Max. pressure in the receiver

The function monitors the pressure in the receiver and will initiate the closing of the 

ICMTS valve if the pressure exceeds the preset value. The value must be at least one 

bar over the reference. The function is not activated when 'n59' is set to 0.

(If n70 is active and attempts to open the valve, n58 will not be active.)

n58

Prec Max

P-band to force closing the ICMTS-valve if the receiver pressure is too high 

P-band over “n58, Prec Max” when the valve is forced closed.

If the pressure becomes 'n58' plus 'n59', the ICMTS valve will be closed. 

The closing of the valve will take place under controlled conditions.

n59

PrecMaxPband

Miscellaneous
Digital input signal - DI 
(terminal 1 and 2)

The controller has a digital input which can be used for one of the following func-

tions:

0: The input is not used

1: External main switch (se also r12)

2: Increasing the pressure in the gas cooler (additional cooling capacity). (closed DI = 

additional capacity)

o02

DI Config

Address

If the controller is built into a network with data communication, it must have an 

address, and the master gateway (system unit) of the data communication must then 

know this address.

These settings can only be made when a data communication module has been 

mounted in the controller and the installation of the data communication cable has 

been completed.

This installation is mentioned in a separate document “RC8AC”

Following installation of a data com-

munication module, the controller can 

be operated on a par with the other 

controllers in ADAP-KOOL® refrigera-

tion controls.

The address is set between 0 and 119 (999)

o03

-

The address is sent to the gateway when the menu is set in pos. ON

(The setting will automatically change back to Off after a few seconds.)

o04

-

Frequency

Set the net frequency.

o12

50 / 60 Hz

(50=0, 60=1)

Pressure transmitter definition for Pgc. Pressure transmitter lower limit

o20

MinTransPgc

Pressure transmitter definition for Pgc. Pressure transmitter upper limit

o21

MaxTransPgc

Pressure transmitter definition for Prec. Pressure transmitter lower limit

o47

MinTransPrec

Pressure transmitter definition for Prec. Pressure transmitter upper limit

o48

MaxTransPrec

Alarm settings

Alarm settings

Pgc Min alarm  limit

An alarm is issued if the value is exceeded

A65

PgcMin AlLim

Permitted variation in relation to Pgc reference

An alarm is issued if the Pgc pressure falls below or exceeds the permitted variation, 

but only once the delay time has expired. This is an 'A94 PgcRef alarm'.

A66

PgcAl Limit

Permitted variation in relation to the Prec reference

An alarm is issued if Prec pressure exceeds or falls below the permitted variation, but 

only once the delay time has expired. This is an 'A95 PrecRef alarm'.

A67

PrecAl Limit

Delay time for 'A94 PgcRef alarm'

A68

PgcAlDelay

Delay time for 'A95 PrecRef alarm'

A69

PrecAlDelay

Service
A number of controller values can be printed for use in a service situation
Read input voltage at Ai-input

u07

AI Volt

Read status of input DI (start/stop input)

u10

DI

Opening degree for ETS (CCM) valve

u24

Vgbp OD %

Calculated reference for regulation (desired pressure in the gas cooler)

U03

Pgc Ref

The output signal to the high pressure valve ICMTS converted into opening degree

U04

Vhp OD %

The temperature in the gas cooler. Measured using temperature sensor Sgc.

U05

Sgc temp.

The pressure in the gas cooler. Measured using pressure transmitter Pgc.

U06

Pgc bar

The pressure in the receiver. Measured using pressure transmitter Prec, but only if it is 

mounted.

U07

Prec bar

Summary of Contents for EKC 326A

Page 1: ...Controller to regulate CO2 gas pressure EKC 326A User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...reading Heat recovery with adjustable reference pressure 0 10 V Optimum heat pump operation System The pressure in the gas cooler is controlled by the valve Regula tion must have inputs from both a pr...

Page 3: ...nput signal of 0 10 V as follows A signal of 1 5 V or above can activate the function and increase the reference to Pgc HR Min If a variable reference is required then a signal between 2 10 V can be c...

Page 4: ...4 Manual RS8FM602 Danfoss 02 2016 EKC 326A Examples Simple heat recovery system Partial heat recovery system Heat recovery system or heat pump system...

Page 5: ...s a signal The function is activated by a voltage signal between 0 10 V Between 0 2 V it is regulated normally At 2 V the reference changes to the setting Pc HR Min At 10 V the reference will increase...

Page 6: ...correspondingly n32 Vhp OD Max Minimum opening degree The closing degree of the ICMTS valve can be limited here Limitation takes place by increasing the lower part of the voltage signal that is sent...

Page 7: ...c Ctrl Receiver reference The reference for receiver control is set here n91 Prec Ref Maximum opening degree The ETS CCM valve s opening degree can be limited here The setting is expressed as a percen...

Page 8: ...the gateway when the menu is set in pos ON The setting will automatically change back to Off after a few seconds o04 Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Pressure transmitter definit...

Page 9: ...apacity through displacement of the pressure reference 43 Alarms E1 Fault in controller Controller fault E15 Cut out Sgc sensor Sgc o c E16 Short circuited Sgc sensor Sgc S C E20 Fault on the signal f...

Page 10: ...efly will display Prec bar Start stop Start stop of regulation r12 OFF 0 On 1 On 1 Ramp for reference after heat recovery r65 0 1 20 1 Displacement of the Pgc minimum reference n89 during heat recover...

Page 11: ...done in this way Cut out the supply voltage to the controller Keep both buttons depressed at the same time as you recon nect the supply voltage 0 V valve closed 10 V valve open Cable connection 060G1...

Page 12: ...een EKC 326A and the ETS CCM CCMT valve exceeds 5 m a filter must be mounted to obtain the correct valve function The filter must be placed close to EKC 326A L 5 m 5 m L 50 m Dimensions Connection Typ...

Page 13: ...m Signal range 2 10 V Sensor input 1 pcs Pt 1000 ohm Alarm relay 1 pcs SPST 250 V a c AC 1 4 A ohmic AC 15 3 A inductive Actuator ICAD mounted on ICMTS Voltage signal 0 10 mA ETS CCM or CCMT 2 8 Step...

Page 14: ...ure plus set p band As such gas can still be sent through the valve Receiver pressure s min limit A minimum receiver pressure limit can be set If the controller register receiver pressure below the se...

Page 15: ...EKC 326A Manual RS8FM602 Danfoss 02 2016 15 Functions for regulation reference...

Page 16: ...rupted none EKC AO remains 0 V ICMT closes if ICMTS has battery back up No change in opening degree EKC Standby Main Switch OFF A45 Standby mode ICMTS closes ETS closes to Vgbp OD Min setting Sgc inte...

Reviews: