EKC 315A

Ref.      Diff.

Function

Para- 

meter

Parameter by operation via 

data communication

Normal display

Normally the superheat is shown (but the valve’s opening degree or air temperature 

may also be selected. See o17).

SH  /  OD%  /  S3 temp

Reference

Se point

Regulation is performed based on the set value provided that there is no external 

contribution (o10).

(Push both buttons simultaneously to set the setpoint).

-

TempSetpoint.

Differential

When the temperature is higher than the reference plus the set differential, the sole-

noid valve’s relay will be activated. It will become deactivated when the temperature 

drops below the set reference.

r01

Differential

Unit

Here you select whether the controller is to indicate the temperature values in °C or 

in °F. If  indication in °F is selected, other temperature settings will also change over to 

Fahrenheit, either as absolute values or as delta values

The combination of temperature unit and pressure unit is depicted to the right.

r05

Units

0: °C + bar

1: °F + psig

(in AKM only °C + bar – is displayed 

– whatever the setting).

External contribution to the reference 

This setting determines how large a contribution is to be added to the set setpoint 

when the input signal is max. (20 mA). See o10.

r06

ExtRefOffset

Correction of signal from S2

(Compensation possibility through long sensor cable).

r09

Adjust S2

Correction of signal from S3

(Compensation possibility through long sensor cable).

r10

Adjust S3

Start/stop of refrigeration

With this setting refrigeration can be started and stopped. Start/stop of refrigeration 

can also be accomplished with the external switch function. See also appendix 1.

r12

Main Switch

Define thermostat function

0:  No thermostat function. Only the superheat is regulated

1:  Thermostat function as well as regulation of superheat.

r14

Therm. Mode

Alarm

The controller can give alarm in different situations. When there is an alarm all the 

light-emitting diodes (LED) will flash on the controller front panel, and the alarm relay 

will cut in.

Alarm for upper deviation

The alarm for too high S3 temperature is set here. The value is set in Kelvin. The alarm 

becomes active when the S3 temperature exceeds the actual reference plus A01. (The 

actual reference can be seen in u28).

A01

Hgh.TempAlrm

Alarm for lower deviation

The alarm for too low S3 temperature is set here. The value is set in Kelvin. The alarm 

becomes active when the S3 temperature drops below the actual reference minus 

A02.

A02

Low.TempAlrm

Alarm delay

If one of the two limit values is exceeded, a timer function will commence. The alarm 

will not become active until the set time delay has been passed. The time delay is set 

in minutes.

A03

TempAlrmDel

With data communication the impor-

tance of the individual alarms can be 

defined. Setting is carried out in the 

“Alarm destinations” menu. See also 

page 14

Survey of functions

Summary of Contents for EKC 315A

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for control of industrial evaporator EKC 315A Manual...

Page 2: ...ctions Regulation of superheat Temperature control MOP function ON OFF input for start stop of regulation Input signal that can displace the superheat reference or the temperature reference Alarm if t...

Page 3: ...valve will operate when refrigeration is required The relay for the alarm function works in such a way thatr the contact is cut in in alarm situations and when the con troller is de energised Modulati...

Page 4: ...ensor cable r09 Adjust S2 Correction of signal from S3 Compensation possibility through long sensor cable r10 Adjust S3 Start stop of refrigeration With this setting refrigeration can be started and s...

Page 5: ...is setting determines the valve s opening degree as a function of the change in evaporating pressure An increase of the evaporating pressure will result in a reduced opening degree When there is a dro...

Page 6: ...with 4 20 mA 4 or 0 mA will not give a displacement 20 mA will displace the reference by the value set in menu r06 o10 AI A type Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Select signal f...

Page 7: ...the thermostat or the duration of the last completed cutin u18 Ther RunTime Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 S...

Page 8: ...Min Max Factory setting Normal display Shows the actual superheat valve s opening degree temperature De ne view in O17 K If you wish to see the expansion valve s actual opening degree give the lower b...

Page 9: ...select ON 2 AKV A output select ON 3 Alarm relay activated cut out o18 o 3 O Working range for pressure transmitter min value o20 1 bar 60 bar 1 0 Working range for pressure transmitter max value o21...

Page 10: ...084B7086 EKA 173 Data communication module accessories FTT 10 module 084B7092 EKA 175 Data communication module accessories RS 485 modul 084B7093 EKA 174 Data communication module accessories RS 485...

Page 11: ...on line accumulators Your local Danfoss agent will be pleased to assist with further advice etc Appendix 1 Interaction between internal and external start stop functions and active functions Appendix...

Page 12: ...be warmer when the valve is completely open If the value is high you can be sure that the valve is completely open but then it will also react slowly when it has to close again Appendix 6 The two typ...

Page 13: ...lternatively it may be due to the fact that the set regulation parameters are not optimal If the time of oscillation is longer than the integration time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1...

Page 14: ...m the various menu displays The programme will for exam ple upload all the collected temperature values once a day Measurements are shown at one side and settings at the other You will also be able to...

Page 15: ...EKC 315A Manual RS8CS302 Danfoss 07 2005 15...

Page 16: ...s can be estab lished Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This a...

Reviews: