BC-HM
VI.72.M4.02
Danfoss 11/97
19
P6.0
Actual temperature at sensor S6
Display of actual temperature at sensor S6.
Sensor S6 can be used as follows:
- Lower sensor in hot-water-service storage tank in a tank-charging system (cutout
temperature).
- Compensation sensor, heating, refrigeration and ventilation systems.
P6.1
Required temperature at sensor S6
Display of temperature required at sensor S6 (reference temperature for decoupling
hot-water-service charging system when two sensors are used).
P6.2
System 1: Storage tank temperature differential:
±
(0-90) K
Setting of differential between cutin and cutout temperatures in tank-charging
system.
System 2-6: Compensation I:
±
(0-90)°C
Setting of temperature giving base point for compensation I.
Compensation influences sensor S1 reference.
The value indicates the temperature at which compensation begins. The sign
indicates maximum or minimum compensation.
(+): max. compensation
(-): min. compensation