Set valve (A1 alarm)

  

Change analog input signal (optional)

ICAD will function based on factory settings as soon as the valve configuration has been set. The default settings are Modulation using 
an analog input of 4–20 mA.

  

Navigate back from the 
advanced control menu 
using 

If starting from main screen 
press enter 

 

and navigate 

to the service menu like in 
previous step.

Navigate to 

Valve

 

configuration

 using  , 

then press enter 

Select the ICM size or CVE. 
Press enter 

 

to set, and 

you will be navigated back 
to the previous screen. 
Continue to next step or 
press   to get back to main 
screen

Press down   until Service 
is selected, then press 
enter 

Press enter 

*Pressing and holding 

 

will go directly to the 
passcode screen

Enter the 8 digit service 
passcode* using 

 

   

press enter 

 to enter next 

number

*factory is 12131400

Navigate to

 Advanced 

control

 in the service 

menu using  , then press 
enter 

Now navigate to 

Control

 in 

the service menu using   , 
then press enter 

Next navigate to 

Input 

signal

 in the service menu 

using  , then press 
enter 

Select the desired input 
signal. Press enter 

 to set, 

and you will be navigated 
back to the previous screen. 

Press   to get back to main 
screen

VALVE CONFIGURATION HELP

 

ICAD 600B

 

 

-  ICM 20

 

-  ICM 25

 

-  ICM 32

ICAD 1200B
 

-  ICM 40

 

-  ICM 50

 

-  ICM 65

 

-  ICM 100

 

-  ICM 125

 

-  ICM 150 

  - CVE
ICAD 600B TS
   -ICMTS 20
   -ICMTS 50
   -ICMTS 80