- With normal and reduced
temperature, total stop function in
P1.2 has the following influence:
0
Reduced temperature: control
according to reduced setpoint
(P9.0).
Fan constantly cut in.
1
Normal temperature: valve closes
and pump stops if the following
two conditions are fulfilled.
-
Room temperature 1 degree
higher than required
temperature.
-
Water temperature limited to
minimum setting.
Reduced temperature: the valve
is closed and fan stopped until
room temperature has fallen to
the required temperature. The
valve is then opened and fan
started until the temperature has
risen 1 degree.
- Relay status for different operating
situations with this system is as
follows:
Operating
Relay 1
Relay 2
condition
Standby
0
1
P1.2 = 0
1
time switch*)
Reduced
P1.2 = 1
0
time switch*)
Normal
1
time switch*)
Frost
0
1
*
)
Relay contact R2 open with reduced
temperature.
0 = open relay contact
1 = closed relay contact