTAL OPERATING TEMPERATURE 40 to 70 C 40 to 158 F MOISTURE Protected against 95 relative humidity Packaged to withstand high p...

Page 4: ...4 DIMENSIONS Dimensions of the KGS in Millimeters Inches 1961...

Page 5: ...s The mating connector assembly for the KGS console must be ordered separately The Danfoss part number is K18169 which is composed of 28 pins 8 seal plugs 1 connector and 3 connector keys 9 8 7 6 5 4...

Page 6: ...rmined by built in software and by instructions received from the operator s use of switches Continuous operating information is provided to the operator with displays which are continuously monitorin...

Page 7: ...effective reference point Both setpoint and actual displays are changed simultaneously Holding this switch and pushing the null setpoint switch will alternately zero the display offset or zero the dis...

Page 8: ...variables to a particular hidden access level is accomplished with the special configuration section of the ordering code Consult Danfoss The foreman level is accessed with the sensitivity switch and...

Page 9: ...m Interlock travel speed Machine speed to turn control 0 0 to 20 0 ft min or 0 to 7 0m min 10 0 ft min Dealer on or off Switch interlock delay Time delay after forward motion 0 0 to 10 0 sec 10 0 sec...

Page 10: ...repair or evaluation include a description of the problem and what work you believe needs to be done along with your name address and telephone number RETURN TO Danfoss US Company Return Goods Departm...

Reviews: