Danfoss EKC 315A User Manual Download Page 2

Manual  RS8CS302  ©  Danfoss  07-2005 

EKC 315A

Introduction

Application

The controller and valve can be used where there are  require-
ments to accurate control of superheat and  temperature

 

in con-

nection with refrigeration.
E.g.:
• Cold store (air coolers)
• Processing plant (water chillers)
• A/C plant

Advantages

• The evaporator is charged optimally – even when there are great 

variations of load and suction pressure

• Energy savings – the adaptive regulation of the refrigerant injec-

tion ensures optimum utilisation of the evaporator and hence a 
high suction pressure

• Exact temperature control – the combination of adaptive 

evaporator and temperature control ensures great temperature 
accuracy for the media

• The superheating is regulated to the lowest possible value at 

the same time as the media temperature is controlled by the 
thermostat function

Functions

• Regulation of superheat
• Temperature control
• MOP function
• ON/OFF input for start/stop of regulation
• Input signal that can displace the superheat reference or the 

temperature reference

• Alarm if the set alarm limits are exceeded
• Relay output for solenoid valve
• PID regulation
• Output signal following the temperature showing in the display

System

The superheat in the evaporator is controlled by one pressure 
transmitter P and one temperature sensor S2.
The valve can be one of the following types:
• TQ (PHTQ, TEAQ)
• AKV (AKVA)
TQ is a modulating valve, and when this is used a solenoid valve 
must also be used in the liquid line.
AKV is a pulsating valve.
Where the AKV valve is used it also functions as solenoid valve.
Temperature control is performed based on a signal from tem-
perature sensor S3 which is placed in the air current before the 
evaporator. Temperature control is in the shape of an ON/OFF 
thermostat that shuts off the liquid flow in the liquid line, either 
via the solenoid valve in TQ applications or directly when AKV is 
used.

Summary of Contents for EKC 315A

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for control of industrial evaporator EKC 315A Manual...

Page 2: ...ctions Regulation of superheat Temperature control MOP function ON OFF input for start stop of regulation Input signal that can displace the superheat reference or the temperature reference Alarm if t...

Page 3: ...valve will operate when refrigeration is required The relay for the alarm function works in such a way thatr the contact is cut in in alarm situations and when the con troller is de energised Modulati...

Page 4: ...ensor cable r09 Adjust S2 Correction of signal from S3 Compensation possibility through long sensor cable r10 Adjust S3 Start stop of refrigeration With this setting refrigeration can be started and s...

Page 5: ...is setting determines the valve s opening degree as a function of the change in evaporating pressure An increase of the evaporating pressure will result in a reduced opening degree When there is a dro...

Page 6: ...with 4 20 mA 4 or 0 mA will not give a displacement 20 mA will displace the reference by the value set in menu r06 o10 AI A type Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Select signal f...

Page 7: ...the thermostat or the duration of the last completed cutin u18 Ther RunTime Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 S...

Page 8: ...Min Max Factory setting Normal display Shows the actual superheat valve s opening degree temperature De ne view in O17 K If you wish to see the expansion valve s actual opening degree give the lower b...

Page 9: ...select ON 2 AKV A output select ON 3 Alarm relay activated cut out o18 o 3 O Working range for pressure transmitter min value o20 1 bar 60 bar 1 0 Working range for pressure transmitter max value o21...

Page 10: ...084B7086 EKA 173 Data communication module accessories FTT 10 module 084B7092 EKA 175 Data communication module accessories RS 485 modul 084B7093 EKA 174 Data communication module accessories RS 485...

Page 11: ...on line accumulators Your local Danfoss agent will be pleased to assist with further advice etc Appendix 1 Interaction between internal and external start stop functions and active functions Appendix...

Page 12: ...be warmer when the valve is completely open If the value is high you can be sure that the valve is completely open but then it will also react slowly when it has to close again Appendix 6 The two typ...

Page 13: ...lternatively it may be due to the fact that the set regulation parameters are not optimal If the time of oscillation is longer than the integration time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1...

Page 14: ...m the various menu displays The programme will for exam ple upload all the collected temperature values once a day Measurements are shown at one side and settings at the other You will also be able to...

Page 15: ...EKC 315A Manual RS8CS302 Danfoss 07 2005 15...

Page 16: ...s can be estab lished Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This a...

Reviews: