Danfoss EKC 326A User Manual Download Page 14

14 

Manual RS8FM602 © Danfoss 02-2016 

EKC 

326A

Guideline for setting automatic safety control

The following ratio between pressure and temperature can be used 

to set the automatic safety control.

Regulation limitations of the receiver pressure

Safety functions

There are two safety functions for the receiver. They are only avail-

able for gas-cooled regulation. 

A P-belt must be installed to be able to regulate the function, but 

both are standard set to zero, which makes the function inactive. 

Receiver pressure's max. limit

Set a max. receiver pressure. If the controller register receiver 

pressure beyond the set value, the ICMTS valve will be closed. 

The opening degree will be linear through the p-band so that the 

ICMTS valve will be closed by pressing 'set max. receiver pressure' 

plus 'set-p-band'.

If the valve's opening degree is set to a limited value and cannot 

be fully closed, the set opening degree value will be at the pres-

sure 'set max. receiver pressure' plus 'set p-band'.

As such, gas can still be sent through the valve.

Receiver pressure's min. limit:  

A minimum receiver pressure limit can be set. If the controller 

register receiver pressure below the set value, the ICMTS valve will 

be opened. The opening degree will be linear through the p-band, 

and the maximum permitted opening degree of the ICMTS will be 

present by pressing 'set min. receiver pressure' minus 'set-p-band'.

If the setting of the valve's opening degree is limited and it cannot 

be fully opened,  the set opening degree value will be at the pres-

sure 'set min. receiver pressure' minus 'set p-band'.

Note 

The PI regulation of the receiver pressure must have space to 

regulate without restrictions.

This means that there should be sufficient space for the PI regula-

tion to move around the reference, i.e. at least 2-3 bars – both over 

and below the reference. 

The value is very dependent on the tuning of the PI regulation 

and the system dynamics. 

An example may be a 40-bar plant in which the receiver's refer-

ence pressure is set to 35 bars. Here the system can interfere 

with normal regulation because the high pressure limit is very 

stringent.

Appendix

Summary of Contents for EKC 326A

Page 1: ...Controller to regulate CO2 gas pressure EKC 326A User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...reading Heat recovery with adjustable reference pressure 0 10 V Optimum heat pump operation System The pressure in the gas cooler is controlled by the valve Regula tion must have inputs from both a pr...

Page 3: ...nput signal of 0 10 V as follows A signal of 1 5 V or above can activate the function and increase the reference to Pgc HR Min If a variable reference is required then a signal between 2 10 V can be c...

Page 4: ...4 Manual RS8FM602 Danfoss 02 2016 EKC 326A Examples Simple heat recovery system Partial heat recovery system Heat recovery system or heat pump system...

Page 5: ...s a signal The function is activated by a voltage signal between 0 10 V Between 0 2 V it is regulated normally At 2 V the reference changes to the setting Pc HR Min At 10 V the reference will increase...

Page 6: ...correspondingly n32 Vhp OD Max Minimum opening degree The closing degree of the ICMTS valve can be limited here Limitation takes place by increasing the lower part of the voltage signal that is sent...

Page 7: ...c Ctrl Receiver reference The reference for receiver control is set here n91 Prec Ref Maximum opening degree The ETS CCM valve s opening degree can be limited here The setting is expressed as a percen...

Page 8: ...the gateway when the menu is set in pos ON The setting will automatically change back to Off after a few seconds o04 Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Pressure transmitter definit...

Page 9: ...apacity through displacement of the pressure reference 43 Alarms E1 Fault in controller Controller fault E15 Cut out Sgc sensor Sgc o c E16 Short circuited Sgc sensor Sgc S C E20 Fault on the signal f...

Page 10: ...efly will display Prec bar Start stop Start stop of regulation r12 OFF 0 On 1 On 1 Ramp for reference after heat recovery r65 0 1 20 1 Displacement of the Pgc minimum reference n89 during heat recover...

Page 11: ...done in this way Cut out the supply voltage to the controller Keep both buttons depressed at the same time as you recon nect the supply voltage 0 V valve closed 10 V valve open Cable connection 060G1...

Page 12: ...een EKC 326A and the ETS CCM CCMT valve exceeds 5 m a filter must be mounted to obtain the correct valve function The filter must be placed close to EKC 326A L 5 m 5 m L 50 m Dimensions Connection Typ...

Page 13: ...m Signal range 2 10 V Sensor input 1 pcs Pt 1000 ohm Alarm relay 1 pcs SPST 250 V a c AC 1 4 A ohmic AC 15 3 A inductive Actuator ICAD mounted on ICMTS Voltage signal 0 10 mA ETS CCM or CCMT 2 8 Step...

Page 14: ...ure plus set p band As such gas can still be sent through the valve Receiver pressure s min limit A minimum receiver pressure limit can be set If the controller register receiver pressure below the se...

Page 15: ...EKC 326A Manual RS8FM602 Danfoss 02 2016 15 Functions for regulation reference...

Page 16: ...rupted none EKC AO remains 0 V ICMT closes if ICMTS has battery back up No change in opening degree EKC Standby Main Switch OFF A45 Standby mode ICMTS closes ETS closes to Vgbp OD Min setting Sgc inte...

Reviews: