Installation

Do not install ICAD before welding. This apply 

for electrical as well as for mechanical installa-

tion. Please observe that ICAD when connected 

to 24 V DC, will send out acoustic noise at stand 

still. This has no influence on the function/ 

operation of the ICAD. 

NOTE!

If media temperature is lower than

-30 °C (-22 °F) it is mandatory to set

parameter 

¡30

 and 

¡31

.

See separate document attached in ICAD 

box: document number AN285243155312

Use

ICAD 600A, ICAD 600A-TS and ICAD 1200A can 

be used  together with the following Danfoss 

valves (fig. 1, 5a and 5b).

ICAD 600A

ICAD 600A-TS

ICAD 1200A

ICM 20

ICMTS 20

ICM 40

ICM 25

ICM 50

ICM 32

ICM 65
ICM 100
ICM 125
ICM 150
CVE pilot valve

Electrical data

Supply voltage is galvanically isolated from in-/

output.

Supply voltage

24 V DC (Tolerances; see below table)

Load 

ICAD 600A, ICAD 600A-TS: 1.2 A

 

ICAD 1200A: 2.0 A

24 Volt DC ONLY

Please observe cable voltage drop.

Distance between the applied DC 

transformer and the ICAD terminal  

box may cause a voltage drop. Cross 

section of cables and size of DC 

transformer must be calculated so that 

the voltage at all time 

at the ICAD terminal 

box*

, both during standstill and during 

operation of ICAD, is within this range:

Prefabricated 

ICAD cable length

Code number

1.5 m    

027H0426

3 m

027H0438

10 m     

027H0427

15 m

027H0435

Voltage ICAD terminal 

(600A/1200A) [V DC]

Min.

21

22

23

24

Max.

26.4

* Do not measure inside the ICAD itself.

Fail safe supply

24 V DC (Tolerances; see table above)

Load 

ICAD 600A, ICAD 600A-TS: 1.2 A

 

ICAD 1200A: 2.0 A

Anolog Input - Current or Voltage

Current

 

0/4 – 20 mA

 

Load: 200 

W

Voltage

 

0/2 – 10 V DC

 

Load: 10 k

W

Analog Output

 

0/4 – 20 mA

 

Load: ≤ 250 

W

Digital Input - Digital ON/OFF input by means of 

voltfree contact (Signal/Telecom relays with gold-

plated contacts recommended) – Voltage input used

ON:  Contact impedance < 50 W)

OFF:  Contact impedance > 100 k

W

Digital Output - 3 pcs. NPN transistor output

External supply:   5 – 24 V DC (same supply as 

for ICAD can be used, but 

please note that the 

galvanically isolated system 

will then be spoiled).

Output load: 

50 

W

Load: 

Max. 50 mA

Temperature range (ambient)

-30 °C/+50 °C (-22 °F/122 °F)

Enclosure

IP67 (~NEMA 6)

Electrical connection

Connection to ICAD is done via M12 connectors. 

ICAD has two M12 male connectors build-in:

Power supply: 4 poled M12 male connector

Control signals: 8 poled M12 male connector

If ICAD is delivered with cables (1.5 m. (60 in.)) 

M12 female connectors: (Cable set with M12 

female connectors in other lengths are available)

Power Supply cable with 4 poled M12 

female connector

3 x 0.34 mm

2

 (3 x ~22 AWG) (fig. 6)

  I:  Black 

(+)  19 – 24 V DC fail safe 

   

 

 

supply (optional).

  II:  White  (+)  24 V DC

  III:  Brown  (–)  24 V DC

 

Control cable with 8 poled M12 

female connector

7 x 0.25 mm

2

 (7 x ~24 AWG) (fig. 7)

  A:  Black 

(–)  Digital output. 

   

 

 

Common Alarm.

  B:  Brown  (–)  Digital output.

   

 

 

ICM fully open.

  C:  Red 

(–)  Digital output.

   

 

 

ICM fully closed.

  D:  Orange  (–)  GND - Ground.

  E:   Yellow   (+)   Analog input  

   

 

 

0/4 – 20 mA. *)

  F:   Green   (+)   Analog input 0/2 – 10 V /  

   

 

 

 DI1 - Digital ON/OFF   

input. 

  G:   Blue  

(+)   Analog output  

   

 

 

0/4 – 20 mA. *)

  *)  If Neutral zone / 3 point control is 

   

selected (parameter i02 = 3) then  

   

E and G is used as DI2 - Digital  

   

ON/OFF input. Se fig. 9.

Electrical installation

General procedure for ICAD 600A/ICAD 

600A-TS/1200A installed on all ICM, ICMTS & CVE 

valves.

All necessary electrical connections to be made. 

ICM valve: Analog or digital operation

CVE/ICMTS valve: Analog only

Fig. 6

Analog operation

 - 7 wired cable (A-G) 

Modulation control. Valve to be controlled 

from Danfoss electronics, type EKC/EKE (fig. 

7), or third party electronics  

(like e.g. PLC).

Connect analog input signals. Currrent 

(mA) or Voltage (V). See 

Parameter list

 for 

configuration of analog input signals.

Yellow (+) and Orange (GND) are used for 

current (mA) input.

 or

Green (+) and Orange (GND) are used for 

Voltage (V) input.

Blue (+) and Orange (GND) are used 

for current (mA) output (optional, not 

mandatory).

 

Fig. 6

Digital operation

 - 7 wired cable (A-G) 

ON/OFF ICM solenoid valve operation. ICM 

valve to be controlled by means of a digital 

voltfree contact.

Connect digital input signals (fig. 8). See 

Parameter list

 for configuration of digital 

input signals.

Green (+) and Orange (GND) are connected 

to a voltfree contact.

Digital output signals are optional, not 

mandatory.

Black (–) and Orange (GND) are connected 

to auxiliary relay for Common Alarm. 

Brown (–) and Orange (GND) are connected 

to an auxiliary relay indicating ICM fully 

open.

Red (–) and Orange (GND) are connected 

to an auxiliary relay indicating ICM fully 

closed. 

Supply voltage

 - 3 wired cable (I, II, III) 

ICAD must be connected to a normal  

24 V DC supply. As an option, a fail safe 

supply is possible by means of a battery or 

UPS (Uninterruptible Power Supply). When 

voltage is applied as described below, ICAD is 

ready to be configurated. See 

Parameter list

ICAD configuration can be done 

independently whether the ICAD is installed 

on the valve or not. 

See 

Mechanical installation

.

Connect the White (+) and Brown (–) to a 

24 V DC supply voltage (fig. 6).

Fail safe supply as an option (not mandatory).

Connect the Black (+) and Brown (–) to a fail 

safe supply.

Mechanical installation

General procedure for ICAD 600A/ICAD 

600A-TS/1200A installed on all valves (fig. 3).

Check that the three socket set screws are 

fully unscrewed counter clockwise with a 

2.5 mm Hexagon key.
Mount ICAD by slowly lowering it on top of 

the valve.
The magnet coupling will drag the valve and 

ICAD together and in position.
Push ICAD in place.
Fasten valve and ICAD with the three socket 

set screws using a 2.5 mm Hexagon key. 

 

Special moisture seal is damaged if 

screws are removed (fig. 3, pos. A)

Neutral zone / 3 point control (fig. 9 - ICM only)

¡02

 = 3 

When 

¡02

 = 3 the factory setting of 

¡04

 

(opening) and 

¡14

 (closing) are both set to 10.

When 

¡02

 = 3 the speed given by 

¡04

 (opening) 

and 

¡14

 (closing) are active

¡13

 (Inverse operation) is active

¡16

 = 1 (Encoder operation enable) is active.

¡13

 = 0 (Direct operation) 

DI1 = DI2 = OFF 

ICAD/ICM maintain current position

DI1 = DI2 = ON 

ICAD/ICM  maintain current position

DI1 = ON, DI2 = OFF

ICAD increase opening degree

DI1 = OFF, DI2 = ON

ICAD decrease opening degree

¡13

 = 1 (Inverse operation) 

DI1 = DI2 = OFF 

ICAD maintain current position

DI1 = DI2=ON 

ICAD maintain current position

DI1 = ON, DI2 = OFF

ICAD decrease opening degree

DI1 = OFF, DI2 = ON

ICAD increase opening degree

Summary of Contents for ICAD 1200A

Page 1: ... the separate installation guide Mechanical intallation of ICAD on ICM document number AN285252668332 Vor Montage des ICAD auf das ICM bitte die separate Montageanleitung Mechanische Montage des ICAD auf das ICM Dokument Nummer AN285252668332 lesen Avant d installer ICAD sur l ICM veuillez lire le guide d installation séparé Installation mécanique d ICAD sur l ICM document numéro AN285252668332 An...

Page 2: ...our régulation modulante E S analógica para control modulante ICAD 600A 600A TS 1200A Digital I O for ON OFF valve operation Digitaler E A für EIN AUS Ventilbetrieb E S numérique pour marche arrêt de la vanne E S digital para control de válvula ON OFF External voltage 24 V DC K1 K2 K1 K2 II III Supply D F G E DI1 DI2 Control ICAD Danfoss M27H0163_1 A Black B Brown C Red D Orange E Yellow F Green G...

Page 3: ...Blue Analog output 0 4 20 mA If Neutral zone 3 point control is selected parameter i02 3 then E and G is used as DI2 Digital ON OFF input Se fig 9 Electrical installation General procedure for ICAD 600A ICAD 600A TS 1200A installed on all ICM ICMTS CVE valves All necessary electrical connections to be made ICM valve Analog or digital operation CVE ICMTS valve Analog only Fig 6 Analog operation 7 w...

Page 4: ...nts that ICAD is operating the ICM valve like an ON OFF solenoid valve with medium speed according to a digital input signal Description ICAD alarm text Definition of event Comments No Valve type selected A1 Alarm ON At start up A1 will be displayed Controller fault A2 Alarm ON Internal fault inside electronics Carry out 1 Power OFF and Power ON If A2 still active 2 Make a Reset to factory setting...

Page 5: ...ore 26 has been operated Always auto reset to 0 CA will flash in the display during calibration if Enter push button has been activated for two seconds 0 No Calibration 1 Normal forced calibration CA flashing slowly 2 Extended calibration CA flashing rapidly AO signal 06 0 2 2 No Type of A0 signal for ICM valve position 0 No signal 1 0 20 mA 2 4 20 mA Failsafe 07 1 4 1 No Define condition at power...

Page 6: ...rm is ON Time interval between boost is set in 19 The boost cyklus continues until the valve is back in operation Delay after boost before A9 alarm See Note 1 19 0 30 1 Minutes No Time delay between two boosts Linked to 18 function Max offset value See Note 1 20 3 15 3 Yes Password 13 Offset value numeric Requested Opening Degree from Analog Input Opening Degree from encoder Used with 21 Define ho...

Page 7: ... ON DI2 OFF 01 DI1 OFF DI2 ON 11 DI1 ON DI2 ON DO Close 55 0 1 DO Closed status ON when OD 3 DO Open 56 0 1 DO Open status ON when OD 97 DO Alarm 57 0 1 DO alarm status ON when a Alarm is detected Display mP SW ver 58 0 100 Software version for display microprocessor Motor mP SW ver 59 0 100 Software version for motor microprocessor Reset to factory setting 1 Remove the power supply 2 Activate dow...

Page 8: ...Typ EKC EKE Abb 7 oder über Steuergeräte von Drittanbietern z B SPS geregelt Analoge Eingangssignale anschließen Strom mA oder Spannung V Siehe Parameterliste für die Konfiguration der analogen Eingangssignale Gelb und Orange Masse werden für den Stromeingang mA verwendet oder Grün und Orange Masse werden für den Spannungseingang V verwendet Blau und Orange Masse werden für den Stromausgang mA ver...

Page 9: ... betreibt Beschreibung ICAD Alarmtext Definition des Zustands Anmerkungen Kein Ventiltyp ausgewählt A1 Alarm EIN Bei der Inbetriebnahme wird A1 angezeigt Reglerstörung A2 Alarm EIN Interne Störung in der Elektronik Vorgehensweise 1 Stromversorgung aus und wieder einschalten Wenn A2 immer noch aktiv ist 2 Reset auf die Werkseinstellung durchführen Wenn A2 immer noch aktiv ist Den ICAD bei Danfoss u...

Page 10: ...ibrierung blinkt CS im Display auf wenn die Drucktaste Enter zwei Sekunden lang gedrückt wurde 0 Keine Kalibrierung 1 Normal erzwungene Kalibrierung CS blinkt langsam 2 Erweiterte Kalibrierung CS blinkt schnell AO Signal 06 0 2 2 Nein Art des A0 Signals für die ICM Ventilposition 0 Kein Signal 1 0 20 mA 2 4 20 mA Eigensichere Stromversorgung 07 1 4 1 Nein Soll Zustand bei Stromausfall definieren B...

Page 11: ...ntervall zwischen den Boosts wird in 19eingestellt Der Boost Zyklus wird solange fortgesetzt bis das Ventil wieder in Betrieb ist Verzögerung nach Boost vor A9 Alarm Siehe Hinweis 1 19 0 30 1 Minuten Nein Verzögerungszeit zwischen zwei Boosts Verknüpft mit Funktion 18 Offsetwert max Siehe Hinweis 1 20 3 15 3 Ja Passwort 13 Offsetwert numerisch gewünschter Öffnungsgrad vom Analogeingang Öffnungsgra...

Page 12: ...DI1 AUS DI2 EIN 11 DI1 EIN DI2 EIN DO geschlossen 55 0 1 DO Status geschlossen Nur EIN wenn OD 3 DO offen 56 0 1 DO Status geöffnet Nur EIN wenn OD 97 DO Alarm 57 0 1 DO Alarmstatus EIN wenn ein Alarm erkannt wird Display MP SW Ver 58 0 100 Softwareversion für Display Mikroprozessor Motor MP SW Ver 59 0 100 Softwareversion für Motor Mikroprozessor Auf Werkseinstellungen zurücksetzen 1 Spannungsver...

Page 13: ...quement Fig 7 Régulation de modulation Vanne commandée à partir du système électronique Danfoss de type EKC EKE fig 7 ou à partir d un autre système électronique tel que l API Connectez les signaux d entrée analogique Intensité mA ou Tension V Consultez la liste des paramètres pour la configuration des signaux d entrée analogique Les bornes jaune et orange GND sont utilisées pour l entrée d intens...

Page 14: ...d un signal d entrée digitale du marché Texte d alarme ICAD Définition d un événement Commentaires Aucun type de vanne sélectionné A1 Alarme activée Au démarrage A1 est affiché Défaut du régulateur A2 Alarme activée Défaut interne des éléments électroniques Mesures 1 Éteignez et rallumez Si A2 est toujours activée 2 Réinitialisez les réglages d usine Si A2 est toujours activée renvoyez l ICAD à Da...

Page 15: ... le calibrage si le bouton Entrée a été enfoncé pendant deux secondes 0 aucun calibrage 1 calibrage forcé normal CA clignote lentement 2 Étalonnage étendu CA clignote rapidement Signal AO 06 0 2 2 Non Type de signal A0 pour position de la vanne ICM 0 aucun signal 1 0 20 mA 2 4 20 mA Sécurité 07 1 4 1 Non Définissez les conditions en cas de coupure de courant l alimentation de sécurité est installé...

Page 16: ...en 19 Le cycle d accélération continue jusqu à restauration du fonctionnement de la vanne Temporisation après accélération avant alarme A9 Voir remarque 1 19 0 30 1 Minutes Non Temporisation entre deux accélérations Lié à la fonction 18 Valeur de décalage max Voir remarque 1 20 3 15 3 Oui Mot de passe 13 Valeur de décalage numérique Degré d ouverture requis par l entrée analogique Degré d ouvertur...

Page 17: ... ARRÊT 01 DI1 ARRÊT DI2 MARCHE 11 DI1 MARCHE DI2 MARCHE DO fermée 55 0 1 État fermé de DO En MARCHE lorsque OD 3 DO ouverte 56 0 1 État ouvert de DO En MARCHE lorsque OD 97 Alarme de DO 57 0 1 État d alarme de DO En MARCHE lorsqu une alarme est détectée Affichage mP SW ver 58 0 100 Version du logiciel du microprocesseur d affichage Moteur mP SW ver 59 0 100 Version du logiciel du microprocesseur d...

Page 18: ...larse con electrónica Danfoss EKC EKE fig 7 o electrónica de otro fabricante como por ejemplo un controlador PLC Conecte las señales de entrada analógicas Corriente mA o tensión V Consulte la Lista de parámetros si desea conocer la configuración de las señales de entrada analógicas Los conductores amarillo y naranja GND se usan como entrada de corriente mA o Los conductores verde y naranja GND se ...

Page 19: ...lvula solenoide ON OFF de velocidad media de acuerdo con una señal de entrada digital Descripción Texto de alarma del actuador ICAD Definición del evento Observaciones No se ha seleccionado ningún tipo de válvula A1 Alarma ON Se mostrará el mensaje A1 durante la puesta en marcha Fallo del controlador A2 Alarma ON Fallo interno de la electrónica Lleve a cabo los pasos descritos a continuación 1 Apa...

Page 20: ...bración 1 Calibración normal forzada el mensaje CA parpadeará lentamente 2 Calibración ampliada el mensaje CA parpadeará rápidamente Señal AO 06 0 2 2 No Tipo de señal AO de posición de la válvula ICM 0 Sin señal 1 0 20 mA 2 4 20 mA Modo de seguridad 07 1 4 1 No Permite definir la acción que debe realizar el actuador en caso de interrupción del suministro eléctrico si existe una fuente de alimenta...

Page 21: ...a válvula vuelve a ponerse en funcionamiento Retardo tras el impulso antes de la alarma A9 Consulte la nota 1 19 0 30 1 Minutos No Retardo entre dos impulsos Vinculado a la función 18 Valor máximo de desviación Consulte la nota 1 20 3 15 3 Sí Contraseña 13 Valor de desviación numérico Grado de apertura solicitado de la entrada analógica Grado de apertura del codificador utilizado con 21 Defina cóm...

Page 22: ...da DO en estado de cierre ON cuando OD 3 Salida DO abierta 56 0 1 Salida DO en estado de apertura ON cuando OD 97 Alarma de salida DO 57 0 1 Salida DO en estado de alarma ON cuando se detecta una alarma Versión de software mP pantalla 58 0 100 Versión de software del microprocesador de la pantalla Versión de software mP motor 59 0 100 Versión de software del microprocesador del motor Volver a ajus...

Page 23: ... Danfoss DCS ms 2020 01 AN19798642980802 000701 23 ...

Page 24: ... Danfoss DCS ms 2020 01 AN19798642980802 000701 24 ...

Reviews: