EKC 315A

Appendix 5

Standby temperatures for TQ valves.

TQ valve

The valve’s actuator temperature is limited, both when regula-
tion is stopped and when the valve is right out at the opening 
point and closing point.
(The opening and closing points may fluctuate a couple of de-
grees up or down, depending on pressures and tolerances).

n26
The setting is based on the TQ valve’s closing curve. With a plus 
value the valve can be kept slightly open. With a minus value the 
valve can be closed completely. If the minus value is high you 
can be sure that the valve will close, but then it will also react 
slowly when it has to open again. 

n27
This setting defines the number of degrees the actuator has to 
be warmer when the valve is completely open. If the value is 
high you can be sure that the valve is completely open, but then 
it will also react slowly when it has to close again.

Appendix 6

The two types of regulation for superheat are, as follows:

Adaptive superheat

Regulation is here based on the evaporator’s load by means of 
MSS search (MSS = lowest permissible superheat).
(The superheat reference is lowered to the exact point where 
instability sets in).
The superheat is limited by the settings for min.and max.super-
heat.

Load-defined superheat

The reference follows a defined curve.This curve is defined by 
three values: the closing value, the min. value and the max. 
value. These three values must be selected in such a way that 
the curve is situated between the MSS curve and the curve for 
average temperature difference 

Tm (temperature difference 

between media temperature and evaporating temperature.
Setting example = 4, 6 and 10 K).

Summary of Contents for EKC 315A

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for control of industrial evaporator EKC 315A Manual...

Page 2: ...ctions Regulation of superheat Temperature control MOP function ON OFF input for start stop of regulation Input signal that can displace the superheat reference or the temperature reference Alarm if t...

Page 3: ...valve will operate when refrigeration is required The relay for the alarm function works in such a way thatr the contact is cut in in alarm situations and when the con troller is de energised Modulati...

Page 4: ...ensor cable r09 Adjust S2 Correction of signal from S3 Compensation possibility through long sensor cable r10 Adjust S3 Start stop of refrigeration With this setting refrigeration can be started and s...

Page 5: ...is setting determines the valve s opening degree as a function of the change in evaporating pressure An increase of the evaporating pressure will result in a reduced opening degree When there is a dro...

Page 6: ...with 4 20 mA 4 or 0 mA will not give a displacement 20 mA will displace the reference by the value set in menu r06 o10 AI A type Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Select signal f...

Page 7: ...the thermostat or the duration of the last completed cutin u18 Ther RunTime Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 S...

Page 8: ...Min Max Factory setting Normal display Shows the actual superheat valve s opening degree temperature De ne view in O17 K If you wish to see the expansion valve s actual opening degree give the lower b...

Page 9: ...select ON 2 AKV A output select ON 3 Alarm relay activated cut out o18 o 3 O Working range for pressure transmitter min value o20 1 bar 60 bar 1 0 Working range for pressure transmitter max value o21...

Page 10: ...084B7086 EKA 173 Data communication module accessories FTT 10 module 084B7092 EKA 175 Data communication module accessories RS 485 modul 084B7093 EKA 174 Data communication module accessories RS 485...

Page 11: ...on line accumulators Your local Danfoss agent will be pleased to assist with further advice etc Appendix 1 Interaction between internal and external start stop functions and active functions Appendix...

Page 12: ...be warmer when the valve is completely open If the value is high you can be sure that the valve is completely open but then it will also react slowly when it has to close again Appendix 6 The two typ...

Page 13: ...lternatively it may be due to the fact that the set regulation parameters are not optimal If the time of oscillation is longer than the integration time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1...

Page 14: ...m the various menu displays The programme will for exam ple upload all the collected temperature values once a day Measurements are shown at one side and settings at the other You will also be able to...

Page 15: ...EKC 315A Manual RS8CS302 Danfoss 07 2005 15...

Page 16: ...s can be estab lished Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This a...

Reviews: