BC-HM
VI.72.M4.02
Danfoss 11/97
47
Notes:
- All frost protection annulled.
- System 6-B (P+PI) is registered
automatically when sensor S2 is
connected. The necessary settings
become visible in the display
(registered when the unit is switched
on).
- Load-dependent compensation is
possible by connecting sensor S6.
Two independent compensation
curves can be set. Curves must be
set in P6.2 and P6.3 in P7.2 and P7.3
respectively.
- With economy temperature, total stop
function in P1.2 has the following
influence:
0
Control according to reduced
setpoint (P9.0).
Fan constantly cut in.
1
Valve closes and fan stops until
the room temperature has risen
to the required temperature.
Valve then opens and fan starts
until room temperature has fallen
1 degree.
- Relay status for different operating
situations with this system is as
follows:
Operating
Relay 1
Relay 2
condition
Standby
0
0
P1.2 = 0
1
time switch**)
Economy
P1.2 = 1
0
time switch**)
Normal
1*)
time switch**)
Wiring diagram - System types 6-A and 6-B
*
)
On changing over from normal to
economy operation, R1 is delayed 3
minutes.
**
)
Relay contact R2 open with reduced
temperature.
0 = open relay contact
1 = closed relay contact
Summary of Contents for EPU 2370
Page 24: ...24 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 1 A 1 B and 1 C...
Page 28: ...28 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 1 D and 1 E...
Page 32: ...32 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 2 A and 2 B...
Page 36: ...36 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System type 3...
Page 40: ...40 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 4 A and 4 B...