Light-emitting diodes (LED) on front panel

The four LED’s will flash, if there is an error in the regulation.

In this situation you can upload the error code on the display and 

cancel the alarm by giving the uppermost button a brief push.

The controller can give the following messages:

E1

Error message

Fault in controller

E15

Cut-out Sgc sensor

E16

Short circuited Sgc sensor

E20

Fault on the signal from Pgc

E39

Fault on the signal from Prec

A43

Alarm message

Step motor error. Output or phase

A45

Regulation stopped. Main switch r12 = off

A82

The Pgc gas pressure measured is higher than the 
maximum limit for n69

A83

The Pgc gas pressure measured is lower than Pgc 
min (A65)

A84

The receiver pressure measured is lower than "n71" 
minus "n72"

A94

Pgc alarm limit "A66" is exceeded

A95

Prec alarm limit "A67" is exceeded

Display

The values will be shown with three digits.

Temperature are to be shown in °C and pressure in bar.

Operation

Menu survey

The buttons

When you want to change a setting, the two buttons will give you 

a higher or lower value depending on the button you are push-

ing. But before you change the value, you must have access to the 

menu. You obtain this by pushing the upper button for a couple 

of seconds - you will then enter the column with parameter codes. 

Find the parameter code you want to change and push the two 

buttons simultaneously. When you have changed the value, save 

the new value by once more pushing the two buttons simultane-

ously.

 

Gives access to the menu (or cutout an alarm)

 

Gives access to changes

 

Saves a change

Examples of operations

Set a menus

1. Push the upper button until a parameter is shown

2. Push one of the buttons and find the parameter you want to 

change

3. Push both buttons simultaneously until the parameter value is 

shown

4. Push one of the buttons and select the new value

5. Push both buttons again to conclude the setting

SW =2.0x

**) The display on the controller can show 3 digits only, but  the setting value has 4 digits. Only the 

3 most important will be shown. It means fx. 250 will give a setting of 2500.

Function

Para-
meter

Min.

Max.

Factory 
setting

Normal display
Shows the current pressure after the gas cooler

Pushing both buttons briefly will display the 

reference

Pushing the bottom button briefly will display 

Prec.

-

bar

Start / stop

Start / stop of regulation

r12

OFF (0) On (1)

On (1)

Ramp for reference after heat recovery

r65

0.1

20

1

Displacement of the Pgc minimum reference 

(n89) during heat recovery. (Displacement value 

at 10 V)

r68

0 bar

100 bar 0

Alarm Settings

Alarm  limit for Pgc Min.

A65

0 bar

200 bar 40

Permitted Pgc reference variation

0 = no alarm function (recommended)

A66

0 bar

50 bar

0

Permitted Prec reference variation

0 = no alarm function (recommended)

A67

0 bar

50 bar

0

Delay time for 'A94' Pgc reference alarm

A68

5 min. 360 min 15

Delay time for 'A95' Prec reference alarm

A69

5 min. 360 min 15

Regulating parameters
Actuator type for receiver control

0=ETS12,5/25 / CCM10/20, 

1=ETS50 / CCM30, 2=ETS100 / CCM40, 

3=ETS250, 4=ETS400, 

5=User defined (set: n37 and n38)

6=CCMT2/4/8

n03

0

6

0

P: Amplification factor Kp

n04

0.5

20

2.0

I:  Integration time Tn

n05

10 s

600 s

75

Max. opening degree. of the valve

n32

0

100

100

Number of steps from 0-100% opening degree 
(x10) **

n37

0

500

262

Number of steps per second

n38

0

300

250

Max. permitted receiver pressure, Prec

n58

10 bar 200 bar 60

P-belt beyond PrecMax for valve to close

n59

0 bar

60 bar

0

P: Amplification factor Kp for receiver

n60

0.5

20

5

I:  Integration time Tn for receiver

n61

10

600

75

The gas cooler’s max. pressure

This is where you set the maximum pressure per-

mitted in the gas cooler. If the pressure reaches 

this value, the valve is fully open.

n69

7

200

90

P-band under n69, so the valve is fully open if 

the pressure is n69.

n70

0

60

5

Min. pressure in the receiver

This function is only used if the pressure trans-

mitter Prec is mounted.

n71

7

60

30

P-band to force open the valve if the receiver 

pressure is too low 

n72

0

60

3

Subcooling is required to be regulated accord-

ing to temperature

Set the desired subcooling in K.

n79

1 K

30 K

1

The gas cooler’s min. pressure

n81

7

200 bar 45

Min. permissible opening degree for ICMTS

n87

0

100%

0

Extra capacity when the contact is closed. 

(The Pgc reference is increased with this value)

n88

0 bar

200 bar 0

Minimum permitted Pgc reference during heat 

recovery (AI > 2 V). The value can be increased 

further using the r68 function.  

n89

7 bar

200 bar 7

Do you require receiver pressure control: Off=no, 

On=yes

n90

Off

On

On

Prec. reference for receiver pressure control

n91

7 bar

200 bar 35

Receiver pressure control. Maximum opening 

degree for ETS

n92

0%

100%

100

Receiver pressure control. Smallest opening 

degree for ETS

n93

0%

100%

0

Define the reference curve point at 100 bar.

n99

35°C

55°C

39

Summary of Contents for EKC 326A

Page 1: ...Controller to regulate CO2 gas pressure EKC 326A User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...reading Heat recovery with adjustable reference pressure 0 10 V Optimum heat pump operation System The pressure in the gas cooler is controlled by the valve Regula tion must have inputs from both a pr...

Page 3: ...nput signal of 0 10 V as follows A signal of 1 5 V or above can activate the function and increase the reference to Pgc HR Min If a variable reference is required then a signal between 2 10 V can be c...

Page 4: ...4 Manual RS8FM602 Danfoss 02 2016 EKC 326A Examples Simple heat recovery system Partial heat recovery system Heat recovery system or heat pump system...

Page 5: ...s a signal The function is activated by a voltage signal between 0 10 V Between 0 2 V it is regulated normally At 2 V the reference changes to the setting Pc HR Min At 10 V the reference will increase...

Page 6: ...correspondingly n32 Vhp OD Max Minimum opening degree The closing degree of the ICMTS valve can be limited here Limitation takes place by increasing the lower part of the voltage signal that is sent...

Page 7: ...c Ctrl Receiver reference The reference for receiver control is set here n91 Prec Ref Maximum opening degree The ETS CCM valve s opening degree can be limited here The setting is expressed as a percen...

Page 8: ...the gateway when the menu is set in pos ON The setting will automatically change back to Off after a few seconds o04 Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Pressure transmitter definit...

Page 9: ...apacity through displacement of the pressure reference 43 Alarms E1 Fault in controller Controller fault E15 Cut out Sgc sensor Sgc o c E16 Short circuited Sgc sensor Sgc S C E20 Fault on the signal f...

Page 10: ...efly will display Prec bar Start stop Start stop of regulation r12 OFF 0 On 1 On 1 Ramp for reference after heat recovery r65 0 1 20 1 Displacement of the Pgc minimum reference n89 during heat recover...

Page 11: ...done in this way Cut out the supply voltage to the controller Keep both buttons depressed at the same time as you recon nect the supply voltage 0 V valve closed 10 V valve open Cable connection 060G1...

Page 12: ...een EKC 326A and the ETS CCM CCMT valve exceeds 5 m a filter must be mounted to obtain the correct valve function The filter must be placed close to EKC 326A L 5 m 5 m L 50 m Dimensions Connection Typ...

Page 13: ...m Signal range 2 10 V Sensor input 1 pcs Pt 1000 ohm Alarm relay 1 pcs SPST 250 V a c AC 1 4 A ohmic AC 15 3 A inductive Actuator ICAD mounted on ICMTS Voltage signal 0 10 mA ETS CCM or CCMT 2 8 Step...

Page 14: ...ure plus set p band As such gas can still be sent through the valve Receiver pressure s min limit A minimum receiver pressure limit can be set If the controller register receiver pressure below the se...

Page 15: ...EKC 326A Manual RS8FM602 Danfoss 02 2016 15 Functions for regulation reference...

Page 16: ...rupted none EKC AO remains 0 V ICMT closes if ICMTS has battery back up No change in opening degree EKC Standby Main Switch OFF A45 Standby mode ICMTS closes ETS closes to Vgbp OD Min setting Sgc inte...

Reviews: