48
VI.72.M4.02
Danfoss 11/97
BC-HM
Row
←
(–) Column 0-4 (+)
→
0-9
0
1
2
3
4
0
P0.0
P0.1
P0.2
P0.3
P0.4
Status
Software
System
Time switch
Slave
generation
number
channel select
adress
F: 6
F: 0,0
F: 15
1
P1.0
P1.1
P1.2
P1.3
P1.4
S1 actual
S1 reference
Total stop
Balance
Motor
brine
brine
F: 0
temperature
constant
temperature
temperature
F: 17 °C
F: 120 s
2
P2.0
P2.1
P2.4
S2 actual
S2 reference
X
p
- propor-
room
room
tional band
temperature
temperature
F: 50 K
3
P3.4
T
n
- integra-
tion time
F: 20 s
4
P4.4
N
z
-
neutral zone
F: 2 K
5
P5.0
P5.3
P5.4
S5 actual
S5 scale mid-
Tmax. flow
ext. setpoint
point for ext.
temperature
setpoint
F: 50°C
F: 0 °C
6
P6.0
P6.2
P6.3
P6.4
S6 actual
Compensation
Compensation
Tmin.- flow
compensation
base point
I
factor
I
temperature
temperature
F: 5 °C
F: 0 times
F: -20 °C
7
P7.0
P7.1
P7.2
P7.3
P7.4
S1 actual
Alarm code
Compensation
Compensation
K
p
- propor-
room/brine
base point
II
factor
II
tional factor
temperature
F: 25 °C
F: 0 times
F: 5 times
8
P8.0
Normal
Settings in connection with sensor S2
temperature
F: 5 20 °C
9
P9.0
Settings in connection with sensors S4 and S6,
Reduced
and ext. setpoint S5
temperature
F: 10 30 °C
F:
Factory setting
Factory settings - System types 6-A and 6-B
For further information see page 15 - 21.
Summary of Contents for EPU 2370
Page 24: ...24 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 1 A 1 B and 1 C...
Page 28: ...28 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 1 D and 1 E...
Page 32: ...32 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 2 A and 2 B...
Page 36: ...36 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System type 3...
Page 40: ...40 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 4 A and 4 B...