DKRCE.PI.RL0.P4.02 | 7
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 211
Installation guide - ERC 211
Parameter name - ERC 211
Code
Min
Max
Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5
Defrost interval
d03
0
240
hours
8
-
6
6
-
8
Max defrost time
d04
0
480
min
30
-
45
60
-
30
Defrost delay at power up
(or DI signal)
d05
0
240.0
min
0
-
0
0
-
-
Drip delay
d06
0
60
min
0
-
0
0
-
-
Defrost stop sensor
configuration,
non=time,
Air=Sair (air temperature)
d10
non
Air
non
-
non
Air
-
non
Compressor accumulated
runtime to start defrost,
0=OFF
d18
0
96
hours
0
-
0
0
-
-
Defrost delay after pull-down
0=OFF
d30
0
960
min
0
-
0
0
-
-
Compressor
c--
Compressor minimum ON time
C01
0
30
min
0
0
0
0
0
0.0
Compressor minimum OFF time
C02
0
30
min
2
2
2
2
2
2.0
Compressor OFF delay
at door open
C04
0
15
min
0
0
0
0
0
1
Zero crossing selection
C70
no
yES
yES
yES
yES
yES
yES
yES
Others
o--
Delay of outputs
at startup
o01
0
600
min
5
5
5
5
5
5
DI1 configuration
oFF=not used,
Sdc=status display output,
doo=door alarm with resumption,
doA=door alarm without resumption,
SCH = main switch, nig=day/ night
mode, rFd=reference displacement,
EAL=external alarm,
dEF=defrost, Pud=pull-down,
Sc=condenser sensor
o02
oFF
Sc
oFF
oFF
oFF
oFF
oFF
oFF
Serial address
o03
0
247
0
0
0
0
0
-
Password
o05
no
999
no
no
no
no
no
no
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K,
Ptc=PTC, Pt1=Pt1000
o06
n5
Pt1
n10
n10
n10
n10
n10
-
Cooling/heating
rE=refrigeration (cooling)
Ht=heating
o07
rE
Ht
rE
rE
rE
rE
Ht
rE
Display resolution
0.1=steps of 0.1 °C,
0.5=steps of 0.5 °C,
1.0=steps of 1.0 °C
o15
0.1
1.0
0.1
0.1
0.1
0.1
0.1
0.1
Relay 1 counter
(1 count=100 cycles of operation)
o23
0
999
0
0
0
0
0
-
Predefined applications
o61
AP0
AP5
AP0
AP1
AP2
AP3
AP4
-
Save settings as factory
WARNING: the earlier factory settings
are overwritten
o67
no
yES
no
no
no
no
no
-
Display at defrost
Air=actual air temperature,
FrE=freezed temperature,
-d-="-d-" is displayed
o91
Air
-d-
-d-
-
-d-
-d-
-
-d-
Polarity
P--
DI1 input polarity
nc=normally closed,
no=normally open
P73
nc
no
no
no
no
no
no
no
Keyboard lock enable
P76
no
yES
no
no
no
no
no
-
N.B.: hidden parameters are greyed out