Electronic superheat controller, type EKC 312

Function

Parameter Parameter by operation via data communication

Refrigerant setting

Before refrigeration can be started, the refrigerant must be defined. 

You can select the following refrigerants:

1=R12.  2=R22.  3=R134a.  4=R502.  5=R717.  6=R13.  7=R13b1.  

8=R23.  9=R500.  10=R503.  11=R114.  12=R142b. 13=User defined. 

14=R32. 15=R227.  16=R401A.  17=R507. 18=R402A.  19=R404A. 

20=R407C.  21=R407A.  22=R407B.  23=R410A.  24=R170.  25=R290.  

26=R600.  27=R600a.  28=R744.  29=R1270.  

(Warning: Wrong selection of refrigerant may cause damage to the 

compressor).

o30

Refrigerant

Service

Service

A number of controller values can be printed for use in a service 

situation.
Read status of input DI (start/stop input).

u10

DI

Read the temperature at the S2 sensor.

u20

S2 temp.

Read superheat.

u21

SH

Read the control’s actual superheat reference.

u22

SH ref.

Read the valve’s opening degree.

u24

OD%

Read evaporating pressure.

u25

Evap. pres. Pe

Read evaporating temperature.

u26

Evap.Press.Te

Read the temperature at the S4 sensor.

u27

S4 temp.

Read value of current signal from pressure transmitter (AIB).

u29

AI B mA

--

DO1 Alarm
Read status of alarm relay

For Danfoss only
Start-up time for safety signal

If the controller does not obtain a reliable signal within this period 

of time the con-troller will in other ways try to establish a stable 

signal. (A too high value may result in a flooded eaporator).

The value should only be changed by specially trained staff.

n15

StartUp time

Signal safety during start-up

The control function uses the value as start value for the valve’s 

opening degree at each thermostat cutin. By adaptive control the 

controller continuously calculates a new value.

The value should only be changed by specially trained staff.

n17

Start OD%

Operating status

The controller’s operating status can be called forth by a brief (1s) 

activation of the upper button. If a status code exists it will be 

shown. (Status codes have lower priority than alarm codes. This 

means that status codes cannot be seen if there is an active alarm 

code. The  status code have the following meaning:

EKC State 
(0 = regulation)

S10: Refrigeration stopped by the internal or external start/ stop.

10

S26: No refrigerant selected.

26

Survey of functions

Summary of Contents for EKC 312

Page 1: ...njection ensures optimum utilisation of the evaporator and hence a high suction pressure y y The superheating is regulated to the lowest possible value User manual Electronic superheat controller Type...

Page 2: ...ve regulation of the refrigerant injection ensures optimum utilisation of the evaporator and hence a high suction pressure y y The superheating is regulated to the lowest possible value Functions y y...

Page 3: ...on is stopped when the connection is interrupted The function must be used when the compressor is stopped The controller then closes the solenoid valve so that the evaporator is not charged with refri...

Page 4: ...umption Controller ETS step motor 5 V A 1 3 V A Input signal Press transmitter 4 20 mA from AKS 33 Digital input from external contact func tion Sensor input 2 pcs Pt1000 ohm Alarm relay 1 pcs SPST AC...

Page 5: ...ification factor Kp If the Kp value is reduced the regulation becomes slower n04 Kp factor I Integration time Tn If the Tn value is increased the regulation becomes slower n05 Tn sec Max value for the...

Page 6: ...e if 2 has been selected Temperature reference if 3 has been selected o17 Display mode Manual control of outputs For service purposes the individual relay outputs and the ETS output can be forced Howe...

Page 7: ...Te Read the temperature at the S4 sensor u27 S4 temp Read value of current signal from pressure transmitter AIB u29 AI B mA DO1 Alarm Read status of alarm relay For Danfoss only Start up time for safe...

Page 8: ...ve s actual opening degree give the lower button a brief push 1s Define view in o17 Reference Units 0 C bar 1 F psig r05 0 1 0 Start stop of refrigeration r12 OFF On 1 Regulating parameters P Amplific...

Page 9: ...tcircuited S2 sensor E17 Cut out S4 sensor E18 Shortcircuited S4 sensor E20 The input signal on terminals 14 15 is outside the range P0 signal A11 Alarm message No refrigerant has been selected A43 Ch...

Page 10: ...are no substitute for normal good engineering practice Danfoss wil not be responsible for any goods or plant components damaged as a result of the above defects It is the installer s responsibility t...

Page 11: ...the regulation 2 Follow the menu survey on page 6 and set the various para meters to the required values 3 Switch on the external switch and regulation will start 4 Follow the actual superheat on the...

Page 12: ...uide for extended operation RC8AC Here you can see how a data communication connection to ADAP KOOL Refrigeration control systems can be established If the distance between EKC 312 and the ETS valve e...

Reviews: