FC 300 Instruction Manual
General Specifications
Protection and Features:
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heat sink ensures that adjustable frequency drive the trips if the
temperature reaches 203 °F ± 9 °F (95 °C ± 5 °C). An overload temperature cannot be reset until
the temperature of the heat sink is below 158 °F ± 9 °F (70 °C ± 5 °C).
•
The adjustable frequency drive is protected against short circuits on motor terminals U, V, W.
•
If a mains phase is missing, the adjustable frequency drive trips or issues a warning.
•
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive
trips if the intermediate circuit voltage is too low or too high.
•
The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
66
MG.33.A4.22 - VLT is a registered Danfoss trademark