Minimum pressure reference during heat recovery

The function can only be used if heat recovery or heat pumps are also used in the system.

The function will increase the gas pressure to the set value when it receives a signal.

The function is activated by a voltage signal at the input to terminal 20. A voltage 

over 1.5 V will activate the function. (Please install a support relay if there is any risk of 

error signals, e.g. with long wires.)

If the function is only required for displacement, r68 should be set to 0.

(The gas pressure can be further increased using the r68 function.)

n89

Pgc HR Min

Displacement of the control reference during heat recovery

This function increases the reference to a value above the n89 setting, but no higher 

than the set value.

Displacement occurs when an input voltage of above 2 V is received for terminal 20. 

The new reference is: Setting in n89 + displacement.

The value of the displacement is determined by the voltage signal and the setting for 

r68.

10 V gives maximum displacement, i.e. the set value. 2 V or below will give nothing. 

Displacement is linear between 2 and 10 V.

r68

Pgc HR offset

Ramp for reference modification

This can be used to set the speed at which the reference must drop again following 

heat recovery (number bar/min). The function is only active after heat recovery is 

complete.

r65

Pgc Ref Ramp

Receiver control

Receiver pressure control

Receiver control

Whether control of the receiver pressure should take place is defined here.

On: ETS (CCM) control. Alarm active

Off: No ETC (CCM) control. No alarm. Pressure control is active

n90

Prec. Ctrl

Receiver reference

The reference for receiver control is set here.

n91

Prec Ref

Maximum opening degree

The ETS (CCM) valve’s opening degree can be limited here. The setting is expressed as 

a percentage of the total opening degree. 

n92

Vgbp OD Max

Minimum opening degree

The closing degree of ETS (CCM) valves can be limited here. The setting is expressed 

as a percentage of the total opening degree.

n93

Vgbp OD Min

Min. pressure in the receiver

The function monitors the pressure in the receiver and will start to force open the 

ICMTS-valve if the pressure falls below the preset value. The value must be at least 1 

bar below the reference.  The function is deactivated if n72 is set to 0.

n71

Prec Min

P-band to force open the ICMTS-valve if the receiver pressure is too low 

P-band under “n71, Prec Min” when the valve is forced open.

If the pressure falls to n71 minus n72, the ICMTS valve will open to the value in n32, 

Vhp OD Max. An alarm is then transmitted.

The pressure is not critical, so opening of the valve will take place under controlled 

conditions.

n72

Prec Min Pband

P: Amplification factor Kp

If the Kp value is reduced the regulation becomes slower.

n60

Kp Receiver

I: Integration time Tn

If the Tn value is increased the regulation becomes slower

n61

Tn Receiver

Actuator type

If receiver control takes place, the type of valve should be set:

0: ETS 12½, ETS 25, CCM 10, CCM 20

1: ETS 50, CCM 30

2: ETS 100, CCM 40

3: ETS 250

4: ETS 400

5: Other type. "n37" and "n38" should also be set when the setting = 5 

("n37" and "n38" are automatically set for settings 0 to 4)

6: CCMT 2, 4, 8

n03

Valve type

ETS (CCM) setting

Number of steps open from 0-100%

Automatically set when "n03" is set to 0, 1, 2, 3, 4 or 6

n37

Max. steps

ETS (CCM) setting

Speed of spindle travel (no. of steps per second)

Automatically set when "n03" is set to 0, 1, 2, 3, 4 or 6

n38

Steps / sec

Summary of Contents for EKC 326A

Page 1: ...Controller to regulate CO2 gas pressure EKC 326A User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...reading Heat recovery with adjustable reference pressure 0 10 V Optimum heat pump operation System The pressure in the gas cooler is controlled by the valve Regula tion must have inputs from both a pr...

Page 3: ...nput signal of 0 10 V as follows A signal of 1 5 V or above can activate the function and increase the reference to Pgc HR Min If a variable reference is required then a signal between 2 10 V can be c...

Page 4: ...4 Manual RS8FM602 Danfoss 02 2016 EKC 326A Examples Simple heat recovery system Partial heat recovery system Heat recovery system or heat pump system...

Page 5: ...s a signal The function is activated by a voltage signal between 0 10 V Between 0 2 V it is regulated normally At 2 V the reference changes to the setting Pc HR Min At 10 V the reference will increase...

Page 6: ...correspondingly n32 Vhp OD Max Minimum opening degree The closing degree of the ICMTS valve can be limited here Limitation takes place by increasing the lower part of the voltage signal that is sent...

Page 7: ...c Ctrl Receiver reference The reference for receiver control is set here n91 Prec Ref Maximum opening degree The ETS CCM valve s opening degree can be limited here The setting is expressed as a percen...

Page 8: ...the gateway when the menu is set in pos ON The setting will automatically change back to Off after a few seconds o04 Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Pressure transmitter definit...

Page 9: ...apacity through displacement of the pressure reference 43 Alarms E1 Fault in controller Controller fault E15 Cut out Sgc sensor Sgc o c E16 Short circuited Sgc sensor Sgc S C E20 Fault on the signal f...

Page 10: ...efly will display Prec bar Start stop Start stop of regulation r12 OFF 0 On 1 On 1 Ramp for reference after heat recovery r65 0 1 20 1 Displacement of the Pgc minimum reference n89 during heat recover...

Page 11: ...done in this way Cut out the supply voltage to the controller Keep both buttons depressed at the same time as you recon nect the supply voltage 0 V valve closed 10 V valve open Cable connection 060G1...

Page 12: ...een EKC 326A and the ETS CCM CCMT valve exceeds 5 m a filter must be mounted to obtain the correct valve function The filter must be placed close to EKC 326A L 5 m 5 m L 50 m Dimensions Connection Typ...

Page 13: ...m Signal range 2 10 V Sensor input 1 pcs Pt 1000 ohm Alarm relay 1 pcs SPST 250 V a c AC 1 4 A ohmic AC 15 3 A inductive Actuator ICAD mounted on ICMTS Voltage signal 0 10 mA ETS CCM or CCMT 2 8 Step...

Page 14: ...ure plus set p band As such gas can still be sent through the valve Receiver pressure s min limit A minimum receiver pressure limit can be set If the controller register receiver pressure below the se...

Page 15: ...EKC 326A Manual RS8FM602 Danfoss 02 2016 15 Functions for regulation reference...

Page 16: ...rupted none EKC AO remains 0 V ICMT closes if ICMTS has battery back up No change in opening degree EKC Standby Main Switch OFF A45 Standby mode ICMTS closes ETS closes to Vgbp OD Min setting Sgc inte...

Reviews: