DKRCE.PI.RL0.P4.02 | 6
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 211
Installation guide - ERC 211
Parameter name - ERC 211
Code
Min
Max
Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5
Configuration
cFg
Main switch
-1=service, 0=OFF, 1=ON
r12
-1
1
1
1
1
1
1
1
Predefined applications
AP0, AP1, AP2, AP3, AP4, AP5
o61
AP0
AP5
AP0
AP1
AP2
AP3
AP4
AP5
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC,
Pt1=Pt1000
o06
n5
Pt1
n10
n10
n10
n10
n10
n10
Reference/thermostat
r--
Temperature setpoint
r00
-100.0
200.0
C/F
2.0
8.0
4.0
4.0
40.0
2.0
Differential
r01
0.1
20.0
K
2.0
2.0
2.0
2.0
2.0
2.0
Min set point limitation
r02
-100.0
200.0
C/F
-35.0
4.0
2.0
2.0
20.0
-35.0
Max set point limitation
r03
-100.0
200.0
C/F
50.0
20.0
6.0
6.0
60.0
50.0
Display offset
(correction value in display
temperature)
r04
-10.0
10.0
K
0.0
0.0
0.0
0.0
0.0
0.0
Display unit (°C/°F)
r05
-C
-F
-C
-C
-C
-C
-C
-C
Calibration of Sair
(offset for air temperature calibration)
r09
-20.0
20.0
K
0.0
0.0
0.0
0.0
0.0
-
Main switch
-1=service, 0=OFF, 1=ON
r12
-1
1
1
1
1
1
1
-
Night set back
(offset temperature during night
mode)
r13
-50.0
50.0
K
0.0
0.0
0.0
0.0
0.0
0.0
Thermostat reference
displacement
(offset temperature)
r40
-50.0
50.0
K
0.0
0.0
0.0
0.0
0.0
-
Pull-down duration
r96
0
960
min
0
-
0
0
-
-
Pull-down limit temperature
r97
-100.0
200.0
C/F
0.0
-
0.0
0.0
-
-
Alarm
A--
Delay for temperature alarm
during normal conditions
A03
0
240
min
30
45
45
45
30
30
Delay for temperature alarm
during pull-down / start-up / defrost
A12
0
240
min
60
60
90
90
60
60
High temperature alarm limit
(Cabinet / room)
A13
-100.0
200.0
C/F
8.0
16
10
10
80
8.0
Low temperature alarm limit
A14
-100.0
200.0
C/F
-30.0
0.0
0.0
0.0
10
-30.0
DI1 delay
(time delay for selected DI1 function)
A27
0
240
min
30
30
30
30
30
30
Condenser high alarm limit
A37
0
200
C/F
80
80
80
80
-
-
Condenser high block limit
A54
0
200
C/F
85
85
85
85
-
-
Voltage protection enable
A72
no
yES
no
no
no
no
no
no
Minimum cut-in voltage
A73
0
270
V
0
0
0
0
0
0
Minimum cut-out voltage
A74
0
270
V
0
0
0
0
0
0
Maximum voltage
A75
0
270
V
270
270
270
270
270
270
Defrost
d--
Defrost method
no=no defrost, nAt=natural
d01
no
nAt
no
no
nAt
nAt
no
no
Defrost stop temperature
d02
0.0
50.0
C/F
6.0
-
-
8
-
6.0
N.B.: hidden parameters are greyed out
9 - Parameters