Danfoss EKC 312 User Manual Download Page 8

8  

 

 

 

DKRCC.PS.R1.A3.02 / 520H9752 

 

© Danfoss A/S (DCS-IMCGPD/sw), 2015-03

Manual 

Electronic superheat controller, type EKC 312

Display

The values will be shown with three digits, and with a setting you 

can determine whether the temperature are to be shown in °C or 

in °F.  (Pressure in bar or psig.)

Light-emitting diodes (LED) on front panel

There are LED’s on the front panel which will light up when the 

belonging relay is activated.

The uppermost LED will indicate when the valve is moving 

towards a greater opening degree.

The next LED will indicate when the valve is moving towards a 

smaller opening degree.

All light-emitting diodes will flash when there is an error in the 

regulation.

In this situation you can upload the error code on the display and 

cancel the alarm by giving the uppermost button a brief push.

The buttons

When you want to change a setting, the two buttons will give 

you a higher or lower value depending on the button you are 

pushing. But before you change the value, you must have access 

to the menu. You obtain this by pushing the upper button for a 

couple of seconds - you will then enter the column with parameter 

codes. Find the parameter code you want to change and push 

the two buttons simultaneously. When you have changed the 

value, save the new value by once more pushing the two buttons 

simultaneously.

Gives access to the menu (or cutout an alarm)

Gives access to changes

Saves a change

Examples of operations

Set one of the other menus
1. Push the upper button until a parameter is shown
2. Push one of the buttons and find the parameter you want to 

change

3. Push both buttons simultaneously until the parameter value is 

shown

4. Push one of the buttons and select the new value
5. Push both buttons again to conclude the setting

SW =1.2x

Function

Param.

Min.

Max.

Fac. 

setting

Normal display

Shows the actual superheat/ valve's opening 

degree/ temperature. Define view in o17

-

K

If you wish to see the expansion valve’s actual 

opening degree, give the lower button a brief 

push (1s). Define view in o17

-

%

Reference

Units (0=°C+bar / 1=°F+psig)

r05

0

1

0

Start/stop of refrigeration

r12

OFF

On

1

Regulating parameters

P: Amplification factor Kp

n04

0.5

20

3

I:  Integration time T

n05

30 s

600 s

120

Max. value of superheat reference

n09

2 K

30 K

10

Min. value of superheat reference

n10

1 K

12 K

4

MOP

n11

0.0 bar 20 bar

20

Signal reliability during start-up. Safety time 

period.  

Should only be changed by trained staff.

n15

0 s

90 s

0

Signal reliability during start-up – Opening

degree’s start value. Should only be changed 

by trained staff

n17

0%

100%

0

Amplification factor for superheat

Changes should only be made by trained staff

n20

0.0

10.0

0,4

Value of min. superheat reference for loads 

under 10%

n22

1 K

15 K

2

”n37” and ”n38” are adapted to valve type ETS 

50 and should only be changed through the 

use of another valve
Number of steps from 0-100% opening degree 

(x10) 

(ETS 50=263, ETS 100=353)

ETS 12.5, ETS 25, ETS 50=263

ETS 100=353

ETS 250, ETS 400=381

n37

000 

stp*

5000 

stp *

263

Number of steps per second

n38

10 

stp/s

300 

stp/s

250

Integration time for inner loop (TnT0)

n44

10 s

120 s

30

Miscellaneous

Controller’s address

o03 *)

1

60

ON/OFF switch (service-pin message)

o04 *)

-

-

Set supply voltage frequency

o12

50 Hz

60 Hz

50

Select display for ”normal picture”

1:  Superheat

2:  Valve’s opening degree

3:  Air temperature

o17

1

3

1

Manual control of outputs:

OFF: no manual control 

3: Alarm relay activated (cut out)

At settings 3, ”o45” will be active

o18

off

3

0

Working range for pressure transmitter – min. 

value

o20

-1 bar

60 bar

-1.0

Working range for pressure transmitter – max. 

value

o21

-1 bar

60 bar

12

Refrigerant setting

1=R12.  2=R22.  3=R134a.  4=R502.  5=R717. 

6=R13.  7=R13b1.  8=R23.  9=R500.  10=R503.  

11=R114.  12=R142b. 13=User defined. 

14=R32. 15=R227.  16=R401A.  17=R507. 

18=R402A.  19=R404A. 20=R407C.  21=R407A.  

22=R407B.  23=R410A.  24=R170.  25=R290.  

26=R600.  27=R600a.  28=R744.  29=R1270.

o30

0

29

0

*) The display on the controller can show 3 digits only, but  the setting 
value has 4 digits. Only the 3 most important will be shown. 
It means f.ex. . 250 will give a setting of 2500.

Operation

Menu survey

Summary of Contents for EKC 312

Page 1: ...njection ensures optimum utilisation of the evaporator and hence a high suction pressure y y The superheating is regulated to the lowest possible value User manual Electronic superheat controller Type...

Page 2: ...ve regulation of the refrigerant injection ensures optimum utilisation of the evaporator and hence a high suction pressure y y The superheating is regulated to the lowest possible value Functions y y...

Page 3: ...on is stopped when the connection is interrupted The function must be used when the compressor is stopped The controller then closes the solenoid valve so that the evaporator is not charged with refri...

Page 4: ...umption Controller ETS step motor 5 V A 1 3 V A Input signal Press transmitter 4 20 mA from AKS 33 Digital input from external contact func tion Sensor input 2 pcs Pt1000 ohm Alarm relay 1 pcs SPST AC...

Page 5: ...ification factor Kp If the Kp value is reduced the regulation becomes slower n04 Kp factor I Integration time Tn If the Tn value is increased the regulation becomes slower n05 Tn sec Max value for the...

Page 6: ...e if 2 has been selected Temperature reference if 3 has been selected o17 Display mode Manual control of outputs For service purposes the individual relay outputs and the ETS output can be forced Howe...

Page 7: ...Te Read the temperature at the S4 sensor u27 S4 temp Read value of current signal from pressure transmitter AIB u29 AI B mA DO1 Alarm Read status of alarm relay For Danfoss only Start up time for safe...

Page 8: ...ve s actual opening degree give the lower button a brief push 1s Define view in o17 Reference Units 0 C bar 1 F psig r05 0 1 0 Start stop of refrigeration r12 OFF On 1 Regulating parameters P Amplific...

Page 9: ...tcircuited S2 sensor E17 Cut out S4 sensor E18 Shortcircuited S4 sensor E20 The input signal on terminals 14 15 is outside the range P0 signal A11 Alarm message No refrigerant has been selected A43 Ch...

Page 10: ...are no substitute for normal good engineering practice Danfoss wil not be responsible for any goods or plant components damaged as a result of the above defects It is the installer s responsibility t...

Page 11: ...the regulation 2 Follow the menu survey on page 6 and set the various para meters to the required values 3 Switch on the external switch and regulation will start 4 Follow the actual superheat on the...

Page 12: ...uide for extended operation RC8AC Here you can see how a data communication connection to ADAP KOOL Refrigeration control systems can be established If the distance between EKC 312 and the ETS valve e...

Reviews: