FC 300 Profibus
Application Examples
Program the FC 300 as follows:
Parameter no.
Function
Setting
4-10
Output speed direction
Both directions [2]
5-10
Digital input 18
No operation [0]
5-11
Digital input 19
Reversing [10]
5-40
Function relay
Control word bit 11/12 [36/37]
8-03
Control word timeout time
1 sec
8-04
Control word timeout function
Stop [2]
8-10
Control word profile
FC Profile [0]
8-50
Coasting select
Bus [1]
8-51
Quick stop select
Bus [1]
8-52
DC brake select
Bus [1]
8-53
Start select
Bus [1]
8-54
Reversing select
Logic AND [2]
8-55
Set-up select
Bus [1]
8-56
Preset reference select
Bus [1]
9-16
PCD read configuration
Sub index [2] 16-16 Motor torque
Sub indes [3] 16-60 Digital input
9-18
Node address
Set the address
70
MG.33.C2.02 - VLT is a registered Danfoss trademark