FC 300 Instruction Manual
How to Program
"
8-** Comm. and options
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
8-0* General settings
8-00
Enabled options
[1] All
All set-ups
FALSE
-
Uint8
8-01
Control site
[0] Digital and ctrl.word
All set-ups
TRUE
-
Uint8
8-02
Controlword source
[0] FC RS485
All set-ups
TRUE
-
Uint8
8-03
Controlword Timeout Time
1.0 s
1 set-up
TRUE
-1
Uint32
8-04
Controlword Timeout Function
[0] Off
1 set-up
FALSE
-
Uint8
8-05
End-of-timeout function
[1] Resume set-up
1 set-up
TRUE
-
Uint8
8-06
Reset Controlword Timeout
[0] Do not reset
All set-ups
TRUE
-
Uint8
8-07
Diagnosis trigger
[0] Disable
2 set-ups
FALSE
-
Uint8
8-1* Ctrl. word settings
8-10
Control word profile
[0] FC profile
All set-ups
TRUE
-
Uint8
8-3* FC Port settings
8-30
Protocol
[0] FC
1 set-up
FALSE
-
Uint8
8-31
Address
1
1 set-up
FALSE
0
Uint8
8-32
FC port baudrate
[2] 9600 Baud
1 set-up
FALSE
-
Uint8
8-35
Minimum response delay
10 ms
All set-ups
FALSE
-3
Uint16
8-36
Max response delay
5000 ms
1 set-up
FALSE
-3
Uint16
8-37
Max inter-char delay
25 ms
1 set-up
FALSE
-3
Uint16
8-5* Digital/Bus
8-50
Coasting select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-51
Quick stop select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-52
DC Brake select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-53
Start select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-54
Reverse select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-55
Set-up select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-56
Preset reference select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-9* Bus jog
8-90
Bus Jog 1 Speed
100 RPM
All set-ups
TRUE
67
Uint16
8-91
Bus Jog 2 Speed
200 RPM
All set-ups
TRUE
67
Uint16
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
53