background image

© Danfoss A/S (AC-MCI/MWA), 2012-01 

DKRCI.PI.HS0.A3.52 / 520H0953 

3

Installation

Refrigerants

Applicable to all common non-flammable 

refrigerants, including R717 and non-

corrosive gases/liquids dependent on sealing 

material compatibility.

Flammable hydrocarbons are not

recommended. 

The valve is only recommended for use in 

closed circuits. For further information please 

contact Danfoss.

Temperature range

–60/+120°C (–76/+248°F)

Pressure range

The valves are designed for a max.

working pressure of 52 bar g (754 psi g).

Technical data

The ICS can be used in suction, liquid, hotgas 

and liquid/vapor lines. The ICS regulates the 

flow of the medium by modulation or on/off 

function, depen ding on the control impulse 

from the screwed on pilot valve or valves. 

Regulating range

Dependent on the chosen type and 

combination of pilot valves.

Opening differential pressure (p)

The ICS main valve requires a minimum 

opening differential pressure of 0.07 bar (1 

psi) to begin to open and 0.2 bar (3 psi) to be 

completely open.
 

The valve must be protected  

 

against back pressure. A check    

 

valve should be installed upstream

 

of the ICS in installations where there 

is a risk of back pressure. Back pressure can 

affect the correct position of the piston ring.

Design (fig. 4)

1.   Body

2.   Top cover

3. 

Function module

3a  Valve plate (Teflon) 

 

(available as spare part)

3b  Washer plate

4. Gasket

5. Bolts

6. Plug

7. Gasket

8. 

Manual operating spindle

9.   Plug

10. Gasket

Installation

The valve must be installed with the spindle 

in vertically upwards position (fig. 1). 
The valve must be installed with the arrow in 

the direction of the flow and the top cover 

upwards (fig. 2). The top cover can be rotated 

4 X 90° in relation to the valve body. 

The valve is fitted with a spindle for manual 

opening. If an external pilot valve is used, the 

pilot line must be connected to the upper 

side of the main line so that any dirt and oil 

from the plant will not find its way into the 

pilot line.

If the ICS 1 is to be used as a solenoid valve in 

a liquid line, external control pressure cannot 

be recommended because it can cause liquid 

hammer.

The valve is designed to withstand a high 

internal pressure. However, the piping system 

should be designed to avoid liquid traps and 

reduce the risk of hydraulic pressure caused 

by thermal expansion. It must be ensured 

that the valve is protected from pressure 

transients like “liquid hammer” in the system.

Welding (fig. 3, 4 and 5)

The top cover (fig. 4, pos. 2) and function 

module (fig. 4, pos. 3), must be removed 

before welding to prevent damage to o-rings 

and teflon (PTFE) in the function module 

and to avoid getting welding debris in the 

module. 

The function module can be lifted out using 

a bolt size M6 or multi-function tool screwed 

into the threaded hole of the piston on the 

function module (fig. 3). Debris blocking the 

bolt hole will need cleaning.

Note: 

Remove all parts from the valve body 

before welding (as shown in fig. 5). 

 

The internal surfaces and weld    

 

connections of the enclosed ICS/  

 

ICM valve have been applied with  

 

an anti-corrosion treatment.

In order to maintain the effectiveness 

of this anti-corrosion treatment, it is 

important to ensure that the valve is 

disassembled just prior to the welding / 

brazing process being undertaken.

In the event that the function modules 

are to be left disassembled for any length 

of time, please ensure that the function 

modules are  further protected by placing 

in a polyethylene bag or by applying a rust 

protection agent (e.g. refrigeration oil or 

BRANOROL) on the surfaces.

Only materials and welding methods, 

compatible with the valve body material, 

must be welded to the valve body. The valve 

should be cleaned internally to remove 

welding debris on completion of welding and 

before the valve is reassembled.
Avoid welding debris and dirt in the

valve body and the function module. The 

valve body must be free from stresses 

(external loads) after installation.
The valves must not be mounted in systems 

where the outlet side of the valve is open 

to atmosphere. The outlet side of the valve 

must always be connected to the system 

or properly capped off, for example with a 

welded-on end plate.

Assembly

Remove welding debris and any dirt from 

pipes and valve body before assembly. Check 

that the o-rings are intact before replacing 

the function module. If possible, apply some 

refrigeration oil to ease the insertion and to 

protect the o-rings.  Check that the top gasket 

has not been damaged. If the surface has 

been damaged or the gasket has been bent, it 

must be replaced.

Tightening (fig. 6)

Tighten the top cover with a torque wrench, 

to the values indicated in the table.

Colours and identification

The ICS valves are Zinc-Chromated from 

factory. The Zinc-Chromatization does not 

cover the welding connections. If further 

corrosion protection is required, the valves 

can be painted.

Precise identification of the valve is made via 

the ID plate on the top cover. 

The external surface of the valve housing 

must be protected against corrosion with 

a suitable top coating after installation 

involving welding and consequent assembly.

Protection of the ID plate when painting the 

valve is recommended.

Maintenance

Service

The ICS valves are easy to dismantle. 

Do not open the valve while the valve is still 

under pressure.

Pressure relief can be done by carefully 

opening the manual operating spindle. 

Small grooves along the thread will release 

refrigerant into open air. This operation must 

only be done after providing the correct 

countermeasures under local legislation.

The function module can be lifted out using 

a bolt size M6 screwed into the threaded hole 

of the piston on the function module (fig. 

3). Debris blocking the bolt hole will need  

cleaning.

Upon opening and removal of the function 

module:

-  Check that the o-rings on the function  

  module has not been damaged.  A  

  valve with a damaged o-ring might not  

  modulate according to the specification.

-  Check that the piston and cylinder is    

  free of scratches and look for wear    

  marks. If the wear is excessive the  

 

  function module should be replaced to  

  prevent false pilot signal around the  

  piston ring.

-  Check that the movement  of the  

 

  cylinder and valve seat is free and with  

  low friction.

-  If the teflon valve plate is damaged it must  

  be replaced. It is available as spare part:  

Type

Code number

ICS 25

027H2222

ICS 32

027H3222

ICS 40

027H4222

ICS 50

027H5222

ICS 65

027H6222

ICS 80

027H8222

 

  For mounting instructions please see  

 DKRCI.PI.HS0.D.

Assembly

Remove any dirt from the body before the 

valve is assembled. Check that all channels 

in the valve are not blocked by particles or 

similar.

If possible, apply some refrigeration oil to ease 

the insertion and to protect the o-rings.

Tightening (fig. 6)

Tighten the top cover with a torque wrench, to 

the values indicated in the table.

Always carry out this operation when the 

manual operation device has been in use 

(see fig 7)

1.  Remove the cap (

A

) and tighten the    

  spindle (

B

) anticlockwise with 8 Nm 

  (5.9 lb/ft)

2.  Remount the cap (

A

) and tighten it    

  clockwise with 8 Nm (5.9 lb/ft)
Use only original Danfoss parts, including  

O-rings and gaskets for replacement. 

Materials of new parts are certified for the 

relevant refrigerant. 

In cases of doubt, please contact Danfoss. 
Drawings are only for illustration, not for 

dimensioning or construction.
Danfoss accepts no responsibility for 

errors and omissions. Danfoss Industrial 

Refrigeration reserves the right to make 

changes to products and specifications 

without prior notice.

The following text is applicable to the UL 

listed products ICS 25-65

Applicable to all common non-flammable 

refrigerants, including/excluding (+) R717 and 

to non-corrosive gases/liquids dependent 

on sealing material compatibility (++).  The 

design pressure shall not be less than the 

value outlined in Sec. 9.2 of ANSI/ASHRAE 15 

for the refrigerant used in the system. (+++). 

ENGLISH

Reviews: