Danfoss EKC 315A User Manual Download Page 5

EKC 315A 

Manual  RS8CS302  ©  Danfoss  07-2005 

5

Control parameters

 

P: Amplification factor Kp

If the Kp value is reduced the regulation becomes slower.

n04

Kp factor

I: Integration time Tn

If the Tn value is increased the regulation becomes slowe

n05

Tn sec.

D: Differentiation time Td

The D-setting can be cancelled by setting the value to min. (0).)

n06

Td sec.

Max. value for the superheat reference

n09

Max SH

Min. value for the superheat reference

Warning! Due to the risk of liquid flow the setting should not be lower than approx. 

2-4 K.

n10

Min SH

MOP

If no MOP function is required, select pos. Off.

n11

MOP (Bar)

(A value of 60 bar corresponds to Off)

AKV valve's time period in seconds

Should only be set to a lower value if it is a decentralised plant and the suction pres-

sure fluctuates a lot and in line with the opening of the AKV valve.

n13

AKV per. time

Stability factor for regulation of superheat

With a higher value the control function will allow a greater fluctuation of the super-

heat before the reference is changed. The value should only be changed by specially 

trained staff.

n18

Stability

Damping of amplification near reference value

This setting damps the normal amplification Kp, but only just around the reference 

value. A setting of 0.5 will reduce the KP value by half.

The value should only be changed by specially trained staff.

n19

Kp Min

Amplification factor for the superheat (AKV only and only in 1:1 plant)

This setting determines the valve’s opening degree as a function of the change in 

evaporating pressure. An increase of the evaporating pressure will result in a reduced 

opening degree. When there is a drop-out on the low-pressure thermostat during 

start-up the value must be raised a bit. If there is pendling during start-up the value 

must be reduced a little.

The value should only be changed by specially trained staff.

n20

Kp T0 

Definition of superheat regulation (Ref. appendix 6)

1:  Lowest permissible superheat (MSS). Adaptive regulation.

2:  Load-defined superheat. The reference is established based on the line formed by 

the three points: n09, n10 and n22.

n21

SH mode

Value of min. superheat reference for loads under 10%

(The value must be smaller than ”n10”).

n22

SH Close

Standby temperature when valve closed (TQ only)

The TQ actuator is kept warm when the valve reaches its closing point. As the closing 

point cannot be defined completely accurately due to tolerances and pressure varia-

tions, the setting can be changed, as required (how ”tightly”/securely the valve is to 

close).  See also appendices 1 and 5.

n26

TQ Kmin

Standby temerature when valve open (TQ only)

The TQ actuator’s temperature is kept low when the valve reaches its fully open posi-

tion. Here you set how many degrees the temperature is to be above the expected 

open temperature in completely open position. The greater the value, the surer it 

is that the valve will be open, but it will also react more slowly when it has to close 

again.

n27

TQ Kmax

Max. opening degree (AKV only)

The valve’s opening degree can be limited. The value is set in %.

n32

AKV/A OD Max

Summary of Contents for EKC 315A

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for control of industrial evaporator EKC 315A Manual...

Page 2: ...ctions Regulation of superheat Temperature control MOP function ON OFF input for start stop of regulation Input signal that can displace the superheat reference or the temperature reference Alarm if t...

Page 3: ...valve will operate when refrigeration is required The relay for the alarm function works in such a way thatr the contact is cut in in alarm situations and when the con troller is de energised Modulati...

Page 4: ...ensor cable r09 Adjust S2 Correction of signal from S3 Compensation possibility through long sensor cable r10 Adjust S3 Start stop of refrigeration With this setting refrigeration can be started and s...

Page 5: ...is setting determines the valve s opening degree as a function of the change in evaporating pressure An increase of the evaporating pressure will result in a reduced opening degree When there is a dro...

Page 6: ...with 4 20 mA 4 or 0 mA will not give a displacement 20 mA will displace the reference by the value set in menu r06 o10 AI A type Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Select signal f...

Page 7: ...the thermostat or the duration of the last completed cutin u18 Ther RunTime Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 S...

Page 8: ...Min Max Factory setting Normal display Shows the actual superheat valve s opening degree temperature De ne view in O17 K If you wish to see the expansion valve s actual opening degree give the lower b...

Page 9: ...select ON 2 AKV A output select ON 3 Alarm relay activated cut out o18 o 3 O Working range for pressure transmitter min value o20 1 bar 60 bar 1 0 Working range for pressure transmitter max value o21...

Page 10: ...084B7086 EKA 173 Data communication module accessories FTT 10 module 084B7092 EKA 175 Data communication module accessories RS 485 modul 084B7093 EKA 174 Data communication module accessories RS 485...

Page 11: ...on line accumulators Your local Danfoss agent will be pleased to assist with further advice etc Appendix 1 Interaction between internal and external start stop functions and active functions Appendix...

Page 12: ...be warmer when the valve is completely open If the value is high you can be sure that the valve is completely open but then it will also react slowly when it has to close again Appendix 6 The two typ...

Page 13: ...lternatively it may be due to the fact that the set regulation parameters are not optimal If the time of oscillation is longer than the integration time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1...

Page 14: ...m the various menu displays The programme will for exam ple upload all the collected temperature values once a day Measurements are shown at one side and settings at the other You will also be able to...

Page 15: ...EKC 315A Manual RS8CS302 Danfoss 07 2005 15...

Page 16: ...s can be estab lished Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This a...

Reviews: