![Danfoss HC6110-3 Installation Instructions Manual Download Page 3](http://html1.mh-extra.com/html/danfoss/hc6110-3/hc6110-3_installation-instructions-manual_508656003.webp)
3
Installation Instructions
Specifi cation
Installa
tion Instruc
tions
Please note: This product should only be installed by a
qualifi ed electrician or competent heating installer and
should be in accordance with the current edition of the
IEEE wiring regulations.
GB
Features
Battery Powered Models
230 Volt Models
Type
Code
Type
Code
Heat and cool systems
(with auto changeover)
for use in 4-pipe systems
HC6110-3
087N705300
HC6113-3
087N705700
HCM6110-3
087N706000 HCM6113-3 087N705600
HCW6110-3
087N706100 HCW6113-3 087N706600
Fan Output
3 speed fan output
Power Supply
2 x AA alkaline batteries
(non-rechargeable)
230 Vac ±15%, 50/60Hz
Temperature Range
Heating stage - Off - 5-30°C
Cooling stage - 16-37°C - Off
Temperature Accuracy
± 0.5°C
Deadzone Adjustment
1, 2, 3 or 4°C
Voltage rating of contacts
20-250 Vac, 50/60Hz
Current rating of contacts
10mA - 3A resistive, 1A inductive
Switching Action
Voltage free SPDT contacts, Type 1B
Time Accuracy
± 1 minute
Memory Retention
1 min. for battery change
15 days
IP Rating
IP30
Dimensions (mm)
130 x 100 x 38 (W x H x D)
Control Pollution Situation
Degree 2
Rated Impulse Voltage
2.5 KV
Ball Pressure Test
75°C
Application
Summary of Contents for HC6110-3
Page 66: ...66 ...
Page 67: ...67 ...
Page 68: ...68 Part No 33088v06 05 08 www danfoss com BusinessAreas Heating ...